INSTALLATION 

P

LACEMENT OF THE 

CAS U

NIT

 

The motorized CAS unit should be located on a flat horizontal 
surface within the space of the appliance or appliances, and try to 
be within 3 feet of the combustion air intake of the appliance. Two 
mounting brackets are provided for securing the unit against a solid 
structure, such as a wall, column, or the side of the appliance itself. 
Use the included screws to attach the brackets to the CAS housing 
as shown in Figure 3. Secure the brackets to a solid structure with 
appropriate fasteners. It is not required to use the brackets as long 
as the unit is located so that it may not be bumped, moved, or 
tipped over. The optional Vacuum Relief Valve (VRV) should be 
placed directly on the air inlet of the CAS unit if using 6” duct or if 
using 4” duct, should be placed above reducer.  (See Figure 1) 
Refer to Diagram A to determine if the VRV is needed. The VRV 
should be oriented so that the axis of the swinging gate is 
horizontal. 

A

SSEMBLING 

T

HE 

W

EIGHTS 

O

T

HE 

VRV 

Refer to Figure 2 to assemble the weight assembly, hex nut, and 
knurled nut to the VRV gate. After the weight is correctly 
positioned, tighten the hex nut against the gate to prevent the 
weight assembly from moving during operation. 

I

NTAKE 

A

IR 

H

OOD LOCATION

 

The 4" galvanized vent hood should be located on an outside wall 
maintaining minimum clearances to other intake and exhaust vents 
in accordance with the National Fuel Gas Code, ANSI Z223.1, 
manufacturer's recommendations and/or local codes which are 
applicable. The hood should be located at least 10 feet from a 
power vented exhaust outlet and should be on the same wall. 

I

NSTALLATION OF 

I

NTAKE 

A

IR 

H

OOD

 

After determining the location of the vent hood, cut a 4-1/2 inch 
round or square hole in the wall. Insert the vent hood and secure 
with appropriate fasteners. Take precautions to avoid interference 
with wiring or other plumbing in the wall to be cut. 

I

NSTALLATION OF 

D

UCT

 

Refer to Diagram A or B to determine what size pipe is needed. 
Connect the duct pipe from the top of the CAS unit to the Vent 
Hood in the wall. If using 4" diameter pipe attach the provided 4" x 
6" Pipe lncreaser Fitting to the top of the CAS unit.  The duct 
should be supported with appropriate mounting straps from floor 
joists, walls, or other solid structures. The straps should be placed 
so as to keep the ductwork out of passageways.  (See Figure 1)  A 
minimum of 12 feet of pipe should be run to help temper outside air 
being drawn in.  The VRV may also be installed near the air intake 
hood and adjusted to mix with outside air to help temper air in cold 
climates. 

Figure 2

Figure 3

Figure 1

Summary of Contents for 46261200

Page 1: ...t work and the input rating of the appliance This device MUST be installed by a qualified agency in accordance with the manufacturers installation instructions The definition of a qualified agency is...

Page 2: ...ould be used when installing the CAS system Using these charts will help ensure that the proper amount of air is drawn into the structure as needed by the appliance The defined regions shown correspon...

Page 3: ...ry is the diagonal line that says 4 inch Duct Hood Orifice Ring Therefore place the Orifice Ring into the inlet on the CAS so that it sits on the ledge above the fan It does not matter which way the O...

Page 4: ...FIRING RATE gallons per hour 1 gallon oil hr 140 000 BTU hr 6 Duct Hood 4 Duct Hood 4 Duct Hood Orifice Diagram A LOW SPEED SIZING CHART 0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400 GAS I...

Page 5: ...moving during operation INTAKE AIR HOOD LOCATION The 4 galvanized vent hood should be located on an outside wall maintaining minimum clearances to other intake and exhaust vents in accordance with the...

Page 6: ...terminals Use the enclosed conduit connector s to route the appropriate wires through the CAS housing The incoming ground wire must be attached to the green colored ground screw near the wire termina...

Page 7: ...Page 7 Figure 6 Riello Oil Fired System Figure 7 Single Vent Oil Fired System...

Page 8: ...Page 8 Figure 8 Chimney Vent Two Oil Fired System with CAC 120...

Page 9: ...4 Clear any obstructions if present from the inlet of the vent hood and the outlet of the CAS unit 5 Periodically the fan blade chamber may need cleaning First disconnect the power supply to the CAS...

Page 10: ...t must be disassembled If this is necessary take note of the positions and locations of whatever items that may need to be removed to replace other items If in doubt please consult the Field Controls...

Page 11: ...Page 11 NOTES...

Page 12: ...Page 12 PN 46261200 Rev I 10 06...

Reviews: