Festo VPPM Operating Instructions Download Page 4

10

Malfunctions

Status of the LED displays

Cause

Green LED [power]

Red LED [error]

Undervoltage or overvoltage
of the setpoint value

on

on

Hardware error

Overvoltage (

>

 30 V)

Internal temperature too
high

on

flashes

Undervoltage (

<

 18 V)

off

off

Tab. 9: Status of the LED displays

Fault clearance

Malfunction

Possible cause

Remedy

Device does not respond

No supply voltage, LED [power]
off.

Check the connection of the
supply voltage 24 V DC.

No data communication.

Check control unit.

Check connection.

Flow rate too low

Restriction of the flow cross
section by connection tech-
nology.

Use alternative connections.

Pressure rise too slow

Large cylinder volume and long
tube length.

Select another parameter set.

Pressure constant despite
modified setpoint specification

Break in the electrical con-
necting cable.

Replace supply cable.

Supply pressure P1 too low.

Increase supply pressure.

Manual selection of parameter
sets with the [UP] and [DOWN]
keys on the device is not pos-
sible

Voltage is applied at digital
inputs D1 and D2.

Apply 0 V DC at digital inputs
D1 and D2.

Tab. 10: Fault clearance

11

Technical data

General technical data

Design

Proportional-pressure regulator

Mounting position

As desired, preferably horizontal (display elements
facing upwards)

Materials
Housing

Wrought aluminium alloy

Cover

PAXMD6 GF50/gr-P

Seals

Nitrile rubber

Lubrication

silicone-free

Weight
VPPM-6...

[g]

400

VPPM-8...

[g]

560

VPPM-12...

[g]

2050

Tab. 11: General technical data

Operating and environmental conditions

Medium

Compressed air in accordance with ISO 8573-1:2010
[7:4:4] inert gases

Information on operating
medium

Lubricated operation not possible

Degree of protection

IP 65 when mounted, with tightened mounting screws,
in combination with plug socket according to accesso-
ries.

Ambient temperature

[°C]

0 … 60

Temperature of medium

[°C]

10 … 50

Storage temperature

[°C]

–10 … +70

Vibration and shock
Vibration

Tested in accordance with DIN/IEC
68/EN 60068 Part 2-6; wall mounting: 0.35 mm path
at 10 … 60 Hz, 5 g acceleration at 60 … 150 Hz

1)

Shock

Tested in accordance with DIN/IEC
68/EN 60068 Part 2-27; wall mounting: ±30 g at 11 ms
duration; 5 shocks per direction

1)

1) Information does not apply when mounting the VPPM-.../VPPX-... on bracket VAME-P1-A/-T.

Tab. 12: Operating and environmental conditions

VPPM-...

0L2H

0L6H

0L10H

Pressure ranges
Permissible input pressure P1

[MPa]

0 … 0.4

0 … 0.8

0 … 1.1

[bar]

0 … 4

0 … 8

0 … 11

[psi]

0 … 58

0 … 116

0 … 159.5

Control range (output pressure
P2)

1)

[MPa]

0.002 … 0.2

0.006 … 0.6

0.01 … 1

[bar]

0.02 … 2

0.06 … 6

0.1 … 10

[psi]

2.9 … 29

8.7 … 87

1.45 … 145

Total leakage when new

[l/h]

<

 5

Connection

G 1/8, 1/8 NPT, G 1/4, 1/4 NPT, G 1/2, 1/2 NPT

VPPM-...

0L2H

0L6H

0L10H

Nominal width
Pressurisation

[mm]

6 for VPPM-6...
8 for VPPM-8...
12 for VPPM-12...

Exhaust port

[mm]

4.5 for VPPM-6...
6 for VPPM-8...
12 for VPPM-12...

1) Input pressure P1 at least 0.1 MPa (1 bar, 14.5 psi) above output pressure P2.

Tab. 13: Characteristic pneumatic values

Characteristic electrical values

Electrical connection

Pin contact M12x1, 8-pin

Permissible operating voltage

[V DC]

21.6 … 26.4
Permissible residual ripple max. 10%

Power rating of digital switching
output D3 (PIN 8 in el. connection)

[mA]

max. 60

Max. permissible supply line
length and signal line length

[m]

10

Max. electrical power consumption
VPPM-6... and VPPM-8...

[W]

7

VPPM-12L-...

[W]

12

Voltage type VPPM-...-V1...
Setpoint variable

[V DC]

0 … 10

Input resistance (setpoint value)

[kΩ]

10

Output actual value load

[kΩ]

min. 2

Current type VPPM-...-A4...
Setpoint variable

[mA]

4 … 20

Input resistance (setpoint value)

[Ω]

250

Output actual value load

[Ω]

max. 500

Tab. 14: Characteristic electrical values

Control characteristics

1)

Linearity

1% Full Scale (FS)/2% Full Scale (FS)

Hysteresis

0.5% Full Scale (FS)

Reproducibility

0.5% Full Scale (FS)

Total accuracy

1.25% (S1)/2.25 (2%)

Temperature coefficient

0.04/K 

1) Maximum deviation, characteristic values determined at room temperature in accordance with ISO 10094.

Linearity refers to the ideal characteristic curve.

Tab. 15: Control characteristics