MAINTENANCE 

1.  Inspect the system annually to ensure proper operation by observing that the fan activates when a 

call for heat occurs and deactivates when the call for heat is satisfied. 

2.  Disconnect power to the CAS unit and repeat Step 1. Note: The unit should not run and the 

appliance should not fire in this condition. 

3.  Inspect the duct pipe for cracks and security to the CAS unit, VRV (if installed), and vent hood. 

4.  Clear any obstructions, if present, from the inlet of the vent hood and the outlet of the CAS unit. 

5.  Periodically, the fan blade chamber may need cleaning. First, disconnect the power supply to the 

CAS. Next, disconnect the duct pipe from the unit. Then remove the top pan and clean the fan 
housing area as needed. Reattach the top pan, reconnect the duct pipe and the power supply. 

 

Figure 9

 - 

Figure 9 shows how the DIP-1 should be attached to the CAS. Note that  

the 1/4" O.D. plastic tubing on the top of the CAS unit must be cut and a 3-way male 

barb TEE suitable for 3/16" I.D. tubing placed as shown in order to connect the DIP-1.

 

Summary of Contents for 46261200

Page 1: ...t work and the input rating of the appliance This device MUST be installed by a qualified agency in accordance with the manufacturers installation instructions The definition of a qualified agency is...

Page 2: ...ould be used when installing the CAS system Using these charts will help ensure that the proper amount of air is drawn into the structure as needed by the appliance The defined regions shown correspon...

Page 3: ...ry is the diagonal line that says 4 inch Duct Hood Orifice Ring Therefore place the Orifice Ring into the inlet on the CAS so that it sits on the ledge above the fan It does not matter which way the O...

Page 4: ...FIRING RATE gallons per hour 1 gallon oil hr 140 000 BTU hr 6 Duct Hood 4 Duct Hood 4 Duct Hood Orifice Diagram A LOW SPEED SIZING CHART 0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400 GAS I...

Page 5: ...moving during operation INTAKE AIR HOOD LOCATION The 4 galvanized vent hood should be located on an outside wall maintaining minimum clearances to other intake and exhaust vents in accordance with the...

Page 6: ...terminals Use the enclosed conduit connector s to route the appropriate wires through the CAS housing The incoming ground wire must be attached to the green colored ground screw near the wire termina...

Page 7: ...Page 7 Figure 6 Riello Oil Fired System Figure 7 Single Vent Oil Fired System...

Page 8: ...Page 8 Figure 8 Chimney Vent Two Oil Fired System with CAC 120...

Page 9: ...4 Clear any obstructions if present from the inlet of the vent hood and the outlet of the CAS unit 5 Periodically the fan blade chamber may need cleaning First disconnect the power supply to the CAS...

Page 10: ...t must be disassembled If this is necessary take note of the positions and locations of whatever items that may need to be removed to replace other items If in doubt please consult the Field Controls...

Page 11: ...Page 11 NOTES...

Page 12: ...Page 12 PN 46261200 Rev I 10 06...