Field Controls FAVC Installation Manual Download Page 31

Page 31 of 36

10A. HOW TO SIZE A FRESH AIR DAMPER

10. SIZING OF FRESH AIR DAMPER AND HRV/ERV

Select the size of the Fresh Air Damper (FAD) based on the continuous ventilation CFM requirement 
multiplied by 3 and adjusted for the actual fresh air ductwork installation parameters to allow the 
FAVC system operate 10 minutes on every 30 minutes.  

There are two methods available to Size the Fresh Air Duct: Estimated and Design.

Estimated Method for FAD Sizing: 

Use Tables 6A and 6B to select fresh air damper air fl ow rate in CFM. 

Table 6A shows estimated FAD air fl ow rates based on smooth wall fresh air pipe ductwork at various 
lengths. Table 6B shows estimated FAD air fl ow rates based on Flex Duct fresh air pipe ductwork at 
various lengths. Short Run Length section is for short simple installations with no elbows or reducing 
fi ttings installed with a total of 10 foot equivalent duct length or less.  Medium Run Length section is for 
8-19 foot duct runs with 1 or less elbows or reducing fi ttings installed with a total of 30 foot equivalent 
duct length or less. Long Run Length section is for 15-28 foot duct runs with 2 or less elbows or reducing 
fi ttings installed with a total of 30 foot equivalent duct length or less.

P/N 780100700 07/18  Rev F

Table 6A: FAD Damper Size Air Flow in CFM  for Smooth Wall Pipe

Table 6B: FAD Damper Size Air Flow in CFM  based on Flex Wall Duct

Design Method for FAD Sizing: 

The design method uses the combination of equivalent duct length 

based on actual ducting design and static pressure measurement at inlet side of fresh air ducting with 
air handler running in cooling and/or heating modes. Figure 15, on page 15, shows a typical FAD 
installation in a basement confi guration. Tables 2A and 2B are used to select the continuous ventilation 
CFM requirement according to size of home (in square foot), number of bedrooms and applicable 
ASHRAE62.2 code year.  Tables 7A and 7B are used to calculate equivalent feet for vent piping and 
reducer/increaser fi ttings. Table 8 is used to verify your fresh air damper air fl ow selection based on 
actual negative return air static pressure (inches WC) measurement taken at the intake of fresh air 
ductwork.

Summary of Contents for FAVC

Page 1: ...OMPLETELY READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION BEFORE PROCEEDING WITH THE INSTALLATION Meets the requirements of the ASHRAE 62 2 standard for ventil...

Page 2: ...Page 2 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Page 3: ...itch 4 15 7 INSTALLATION 16 7A Installation Locations 16 i FAVC location 16 17 ii FAVC Mounting 18 iii Intake Air Connection Duct Installation 19 iv Fresh Air Damper or HRV ERV location 20 7B Wiring a...

Page 4: ...ventilation controller in an outdoor location and or wet location Do not obstruct or cover the fresh air intake or air outlet of the ventilation system Provisions should be made for make up air requi...

Page 5: ...Page 5 of 36 P N 780100700 07 18 Rev F 1 FAVC LAYOUT OVERVIEW FIGURE 1 FAVC Functional Product Layout shown with cover removed...

Page 6: ...ect the number of bedrooms associated with your application 6 Locate where the square footage row and bedroom column intersect This determines the CFM continuous ventilation dial setting 7 Record and...

Page 7: ...5 6 500 30 38 45 53 60 68 600 33 41 48 56 63 71 700 36 44 51 59 66 74 800 39 47 54 62 69 77 900 42 50 57 65 72 80 1000 45 53 60 68 75 83 1100 48 56 63 71 78 86 1200 51 59 66 74 81 89 1300 54 62 69 77...

Page 8: ...heating and cooling cycle 4 Determine the fresh air intake internal round duct size and type If square or rectangular duct convert free area to the nearest round duct size 5 Determine the fresh air in...

Page 9: ...fully adjust the CFM Cool Vent dial Use the recorded volume that was determined from using one of the previous methods and Recorded in Section 2B Note Locate arrow on the dial stem Align to the desire...

Page 10: ...door temperatures During the summer months when outdoor temperatures summer months when outdoor temperatures are at 85 F or higher the FAVC will prohibit are at 85 F or higher the FAVC will prohibit v...

Page 11: ...e is between 100 F and 17 F depending on if the HVAC system is in heating or cooling mode and depending on indoor relative humidity change during the ventilation cycle Below 25 F outside temperature a...

Page 12: ...entilation is limited to prevent induct condensation from occurring FIGURE 7 Cold Climate Operation 3C COLD CLIMATE ZONE In Climate Mode HOT The FAVC will provide fresh outside ventilation if the outs...

Page 13: ...lectrically isolated from the other pairs Unused input pairs should be left unconnected The associated control setting does not matter if the input is not used The optional inputs are not required for...

Page 14: ...A3C terminal should be connected to common 24VAC power This input is typically used to monitor a clothes dryer or other medium CFM suitable exhaust fan appliance The control setting represents the air...

Page 15: ...13 for DIP Switch 4 setting to configure FAVC central fan control during a call for ventilation function This is ideal for use with an ERV HRV system or to remote control a bathroom fan or exhaust fa...

Page 16: ...VAC system when the small room is designed to act as a return air plenum using the optional FAVC mounting bracket Field Controls P N 602600150 refer to Figure 16 for return air closet installation inf...

Page 17: ...CE AIR HANDLER FILTER TRIO 1200 2000 FRESH AIR DAMPER FRESH AIR OUTSIDE WALL FRESH AIR INTAKE HOOD W SCREEN OUTDOOR TEMPERATURE SENSOR R A VENT FROM HOME FAVC ON WALL MOUNT BRACKET INSIDE WALL OPTIONA...

Page 18: ...h square hole in ductwork to allow the controller s Humidity Temperature Sensor to sense actual return air duct environmental conditions The Humidity Temperature sensor extends out from the back of th...

Page 19: ...sh air inlets 7Aiii Intake Air Connection and Duct Installation Ductwork Specification All flexible ducts must meet UL safety standards for Class I air ducts and connectors All ducting must be install...

Page 20: ...nd Fresh Air Intake location The HRV ERV unit should be installed in an area where the air is tempered to avoid freezing of the condensate line The contractor should install the unit in an area that i...

Page 21: ...iring Diagrams 1 and 2 for basic ventilation wire requirements using Fresh Air Damper or HRV ERV devices Refer to wiring diagrams 3 and 4 when adding optional appliance monitoring and or control featu...

Page 22: ...andler R is the 24VAC hot The FAVC does not need to be connected to the Y compressor or cooling as the GT thermostat fan signal will suffice for all applications including heat pumps There may be func...

Page 23: ...Page 23 of 36 DIAGRAM 1 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and Fresh Air Damper P N 780300901 P N 780100700 07 18 Rev F...

Page 24: ...Page 24 of 36 DIAGRAM 2 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and HRV ERV Device P N 780300902 P N 780100700 07 18 Rev F...

Page 25: ...he ODT sensor is supplied with the FAVC and MUST BE INSTALLED for the FAVC to operate properly The best loca tion to mount the ODT sensor is next to the fresh air damper on the side wall of the duct L...

Page 26: ...iance can be monitored if its air flow is within the appliance dial setting range The appliance monitoring features are based on the following equipment devices Appliance 1 HRV ERV or Bathroom Fan or...

Page 27: ...RAM 3 Appliances 1 thru 4 Monitoring Connections using Current or Pressure Sensors P N 780300903 NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780...

Page 28: ...ntrol and Monitoring Appliances using Current or Pressure Sensors and External Aube Relay NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780300904...

Page 29: ...Blue Red No Color Green LED indicates outside air meets ventilation requirements without restrictions This is normal system will function normally Blue LED indicates the outside air temperature or re...

Page 30: ...OOR TEMPERATURE SENSOR 620000102 C SENSOR CURRENT SENSOR 24VAC 46676600 P SENSOR PRESSURE SENSOR 24VAC 46679400 40XFMR TRANSFORMER UV 16 24 PLUG IN 46524800 50XFMR TRANSFORMER 24VAC 50VA 46638800 24VA...

Page 31: ...fittings installed with a total of 30 foot equivalent duct length or less Long Run Length section is for 15 28 foot duct runs with 2 or less elbows or reducing fittings installed with a total of 30 f...

Page 32: ...able 8 to select fresh air damper size based on measuring static pressure at the return intake multiple the continuous ventilation CFM value by 3 for fresh air damper CFM and calculated total equivale...

Page 33: ...sh air damper size Step 2 Static pressure in the return is 0 15 inches WC measured Step 3 Ductwork system design consists of i Two 6 diameter 45 Elbow 10 equivalent feet ii 10 feet of straight 6 smoot...

Page 34: ...____ CFM CFM Appliance 4 __________________________ CFM 100 400 400 75 75 200 850 Damper Size ________________________________ Inches or HRV Model _________________________________ CFM ___________ or...

Page 35: ...Page 35 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Page 36: ...ted from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or any Field Con...

Reviews: