background image

WARNING: never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. 

Never operate the UV-Aire™ AirPurifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

WARNING: Before installing or servicing a humidifier, air filter, heat system, or this unit, etc., always turn all 
power OFF and have unit unplugged. Electrical shock can cause personal injury or death. Never expose eyes 
or skin to direct UVC light from any source.
WARNING: To prevent water damage or electric shock, do not mount unit under a humidifier.
WARNING: Designed for a closed duct system. Do not mount near a supply or a return air opening.
WARNING: This product is designed for installation in the interior of weather-protected HVAC equipment or 
ductwork, or on the exterior of protected ductwork only.  For use on gas fired, oil fired, electric, split system 

heat pump forced air systems*, and the interior of weather-protected heat pump packaged units**.
*Split system heat pumps are systems where the air handler and the air conditioning compressor are 

separate units.

**Packaged units are systems where the air handler and the air conditioning compressor are built together 

and are installed outside of the building

MAGNET MOUNT INSTALLATION INSIDE PLENUM OR AIR HANDLER

1.  Choose a suitable location for the lamp in the supply plenum, return plenum, or air handler; preferably 
downstream from the air filter. For optimum “cleaning” effect on the A coil, mount the unit above or below 

the A-coil as close as possible while still illuminating the entire surface of the coil. (See Figure 1)
2.  Clean the mounting surface with degreaser and let dry.  The mounting surface must be clean and dry.

3.  Attach the Shield to the Mounting Bracket Assembly, if it is to be used, by 

bending the tabs on the shield over the Lamp Bracket notches (see Figure 2).  This 

will hold the shield in place during installation and lamp replacement.  The shield 
will be held firmly in place when the lamp is installed.
Attach the Shield in the best of four possible positions, to shield sensitive wiring 
and ductwork etc., and/or concentrate the UVC irradiation on a certain area or 
surface, and allow positioning of the mounting bracket that creates minimal 

obstruction to air flow.
4.  Attach the Lamp to the Mounting Bracket Assembly with the supplied #8-32 
wing nuts (see Dimensional Drawing).  Remove tag and alcohol swab from the 

lamp, and clean the lamp glass with the alcohol swab.   Avoid touching the cleaned 
lamp with your hands.

5.  Separate the Lamp Cable from the Ballast output cable connector, if attached.  The cables have 
mating watertight connectors to allow ease of installation and service (see Figure 3).
6.  Attach the Lamp Cable lamp connector to the lamp base, ensuring correct alignment of the rectangular pin 

arrangement.  The connector may be connected in either of two positions for which the pins line up.  Ensure 
that the lamp connector is firmly attached and that the sealing boot is pushed fully onto the lamp base.

Figure 1 Typical Installation

Figure 2

Summary of Contents for FlexMountUV UV-AIRE Series

Page 1: ... SYSTEM Model UV 13FM 17FM UV C light inhibits the growth and reproduction of germs and bacteria that circulate through a homes heating and air conditioning system The treatment is a safe silent and proven way to make your home a healthier place to live ITEMS INCLUDED IN KIT Twin Tube High Output UVC Lamp 24 VAC Ballast UL listed with Lamp Cable connector Lamp Cable with connector FlexMount Articu...

Page 2: ... condition nor for use in the mitigation treatment or prevention of any disease or condition INDICATION FOR USE There are different size units available depending on the tonnage of your HVAC system See chart below for determining the needs of your home The FlexMount UV Aire system is provided with a unique patent pending magnetically attached Mounting Bracket Assembly The mounting bracket assembly...

Page 3: ...nstream from the air filter For optimum cleaning effect on the A coil mount the unit above or below the A coil as close as possible while still illuminating the entire surface of the coil See Figure 1 2 Clean the mounting surface with degreaser and let dry The mounting surface must be clean and dry 3 Attach the Shield to the Mounting Bracket Assembly if it is to be used by bending the tabs on the ...

Page 4: ... that the 120V transformer power source be wired through a safety disconnect switch such as a door switch that will disconnect power to the transformer if the access panel to the UVC lamp installation area is removed see Wiring Diagram If such a switch is not present on the equipment it is recommended that a door interlock switch not included min 3A 24VAC rating be installed and wired into the 24V...

Page 5: ...hese steps for installation 1 Separate the lamp mounting portion of the Lamp Bracket from the remainder of the lamp bracket see Figure 4 by bending back and forth or cut with snips or hacksaw 2 Attach the shield to the separated bracket on the side opposite from the lamp mounting studs see Figure 5 if it is to be used Any of the four attachment positions may be used 3 Insert the lamp through the o...

Page 6: ...XTERNALLY ON A PLENUM OR AIR DUCT DISCONNECT THE LAMP CABLE FROM THE LAMP BEFORE REMOVING THE LAMP FROM THE EXTERNAL MOUNT BRACKET VERIFY THAT THE LAMP IS NOT LIT BY LOOKING THROUGH THE SAFETY VIEWPORT BEFORE REMOVING ANY ACCESS PANELS OR THE LAMP FROM THE EXTERNAL MOUNT BRACKET 1 Verify that the lamp is not lit by looking through the safety viewport 2 Disconnect the Lamp Cable connector from end ...

Page 7: ...e glass portion of the lamp with your hands TROUBLESHOOTING GUIDE 1 If the lamp does not light up replace the lamp 2 If the lamp still does not light up after replacing the lamp replace ballast REPLACEMENT PARTS LIST MODEL LAMP P N BALLAST P N UV 13FM 46632513 46635900 UV 17FM 46632517 OPTIONAL ACCESSORY PARTS LIST MODEL DESCRIPTION PART NUMBER TR50VA Transformer 120 208 240V Primary 24VAC 50 VA U...

Page 8: ... 252 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46631000 Rev A 7 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com warranty ...