REPLACING UVC GERMICIDAL LAMPS                           

 

 

 

 

1.  Always wear protective eye goggles when servicing UVC germicidal lamps. 

 

2.  Unplug the power cord from main outlet on the Cube unit. 

 

3.  Remove the central Cube metal cover which is held in place with eight (8) screws.  This will allow 

access to the 3 PRO-Cell™ modules and electronics. 
 

4.  Next to the MERV13 filter is the PRO-Cell/MM2025C Master Module. Unplug the power cord, remove 

service panel metal cover from the PRO-Cell/MM2025C Master Module and set aside metal cover. 
 

5.  The remaining two modules are the PRO-Cell/SM2025 Slave Modules.  Unplug the low voltage wires 

from the master module and the two slave modules. 
 

6.  Unplug the UVC germicidal lamp wires from each of the lamp connections. 

 

7.  Each module is held in place by a retaining bracket by two (2) thumb screws.  Unscrew the thumb 

screws.  Set aside thumb screws and retaining brackets. 
 

8.  Carefully slide forward the PRO-Cell™ Module to a point where access to the far end of the UVC 

germicidal lamps can be reached, or fully withdraw the module completely from the frame.  Loosen the 
UVC germicidal lamp clamp thumb screw located at the far end of the UVC germicidal lamp so as to be 
able to carefully remove the lamp through the rubber grommet on the front of the module. 

 

IMPORTANT 

 

AVOID TOUCHING THE NEW UVC GERMICIDAL LAMPS WITH BARE HANDS AS THE OIL ON THE SKIN CAN IMPEDE LAMP 
PERFORMANCE OR CAUSE PERMATURE FAILURE OF LAMP ILLUMINATION. 
 
THE USE OF COTTON GLOVES OR PAPER TOWELS IS PREFERRED WHEN HANDLING THE UVC GERMICIDAL LAMPS. 

 
9.  Replace with new UVC germicidal lamps:  re-insert the lamp through the rubber grommet at the front, 

and insert into the UVC germicidal lamp clamp at the far end until the plastic shield of the lamp rests 
softly against the frame. 

 

10. Finger-tighten the thumb screws on far end of the UVC germicidal lamp holding clamp.  

 

11. Replace all six (6) lamps in the same fashion. 

 

12. Fully re-insert the 3 PRO-Cell™ modules into the frame.  Replace retaining bracket and re-fasten each 

with two thumb screws. Repeat steps on all modules. 
 

13. Re-attach all low voltage wires and power cord. 

 

14. Re-attach the central PRO-Cell™ module metal cover with screws supplied making sure the rubber 

gaskets are properly seated to assure no air leakage. 
 

15. Re-connect power cord and check through the six UVC germicidal lamp view ports for illumination. 

 

Summary of Contents for Cube

Page 1: ...Field Controls 2630 Airport Road Kinston NC 28504 252 522 3031 www fieldcontrols co ...

Page 2: ...cations 4 Operation 5 Air Cycles HHSC 5 Service 6 Changing Filters 6 Replacement Filters and Germicidal UVC Lamps 7 Resetting Remote Service Panel 8 Installation 9 Transitions for In Duct Mounting 9 10 Electrical Schematic 11 Performance Data 12 Warranty 13 ...

Page 3: ...sult The Cube is rated for standard ambient air temperatures during heating and cooling functions The Cube is not rated for temperatures in excess of 125 Degrees Fahrenheit 52 Degrees Celsius Do not attempt to clean the PRO Cell honeycomb catalyst with cleaning solutions The PRO Cell catalyst is radiated with short wave germicidal ultraviolet light during periods of airflow and is self cleaning Do...

Page 4: ... 23 H x 31 W x 29 D 585mm H x 787mm W x 737mm D Standard with MERV13 Media Pre Filter and 3 PRO Cell Modules 1 Master Module MM 2 Slave Module SM CFM in W C pa 1200 0 19 47 326 1600 0 26 64 763 2000 0 35 87 181 Frame body between flanges Flange height Cover for MERV13 Pre Filter W L H 1 2 all around W H D 24 3 4 30 3 4 22 12mm all around 3 5 16 19 1 2 620mm 784mm 560mm 84mm 484mm 12mm Outside dime...

Page 5: ...The length of operation depends on the location of the facility in relation to point source of pollution such as refineries processing plants automobile traffic hair salons dog motels fitness center locker rooms and areas that produce high levels of pollutants Individuals that are sensitive to mold spores dust mites chemicals or have respiratory problems such as asthma emphysema and chronic allerg...

Page 6: ... 5 months and to red after six 6 months Change the post filter before the red LED light illuminates Carbon Post Filter is an onsite installed option Order Field Controls part number 46728500 model number 1RK027 Field Controls recommends replacing minimum every six 6 months The service light turns from green to yellow after five 5 months and to red after six 6 months Change the post filter before t...

Page 7: ... germicidal lamp clamp thumb screw located at the far end of the UVC germicidal lamp so as to be able to carefully remove the lamp through the rubber grommet on the front of the module IMPORTANT AVOID TOUCHING THE NEW UVC GERMICIDAL LAMPS WITH BARE HANDS AS THE OIL ON THE SKIN CAN IMPEDE LAMP PERFORMANCE OR CAUSE PERMATURE FAILURE OF LAMP ILLUMINATION THE USE OF COTTON GLOVES OR PAPER TOWELS IS PR...

Page 8: ...ers and UVC germicidal lamps are available from your authorized Field Controls Wholesaler Distributor or Contractor You may contact Field Controls for information on a Wholesaler Distributor or Contractor at Field Controls 2630 Airport Road Kinston NC 28504 252 522 3031 www fieldcontrols com PART NUMBER MODEL DESCRIPTION 46636500 TrioRM13 2025 20x25x4 MERV13 Repl Media Pre Filter 6 MCTN 46636700 T...

Page 9: ... certain to provide for a door open access to service covers TRANSITIONS FOR IN DUCT MOUNTING Metal adapter of 18 gauge sheet metal or greater and insulated should be fabricated to make suitable transitions Attach the transitions to the Cube and fasten with 10 x 1 2 self tapping sheet metal screws See Figure 2 illustration on following page 1 Tape all seams between the air handler blower return si...

Page 10: ...FIGURE 2 10 ...

Page 11: ...ELECTRICAL SCHEMATIC 11 ...

Page 12: ...PERFORMANCE DATA 12 ...

Page 13: ...WARRANTY 13 Refer to www fieldcontrols com for complete warranty statement ...

Reviews: