28
confIguratIon
35.
Alarm configuration – duration
Description
This parameter defines duration of alarm se-
quence. When time set in this parameter elaps-
es, alarm is cancelled, LED frame and relay re-
store normal operation, but do not recover state
from before the alarm.
Parameter size
2B
Default value
600 (10min)
Available
values
0 – infinite
1-32400 (1s-9h, 1s step) – duration
40.
First button – scenes sent
Description
This parameter determines which actions result
in sending scene IDs assigned to them. Values
can be combined (e.g. 1+2=3 means that scenes
for single and double click are sent).
Enabling scenes for triple click disables entering
the device in learn mode by triple clicking.
Parameter size
1B
Default value
0 (no scenes)
Available
values
1 – Key pressed 1 time
2 – Key pressed 2 times
4 – Key pressed 3 times
8 – Key hold down and key released
41.
Second button – scenes sent
Description
This parameter determines which actions result
in sending scene IDs assigned to them. Values
can be combined (e.g. 1+2=3 means that scenes
for single and double click are sent).
Enabling scenes for triple click disables entering
the device in learn mode by triple clicking.
Parameter size
1B
Default value
0 (no scenes)
Available
values
1 – Key pressed 1 time
2 – Key pressed 2 times
4 – Key pressed 3 times
8 – Key hold down and key released