05-06  Testing Cooling Airflow Limits 

In TEST 5, the system 
is Off.

Touch 

 to go to 

TEST 6 to activate 
cooling. Verify the 
equipment is 
operating.

To determine the 
maximum allowable 
airflow to the 
sleeping area, touch

NEXT

This test is used to determine the maximum 
allowable airflow to the Sleeping and Living 
Areas in COOLING.

Maximum Allowable Airflow in Cooling 

to the Sleeping Area

To determine the 
maximum allowable 
airflow to the Living 
Area, touch the 

 key until the 

airflow is too great

DOWN

Maximum Allowable Airflow in cooling 

to the Living Area

Touch 

 to end testing and return to normal 

thermostat operation.

ENTER

Enter the maximum airflow limits using Options 
20 through 23 of the installer menu.

The test can also be used to perform the HERS 
Total Airflow test. The test activates a cooling call 
and opens both dampers to 100%.

Airflow %

Cool

Airflow %

Cool

Test

Test

NEXT

NEXT

ENTER

ENTER

Sleeping

Living

Sleeping

Living

Airflow %

Cool

Test

NEXT

ENTER

Sleeping

Living

the 

 key until the airflow is too great and 

causes noise or annoyance. Lower the airflow 
using the 

 key until it is acceptable. This is 

the maximum allowable airflow in cooling to the 
sleeping area. Record the airflow value.

UP

DOWN

and causes noise or annoyance. Increase the 
airflow using the 

 key until it is acceptable. This 

is the maximum allowable airflow in cooling to 
the living area. Record the airflow value.

UP

01-02  Testing Indoor Fan Operation

In TEST 1, the Fan is 
Off.

Touch 

 to go to 

TEST 2 to turn on the 
indoor fan. Verify the 
fan is operating and 
delivering airflow to 
the sleeping and 
living area.

Touch 

 to go to 

Testing Heating 
Airflow Limits.

NEXT

NEXT

This test is used to verify that the indoor fan is 
operating correctly.

Sleeping

Living

Airflow %

Test

Airflow %

Test

NEXT

NEXT

Sleeping

Living

FAN

ENTER

FAN

ENTER

03-04  Testing Heating Airflow Limits

In TEST 3, the system 
is Off.

Touch 

 to go to 

TEST 4 to activate 
heating. Verify the 
equipment is 
operating.

To determine the 
maximum allowable 
airflow to the 
Sleeping Area, touch

NEXT

This test is used to determine the maximum 
allowable airflow to the sleeping area and the 
living area in HEATING.

Maximum Allowable Airflow in Heating 

to the Sleeping Area

Airflow %

Test

Airflow %

Test

Sleeping

Living

Sleeping

Living

NEXT

NEXT

ENTER

ENTER

Heat

Heat

the 

 key until the airflow is too great and 

causes noise or annoyance. Lower the airflow 
using the 

 key until it is acceptable. This is 

the maximum allowable airflow in heating to the 
sleeping area. Record the airflow value.

UP

DOWN

Sleeping

Living

Airflow %

Heat

Test

NEXT

ENTER

To determine the 
maximum allowable 
airflow to the living 
area, touch the 

 key until the 

airflow is too great

DOWN

and causes noise or annoyance. Increase the 
airflow using the 

 key until it is acceptable. This 

is the maximum allowable airflow in heating to 
the living area. Record the airflow value.

UP

Maximum Allowable Airflow in Heating 

to the Living Area

Touch 

 to go to Testing Cooling Airflow 

Limits.

NEXT

ACCESSING THE TEST MENU

To access the Test Menu, 

 and 

 the 

hidden Next key for 7 seconds until the fan test 
screen (TEST 01) appears.

TOUCH

HOLD

The Test Menu is used to test the Indoor Fan 
Operation, Allowable Heating Airflow Limits and 
Allowable Cooling Airflow Limits.

