After proper air flow is established, the pressure switch adjustment is made by 
turning the pressure switch adjustment screw clockwise (See Figure 4) until 
burner operation stops. Turn the adjustment screw counterclockwise until 
burner ignites. Turn the adjustment screw an additional 1/4 to 3/4 turn 
counterclockwise to ensure adequate switch adjustment. 

WARNING:

 

Failure to properly adjust the pressure switch as specified above 

could lead to improper operation of the pressure switch which will result in a 
hazardous condition and bodily harm!

 

T

HERMOSTAT 

H

EAT 

A

NTICIPATOR 

A

DJUSTMENT

 

After venting kit installation and checkout, check the amperage current draw through the 
thermostat circuit and adjust the thermostat anticipator accordingly. 

INSTALLATION OF GAS PRESSURE SWITCH 
CAUTION:

 

Check gas control valve pressure. Pressure MUST NOT exceed 14" WC 

pressure.

 

1.  Remove pressure tap plug in gas valve. (See Figure 5) 

NOTE:

 

If installing on an 

existing appliance, shut off gas supply to gas valve before plug removal.

 

2.  Replace the pressure tap plug with the 1/8" pipe nipple and pipe tee. Install pressure 

tap plug at the bottom of the pipe tee. (See Figure 6) 

3.  Install the gas pressure switch into the side of the pipe tee. The gas pressure switch 

is supplied with a restrictor orifice in the inlet and outlet ports.  With these orifices in 
place, the switch does not need to be vented.  This feature complies with current 
ANSI standards for gas regulators. (See Figure 7)

.

 

CAUTION:

 

If for any reason the system has shut down during operation, the cause of 

the system failure should be investigated and corrected before resetting the safety 
switch and restarting the system.

 

DRAFT HOOD SAFETY SWITCH INSTALLATION PROCEDURE 
NOTE:

 

12 ga. wire should be used when wiring safety spillage switches, to reduce the 

voltage drop in the thermocouple circuit.

 

1.  Remove the thermocouple from the gas control valve. (See Figure 5) 
2.  Thread the junction block into the thermocouple port and thermocouple into the 

bottom of the junction block. Connect lead wire from the junction block to the 
jacketed lead wires or wire enclosed in an accepted wiring enclosure. (See Figure 
8) 

Figure 4

Figure 5

Figure 6

Figure 7

Figure 8

Summary of Contents for 46285400

Page 1: ...witch and post purge timer 1 Fan control gas pressure switch with built in post purge option 1 2 ft length of 1 4 inch aluminum tubing 1 1 8 NPT x 3 inch pipe nipple 1 1 8 NPT x 1 4 inch OD tubing elb...

Page 2: ...2F junction box or installer supplied junction box onto the wall or floor joist without straining the flexible conduit Fasten the CK 92F junction box through the four dimpled locations on the base of...

Page 3: ...s supply to gas valve before plug removal 2 Replace the pressure tap plug with the 1 8 pipe nipple and pipe tee Install pressure tap plug at the bottom of the pipe tee See Figure 6 3 Install the gas p...

Page 4: ...er when wiring power venter Wire the venter motor and controls in accordance with the National Electrical Code manufacturer s recommendations and or applicable local codes UNITS MUST BE GROUNDED Check...

Page 5: ...wire from this terminal and reroute to T1 on CK 92F 4 With boilers connect T3 on CK 92F to hot side of gas valve if standing pilot or to terminal TH W 24 V THS or T1 if spark ignition NOTE Remember th...

Page 6: ...wer to the gas pressure switch 2 Adjust the thermostat to call for heat with the venter inoperative Allow approximately 2 minutes of flue gas spillage for the spillage switches to sense the spillage a...

Page 7: ...__ INSTALLER S NAME _____________________________________________________ INSTALLER S COMPANY _________________________________________________ INSTALLER S PHONE NO ___________________________________...

Page 8: ...Page 8 P N 46285400 Rev C 10 03...

Reviews: