FHF 5842/2 Manual Download Page 3

Technical specification

Setting the tone signal
according to the following
table 

any position of the DIP-
switch may be used to set
the tone signal. 

Switch-

Signals

Tone sequence

position

Tone seq. frequency

Three-tone

5 Hz

Three-tone

10 Hz

Three-tone

15 Hz

Three-tone

20 Hz

Two-tone

5 Hz

Two-tone

10 Hz

Two-tone

15 Hz

Two-tone

20 Hz

Switch-

Signals

Tone sequence

position

Tone seq. frequency

Single tone 180 ms on

70 ms off

Single tone 120 ms on

50 ms off

Single tone

60 ms on
25 ms off

Single tone

Continuous

tone

Warble tone

1.8 Hz

Warble tone

3.6 Hz

Warble tone

3.9 Hz

Warble tone

7.8 Hz

3

Type:    

5842/2

Device designation:  

Ex-Secondary Sounder

Housing material:  

Die-casting aluminium     Colour: black

Weight:   

approx. 0.9 kg

Resonant hood material: 

Makrolon, UV proof (polycarbonate)     Colour: black

Physical dimensions:  

approx. 140 x 150 x 120 mm

Cable entry:  

1x M20 x 1.5

Terminals:   

cable cross section 1.5 mm

2

; single core and fine strand

Operation position:  

any (wall mount, ceiling mount*)

Protection category: 

IP 66

Explosion category:  

II 2 G EEx em [ib] IIC T6

Certificate of conformity:  

DMT 99 ATEX E 095

CE label:   

yes, according to EMC Law 11/92

Ambient operation temperature: 

-20°C to + 40°C

Storage temperature:  

-40°C to +75°C

Transport temperature: 

-40°C to +75°C

Relative humidity:  

up to max. 90%

Telephone connection: 

Terminals 
D: Lb and W

Ringing alternating current: 

32 V

AC

- 75 V

AC

; 23 Hz - 54 Hz

Overlaid supply voltage: 

0 V

DC

- 63 V

DC

Input impedance:  

at 25 Hz: Z 8 k

at 50 Hz: Z 4 k

Current intensity: 

I

K

3 A

Equipotential bonding: 

Connection inside the housing

Insulation class: 

I

Acoustic signalling device: 

Loudspeaker

Acoustic signal:  

3-tone call, tone sequence: 800 Hz, 1067 Hz, 1333 Hz
2-tone call, approx. 931 Hz, approx. 1253 Hz

Tone sequence frequency: 

Choice of 4 different DIP switch settings

Sound pressure level:  

> 90 dB(A) using 2-tone call, at 1 m distance at 45 V 23 Hz

Maintenance:   

not necessary

* In rooms considerably influenced by dust or water ceiling mounting to be effected the open acoustic hood

showing downwards.

Summary of Contents for 5842/2

Page 1: ...n und Hin weise zum Anschalten an das Telefonnetz zu beachten Ruf wechselspannung an Klemmen Lb und W Note Prior to installing the device these operating instructions must be read carefully In case of any damage and liabilities the latest version of the General terms of delivery of products and services in the electric industry is authorita tive Notes on use The explosion proof secondaray sonder i...

Page 2: ...nd W Rufwechselspannung 32 VAC bis 75 VAC 23 Hz bis 54 Hz überlagerte Speisespannung 0 VDC bis 63 VDC Eingangsimpedanz bei 25 Hz Z 8 kΩ bei 50 Hz Z 4 kΩ Stromstärke IK 울 3 A Potentialausgleich Anschluss innen am Gehäuse Schutzklasse I Akustischer Signalgeber Lautsprecher Akustisches Signal 3 Tonruf Tonfolge 800 Hz 1067 Hz 1333 Hz 2 Tonruf ca 931 Hz ca 1253 Hz Tonfolgefrequenz 4 unterschiedliche Ei...

Page 3: ... 2 single core and fine strand Operation position any wall mount ceiling mount Protection category IP 66 Explosion category II 2 G EEx em ib IIC T6 Certificate of conformity DMT 99 ATEX E 095 CE label yes according to EMC Law 11 92 Ambient operation temperature 20 C to 40 C Storage temperature 40 C to 75 C Transport temperature 40 C to 75 C Relative humidity up to max 90 Telephone connection Termi...

Page 4: ...4 ...

Page 5: ... Gerätes ist zu berücksichtigen 6 Das Gerät ist für den Betrieb in Räumen oder im Freien bestimmt 7 Bei Betrieb des Gerätes sind die gesetzlichen und gewerblichen Vorschriften Unfallverhütungsvor schriften sowie elektrische Bestimmungen und Vorschriften zum Anschluss und Betrieb an Netzspannung zu beachten Der Anschluss und die Inbetriebnahme darf nur durch einen unter wiesenen Fachmann erfolgen 8...

Page 6: ... of the device the legal and professional regulations the safety regulations and the electrical rules and regulations regarding connection and operation with line voltage must be observed Connection and commissioning may be done by an educated professional only 8 The device may be opened by educated professional personnel only During the process of opening covers or removing parts live parts may b...

Reviews: