WARNING:
Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage
or blindness.Never operate the Trio Air Purifying System out of the ductwork. Avoid touching the glass portion of the lamp with your hands.
Page 6 of 12
WARNING: Make sure unit is unplugged before installing the lamp.
WARNING: Make sure unit is unplugged before installing the lamp.
INSTALLATION
Make sure to install the Trio Healthy Home Purifi cation System so that the inlet or return air enters the side
containing the MERV13 particulate reduction cartridge fi rst.
1.
Remove the door to the unit per the steps listed previously.
2.
Remove the inside module & fi lter from the outer cabinet.
Take care not to bend or distort the cabinet. The ballast is
factory set to 120VAC. Please confi rm the voltage on both
ballasts is correct. The voltage can be changed in the fi eld to
230VAC by sliding the voltage selector switch in Figure 5 to
the 230 volt position. The plug must be replaced and wiring
must be done to applicable electrical codes.
3. Mount the outer cabinet to the support plenum.
NOTE:
NOTE: Do not use a screw length that will extend into or penetrate
the inside module containing the TiO2 catalyst or fi lter
cartridge.
4. In some cases the foot print of the air handler may be larger or smaller
than the outer enclosure of the Trio Unit. A metal adapter plate of 18
ga. metal should be fabricated to make a suitable transition. (Figure 6)
FIGURE 5
FIGURE 6
P/N 780105101 11/20 Rev B