Field Controls FAVC Installation Manual Download Page 15

Page 15 of 36

Energy Saving Mode

 is a confi gurable feature designed to allow 

the FAVC to control or not to control the central fan during a call for 
ventilation when the thermostat is not in a heating or cooling mode
condition.  If energy saving mode is ON (ENABLED) and the
thermostat requires a heating or cooling action, the CFM Heat Vent 
and CFM Cool Vent dial rates for heating and cooling modes are 
used in combination with CFM continuous dial rate to determine 
if the HVAC has operated long enough to meet the ventilation
requirement. If the heat or cooling run time driven by the thermostat 
does not meet the required ventilation run time for the heat/cooling 
event,  the FAVC will keep the fresh air damper open and activate 
the auxiliary exhaust device once the central fan has shut down 
due to the thermostat control call. In specifi c terms, the vent (V) and
auxiliary fan (E) terminals of the FAVC will remain active based 
on the required time to meet ventilation requirements using the
Appliance #1 fl ow rate setting.

DIP 3

FUNCTION

ON

FAN CYCLES WITH 

APPLIANCE #3 INPUT

OFF

FAN DOES NOT CYCLE WITH

APPLIANCE #3 INPUT

ENERGY SAVING MODE

DIP 4

FUNCTION

ON

ENERGY SAVINGS MODE,

EXHAUST FAN CONTROL

OFF

DISABLED

FIGURE 11:  DIP Switch 3 Fan-

Activity with Appliance #3

FIGURE 13:  DIP Switch 4

Energy Saving Mode

P/N 780100700 07/18  Rev F

5. MAKE-UP AIR OPTIONS - DIP Switch 3

To 

ENABLE Energy Saving Mode

, set DIP Switch 4 to ON (ENABLE) to allow the FAVC to not control the 

central fan during a call for ventilation. In the ENABLE mode, the FAVC will independently energize the 
vent (V) and auxiliary fan (E) terminals when fresh air ventilation is required; and the HVAC system is 
not running. Refer to Figure 12 and Figure 13 for DIP Switch 4 setting to confi gure FAVC central fan 
control during a call for ventilation function.
This is ideal for use with an ERV/HRV system or to remote control a bathroom fan or exhaust fan. The 
FAVC will operate the central fan of the air handler under specifi c conditions, regardless if energy
saving mode is ON or OFF:

 

 Condition 1 

If the thermostat has had no calls for heat or cooling with in a 4-hour time 

 

 

 

 

period, the FAVC will cycle the central fan for one ventilation time period,

 

 Condition 2 

If appliance #3 has input monitoring event and DIP Switch 3 is set to 

 

 

 

 

ON, the central fan will operate whenever the appliance #3 is turned on, or

 

 

Condition 3 

If appliance #4 has an input monitoring event, the central fan will operate 

 

 

 

 

whenever appliance #4 is turned on.

FIGURE 10: DIP Switch3

6. ENERGY SAVING OPTION - DIP Switch 4

With the 

Energy Saving Mode 

OFF (DISABLED), the FAVC will turn ON the central fan and activate the 

vent (V) terminal for all ventilation requirements even if the thermostat is idle or off.

FIGURE 12:

Energy Saving DIP Switch 4

The FAVC is equipped with two make-up air features for use 
with high fl ow exhaust appliances such as kitchen range hoods, 
clothes dryers, and draft assisted gas log fi re places.  The primary
make-up air function is associated with appliance #4.  When a signal is
present on appliance #4 terminals, (A4 and A4C), the fresh air 
damper will open and the central fan will run.   The secondary
make-up air function is associated with appliance #3.  This feature is 
confi gurable with dip switch 3.  With the dip switch 3 set to off (de-
fault), will set the appliance #3 in a passive ventilation mode, such that 
only the fresh air damper will open when the appliance #3 is active.  To
select the make-up air mode for appliance #3, set dip switch #3 to 
on.  When appliance #3 is active, the fresh air damper will open and 
the central fan will run.  Refer to Figure 10 and 11 to set dip switch 3. 

Summary of Contents for FAVC

Page 1: ...OMPLETELY READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION BEFORE PROCEEDING WITH THE INSTALLATION Meets the requirements of the ASHRAE 62 2 standard for ventil...

Page 2: ...Page 2 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Page 3: ...itch 4 15 7 INSTALLATION 16 7A Installation Locations 16 i FAVC location 16 17 ii FAVC Mounting 18 iii Intake Air Connection Duct Installation 19 iv Fresh Air Damper or HRV ERV location 20 7B Wiring a...

Page 4: ...ventilation controller in an outdoor location and or wet location Do not obstruct or cover the fresh air intake or air outlet of the ventilation system Provisions should be made for make up air requi...

Page 5: ...Page 5 of 36 P N 780100700 07 18 Rev F 1 FAVC LAYOUT OVERVIEW FIGURE 1 FAVC Functional Product Layout shown with cover removed...

Page 6: ...ect the number of bedrooms associated with your application 6 Locate where the square footage row and bedroom column intersect This determines the CFM continuous ventilation dial setting 7 Record and...

Page 7: ...5 6 500 30 38 45 53 60 68 600 33 41 48 56 63 71 700 36 44 51 59 66 74 800 39 47 54 62 69 77 900 42 50 57 65 72 80 1000 45 53 60 68 75 83 1100 48 56 63 71 78 86 1200 51 59 66 74 81 89 1300 54 62 69 77...

Page 8: ...heating and cooling cycle 4 Determine the fresh air intake internal round duct size and type If square or rectangular duct convert free area to the nearest round duct size 5 Determine the fresh air in...

Page 9: ...fully adjust the CFM Cool Vent dial Use the recorded volume that was determined from using one of the previous methods and Recorded in Section 2B Note Locate arrow on the dial stem Align to the desire...

Page 10: ...door temperatures During the summer months when outdoor temperatures summer months when outdoor temperatures are at 85 F or higher the FAVC will prohibit are at 85 F or higher the FAVC will prohibit v...

Page 11: ...e is between 100 F and 17 F depending on if the HVAC system is in heating or cooling mode and depending on indoor relative humidity change during the ventilation cycle Below 25 F outside temperature a...

Page 12: ...entilation is limited to prevent induct condensation from occurring FIGURE 7 Cold Climate Operation 3C COLD CLIMATE ZONE In Climate Mode HOT The FAVC will provide fresh outside ventilation if the outs...

Page 13: ...lectrically isolated from the other pairs Unused input pairs should be left unconnected The associated control setting does not matter if the input is not used The optional inputs are not required for...

Page 14: ...A3C terminal should be connected to common 24VAC power This input is typically used to monitor a clothes dryer or other medium CFM suitable exhaust fan appliance The control setting represents the air...

Page 15: ...13 for DIP Switch 4 setting to configure FAVC central fan control during a call for ventilation function This is ideal for use with an ERV HRV system or to remote control a bathroom fan or exhaust fa...

Page 16: ...VAC system when the small room is designed to act as a return air plenum using the optional FAVC mounting bracket Field Controls P N 602600150 refer to Figure 16 for return air closet installation inf...

Page 17: ...CE AIR HANDLER FILTER TRIO 1200 2000 FRESH AIR DAMPER FRESH AIR OUTSIDE WALL FRESH AIR INTAKE HOOD W SCREEN OUTDOOR TEMPERATURE SENSOR R A VENT FROM HOME FAVC ON WALL MOUNT BRACKET INSIDE WALL OPTIONA...

Page 18: ...h square hole in ductwork to allow the controller s Humidity Temperature Sensor to sense actual return air duct environmental conditions The Humidity Temperature sensor extends out from the back of th...

Page 19: ...sh air inlets 7Aiii Intake Air Connection and Duct Installation Ductwork Specification All flexible ducts must meet UL safety standards for Class I air ducts and connectors All ducting must be install...

Page 20: ...nd Fresh Air Intake location The HRV ERV unit should be installed in an area where the air is tempered to avoid freezing of the condensate line The contractor should install the unit in an area that i...

Page 21: ...iring Diagrams 1 and 2 for basic ventilation wire requirements using Fresh Air Damper or HRV ERV devices Refer to wiring diagrams 3 and 4 when adding optional appliance monitoring and or control featu...

Page 22: ...andler R is the 24VAC hot The FAVC does not need to be connected to the Y compressor or cooling as the GT thermostat fan signal will suffice for all applications including heat pumps There may be func...

Page 23: ...Page 23 of 36 DIAGRAM 1 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and Fresh Air Damper P N 780300901 P N 780100700 07 18 Rev F...

Page 24: ...Page 24 of 36 DIAGRAM 2 Conventional Wiring Diagram Thermostat Air Handler FAVC ODT Sensor and HRV ERV Device P N 780300902 P N 780100700 07 18 Rev F...

Page 25: ...he ODT sensor is supplied with the FAVC and MUST BE INSTALLED for the FAVC to operate properly The best loca tion to mount the ODT sensor is next to the fresh air damper on the side wall of the duct L...

Page 26: ...iance can be monitored if its air flow is within the appliance dial setting range The appliance monitoring features are based on the following equipment devices Appliance 1 HRV ERV or Bathroom Fan or...

Page 27: ...RAM 3 Appliances 1 thru 4 Monitoring Connections using Current or Pressure Sensors P N 780300903 NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780...

Page 28: ...ntrol and Monitoring Appliances using Current or Pressure Sensors and External Aube Relay NOTE HVAC Thermostat Outdoor Sensor Wiring and FAD HRV ERV Connections not shown for simplicity P N 780300904...

Page 29: ...Blue Red No Color Green LED indicates outside air meets ventilation requirements without restrictions This is normal system will function normally Blue LED indicates the outside air temperature or re...

Page 30: ...OOR TEMPERATURE SENSOR 620000102 C SENSOR CURRENT SENSOR 24VAC 46676600 P SENSOR PRESSURE SENSOR 24VAC 46679400 40XFMR TRANSFORMER UV 16 24 PLUG IN 46524800 50XFMR TRANSFORMER 24VAC 50VA 46638800 24VA...

Page 31: ...fittings installed with a total of 30 foot equivalent duct length or less Long Run Length section is for 15 28 foot duct runs with 2 or less elbows or reducing fittings installed with a total of 30 f...

Page 32: ...able 8 to select fresh air damper size based on measuring static pressure at the return intake multiple the continuous ventilation CFM value by 3 for fresh air damper CFM and calculated total equivale...

Page 33: ...sh air damper size Step 2 Static pressure in the return is 0 15 inches WC measured Step 3 Ductwork system design consists of i Two 6 diameter 45 Elbow 10 equivalent feet ii 10 feet of straight 6 smoot...

Page 34: ...____ CFM CFM Appliance 4 __________________________ CFM 100 400 400 75 75 200 850 Damper Size ________________________________ Inches or HRV Model _________________________________ CFM ___________ or...

Page 35: ...Page 35 of 36 THIS PAGE LEFT INTENTIONALLY BLANK P N 780100700 07 18 Rev F...

Page 36: ...ted from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or any Field Con...

Reviews: