BASIC OPERATION
14
010
NCL
Output
*****
[DIS] (Disable) [ENA] (Enable)
Enable
*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode, but transfer time should not be 0ms
**) When operating in Converter Mode, the frequency of output should be always 50Hz or 60Hz, but load capacity will be derated
by 40%.
*) This function would be set as 0% when Converter Mode is enabled.
**) UPS has no bypass when Converter Mode is enabled.
***) ROO (Remote On/Off): If ROO is enabled, UPS can be turn on/off by the ROO port. If ROO port is disconnected, UPS will be
turned off. If ROO port is connected, UPS will be turned on when the utility is normal
****) 1. UPS cannot detect the numbers of external battery automatically, so manual input from user is necessary.
2. For standard models, the maximum number is prefer to 1. For long run models, the maximum number is just 1 EBM, the
charge current will be 4A, if EBM number is over 1, the charge current will be 8A