Living

Tu

Day

Sleeping

Living

Airflow %

COOL

Schedule

AUTO

FAN

MENU

MODE

Cool

Set To

SYSTEM

AM

TOUCH

HOLD

 and 

 this key for 7 seconds

to access the Installer Options.

The Test Menu can also be used to perform the 
HERS Total Airflow test. TEST 05-06 activates a 
cooling call and opens both dampers to 100% 
enabling the installer to perform the test.

INSTALLER SECTION

page 13 of 16

P/N 780101703 3/18 Rev A

Summary of Contents for EvenAir T21

Page 1: ...OW to the sleeping and living areas in a home and provides remote access to your HVAC system using a smart phone tablet or PC The thermostat is installed in the downstairs living area a temperature se...

Page 2: ...es on 24VAC from the HVAC equipment using the R and C wires Connects to the home WiFi network to provide remote access via the internet using smart phone tablet or PC FEATURES The airflow to the livin...

Page 3: ...control feature This features allows the homeowner to change the airflow level as desired and hold that level indefinitely This feature needs to be enabled using Installer Option 18 The homeowner then...

Page 4: ...Hold Vacant Changing the Setpoint Temperature The UP DOWN keys are used to change the setpoint temperature Tu Day Airflow Schedule MENU MODE Cool Set To AM Living Living Sleeping 5 Tu Day Airflow Sch...

Page 5: ...ng User Option 1 to change the Night Schedule Start Time Default airflow level upstairs is 130 If a different airflow level is desired use User Option 4 to change the airflow level in heating and User...

Page 6: ...s a User Option Nighttime Airflow Control Set the Nighttime Airflow in Heating will only show if Nighttime Airflow Control is ON Set the Nighttime Airflow in Cooling will only show if Nighttime Airflo...

Page 7: ...anual before installing EvenAir products When servicing EvenAir system or accessing products turn off all power to these items R C WOB EQUIPMENT Y G TS COM COM CLS CLS OPN OPN Sleeping Living W2E Y2 T...

Page 8: ...a the damper may be wired in parallel LEDs on the damper actuator indicate when the damper is fully open green or fully closed red When properly installed the dampers will never fully close Gas Electr...

Page 9: ...nted circuit board and hand tighten screw The TS5 sensor can be installed in a single gang box or directly to the wall using the hardware provided HAND TIGHTEN Printed circuit board Brass washer Use 2...

Page 10: ...4 Heating Stages Htg 0 1 or 2 1 Only displayed if HP selected in Option 1 14 15 16 17 18 19 21 20 22 23 Night Level LCD Backlight Airflow Control On or Off Enable User Airflow Control Up Stage Time Ma...

Page 11: ...s used to display the next option The ENTER key is used to save options and return to normal thermostat operation The hidden BACK key is used to return to previous options and is located to the left o...

Page 12: ...tomatic airflow control on or off If off the dampers fully open nighttime airflow options are disabled and airflow is no longer displayed on the thermostat 17 Airflow Control On or Off Factory Default...

Page 13: ...ing Living Airflow Test Airflow Test NEXT NEXT Sleeping Living FAN ENTER FAN ENTER 03 04 Testing Heating Airflow Limits In TEST 3 the system is Off Touch to go to TEST 4 to activate heating Verify the...

Page 14: ...ure sensor s Check for open wires or shortages ENTER AM Touch the UP DOWN keys to change the HOUR Touch NEXT CHANGE THE HOUR Touch the UP DOWN keys to change the MINUTE Touch NEXT CHANGE THE MINUTE To...

Page 15: ...ting airflow to the sleeping area the airflow is actually directed to the living area and when directing the airflow to the living area the airflow is actually directed to the sleeping area Turn syste...

Page 16: ...rols product visit www fieldcontrols com Field Controls Technical Support 1 800 742 8368 fieldtec fieldcontrols com Phone 252 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC c Field...

Reviews: