background image

PRESSURE SWITCH ADJUSTMENT 

Important:

 

Both the CK-41 and CK-81 power vent control systems 

have a pressure switch which must be properly set before the 
water heater can be started. The pressure switches are set so that 
the contacts will not close until properly set by the installer. Failure 
to carefully follow the procedure below for setting the pressure 
switch will either prevent the water heater from operating properly 
of defeat the safety feature of the control which could allow a 
hazardous condition to occur in the event the power venter 
operates with a venting malfunction.

 

1.  Attach the 0.25" tubing connector on the pressure tube on the 

SWG venter. Connect the supplied 0.25" aluminum tubing to 
the tubing connector. Route the tubing to the power venter 
control box and connect the tubing to the pressure switch. 
When routing the tubing, avoid kinking the tubing by bending 
the tubing too sharply. 

2.  Follow the lighting instructions and light the pilot (millivolt 

models). Turn thermostat to the highest setting and turn on 
sufficient water flow to keep the burners on continually. The 
power venter should start, but the main burners will not come 
on until the pressure switch is adjusted. 

3.  Slowly rotate the pressure switch adjustment screw 

counterclockwise until the contacts close and the burners fire, 
then rotate the screw 1/4 turn counterclockwise. (See Figure 
15) Cycle the thermostat a couple of times to insure proper 
operation. 

4.  Follow the "General Installation Inspection " below to make 

sure the pressure switch and venting system operates properly 
with all gas appliances and exhaust fans operating. 

GENERAL INSTALLATION INSPECTION 

Recommended procedures for safety inspection of an appliance in accordance 
with the National Fuel Gas Code A.N.S.I.Z223.1. The following procedure will 
help evaluate the venting system. It is intended as a guide to aid in determining 
that the venting system is properly installed and is in a safe condition for 
continuous use. This procedure should be recognized as a generalized 
procedure which cannot anticipate all situations. Accordingly, in some cases, 
deviation from this procedure may be necessary to determine safe operation of 
the equipment. If it is determined that a condition exists which could result in 
unsafe operation, the appliance should be shut off and the owner advised of the 
unsafe condition. Corrections must be made before the appliance is put into 
continuous operation. The following steps should be followed in making a safety 
inspection. 

1.  Visually inspect the venting system for proper size and determine that there is no flue gas spillage, blockage,  re-

striction, leakage, corrosion, or other deficiency which could cause an unsafe operation. 

2.  Insofar as practical, close all building doors, fireplace dampers, windows, and all doors in area in which the appliance 

is located. Turn on clothes dryers, any exhaust fans, such as range hoods and bathroom exhausters so they operate 
at maximum speed. Do not operate a summer exhaust fan. If, after completing Steps 3 through 6 it is believed 
sufficient combustion air is not available, refer to the National Fuel Gas Code A.N.S.I.Z223.1, or any applicable local 
codes for guidance. 

3.  Place in operation the appliance being inspected. Follow the lighting instructions and adjust thermostat so appliance 

will operate continuously. 

4.  Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily, by 

interrupting and re-establishing the electrical power of the appliance in any convenient manner. Test the pilot or 
burner safety device to determine if it is operating properly by extinguishing the pilot or disconnecting the flame safety 
circuit and pressure switch sensing tube from the pressure switch. 

5.  Visually determine that the main burner is burning properly; i.e., no floating, lifting, or flashbacks. 

Figure 14

Figure 15

Page 12 

Summary of Contents for 46256400

Page 1: ... CONTROLS WITH INPUT RATINGS OF UP TO 290 000 BTU HR 239 81766 00 SWGII 6 POWER VENTER CK 41 24 VOLT CONTROL KIT COMMERCIAL WATER HEATERS WITH 24 VOLT CONTROLS WITH INPUT RATINGS GREATER THAN 290 000 BTU HR UP TO 416 000 BTU HR 239 81767 00 SWGII 6 POWER VENTER CK 81 MILLIVOLT CONTROL KIT COMMERCIAL WATER HEATERS WITH 24 VOLT CONTROLS WITH INPUT RATINGS GREATER THAN 290 000 BTU HR UP TO 416 000 BT...

Page 2: ... flue damper closes POWER VENTER KIT FOR MILLIVOLT CONTROLS CK 81 CONTROL KIT 1 When the aquastat contacts close the 24 volt circuit is completed from the transformer through the wiring harness and switch contacts and through the relay coil causing the motor relay contacts to close and start the power venter blower 2 When the blower reaches operating speed the vacuum near the blower causes the pre...

