En-11
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to “Both” (01).
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(
♦
... Factory setting)
Function Number
Setting
Value
Setting Description
35
(For cooling)
36
(For heating)
00
No correction
♦
01
No correction 0.0 °C (0 °F)
02
-0.5 °C (-1 °F)
More
Cooling
Less
Heating
03
-1.0 °C (-2 °F)
04
-1.5 °C (-3 °F)
05
-2.0 °C (-4 °F)
06
-2.5 °C (-5 °F)
07
-3.0 °C (-6 °F)
08
-3.5 °C (-7 °F)
09
-4.0 °C (-8 °F)
10
+0.5 °C (+1 °F)
Less
Cooling
More
Heating
11
+1.0 °C (+2 °F)
12
+1.5 °C (+3 °F)
13
+2.0 °C (+4 °F)
14
+2.5 °C (+5 °F)
15
+3.0 °C (+6 °F)
16
+3.5 °C (+7 °F)
17
+4.0 °C (+8 °F)
Auto restart
Enable or disable automatic restart after a power interruption.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
40
00
Enable
♦
01
Disable
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
42
00
Indoor unit
♦
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller.
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
44
00
A
♦
01
B
02
C
03
D
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
46
00
Operation/Stop mode 1
♦
01
(Setting forbidden)
02
Forced stop mode
03
Operation/Stop mode 2
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
“Wired remote controller” (01).
This function will only work if the function setting 42 is set at “Both” (01).
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
48
00
Both
♦
01
Wired remote controller
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
49
00
Disable
01
Enable
02
Remote controller
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
* When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made
by using the remote controller. Set to (00) or (01).
To con
fi
rm if the remote controller has this function, refer to the operating manual of each
remote controller.
Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “12.1. External
input and output”.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
60
00
Operation status
♦
09
Error status
10
Indoor unit fan operation status
12
Set point attainment status
Server room control switching
Switches between normal control and server room control.
To use this function, address setting of the primary unit and secondary unit needs to be done.
(
♦
... Factory setting)
Function
Number
Setting Value
Setting Description
96
00
Normal control
♦
01
Server room control (Primary unit)
02
Server room control (Secondary unit)
Setting record
Record any changes to the settings in the following table.
Setting Description
Setting Value
Remote controller address setting
Filter sign
Room temperature control for indoor
unit sensor
Cooling
Heating
Room temperature control for wired
remote controller sensor
Cooling
Heating
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Server room control switching
After completing the function setting, be sure to turn off the power and turn it on again.