Page 3: ...re conditions To ensure extreme negative pressure does not exist follow General Installation Inspection of this manual 7 The commercial water heaters for the SWGII 5 and 6 power venters have draft hoods and each kit includes a GSK 3 spillage switch which must be installed on the bottom of the draft hood to detect spillage of flue products due to inadequate venting draft or vent system blockage In ...

Page 4: ...tem in accordance with manufacturer s instructions will result in conditions which may produce bodily injury and or property damage 1 Remove power venter from box and inspect unit for damage If the carton has been crushed or mutilated check unit very carefully for damage Rotate blower wheel to insure that the motor and blower wheel rotate freely DO NOT install if any damage is apparent Refer to un...

Page 5: ...rial and the flue gas temperature is above 400EF at the power venter inlet line the square hole with a piece of corrosion resistant sheet metal or non combustible material The liner piece should be the same width as the wall section See Figure 3 The power venter has maximum flue gas temperature of 550EF at the power venter inlet Figure 7 shows how the airflow pattern through an SWG reduces the req...

Page 6: ...ING SINGLE WALL VENT PIPE INSTALLATION CLEARANCE WITH SINGLE WALL VENT PIPE DOUBLE PIPE SYSTEM SINGLE PIPE SYSTEM ALLOWABLE INLET TEPERATURE CLEARANCE A ALLOWABLE INLET TEMPERATURE CLEARANCE B 400 F OR LESS INCH MINIMUM 400 F OR LESS 3 INCH MINIMUM 400 F TO 550 F 1 INCH MINIMUM 400 F TO 550 F 4 INCH MINIMUM 400 F TO 550 F INCH MINIMUM WITH SHEET METAL LINER 400 F TO 550 F 3 INCH MINIMUM WITH SHEET...

Page 7: ...CAUTION MUST be taken to ensure that the wiring does not come in contact with any heat source All line voltage and safety control circuits between the power venter and the appliance MUST be wired in accordance with the National Electrical Code for Class 1 wiring or equivalent CK 41 CONTROL KIT WIRING FOR 24 VOLT WATER HEATER CONTROLS 1 Remove the wiring harness supplied with the control kit 2 Remo...

Page 8: ...he joists at regular intervals to prevent sagging 10 Run the low voltage wires into the control box through hole with plastic bushing and connect the wires as follows Connect the black wire to terminal T1 the red wire to T2 and the yellow wire to T3 See Figures 11 and 12 11 Follow the National Electrical Code and or applicable local codes for running high voltage wires to the CK 41 control box an ...

Page 9: ...Figure 11 Page 9 ...

Page 10: ...Figure 12 Page 10 ...

Page 11: ...pping sheet metal screw supplied The thermal element disc should hang just below the draft hood relief opening See Figure 10 7 Run the two 2 red wires from the break in the top of the harness into the spillage switch through the plastic bushing opening and connect to the switch terminals 8 Run the harness to the CK 81 junction box which will be mounted in a convenient location near the power vente...

Page 12: ...ded as a guide to aid in determining that the venting system is properly installed and is in a safe condition for continuous use This procedure should be recognized as a generalized procedure which cannot anticipate all situations Accordingly in some cases deviation from this procedure may be necessary to determine safe operation of the equipment If it is determined that a condition exists which c...

Page 13: ...ar any soot ash or coating which inhibits either rotation or air flow Remove all foreign materials before operating 3 Vent System Inspect all vent connections annually for looseness for evidence of corrosion and for flue gas leakage Replace seal or tighten pipe connections if necessary 4 System Safety Devices With the heating system operating disconnect the pressure sensing tube from the pressure ...

Page 14: ...ssembly See Figure 17 2 Slide the motor assembly onto the protruding threaded studs on the venter body with the exhaust chute pointing downward and replace the four nuts securely to the threaded studs 3 Reattach the flexible conduit and wires to the motor and secure the cover on the electrical box 4 Install the motor cover with the side louvers pointing downward INITIAL BURNER AND VENTING SYSTEM O...

Page 15: ...__ INSTALLER S NAME _____________________________________________________ INSTALLER S COMPANY __________________________________________________ INSTALLER S PHONE NO _________________________________________________ DATE OF INSTALLATION _________________________________________________ Page 15 ...

Page 16: ...PN 46256400 Rev B 7 00 ...

Reviews: