Festo VPPM Operating Instructions Download Page 3

3.

1.

1.

Pin allocation
The pins on the electrical connection are assigned as follows:

Fig. 5: Pin allocation

PIN

Wire colour

1)

Port identifications
VPPM-...-V1...

VPPM-...-A4...

1

white (WH)

Digital input D1

2

brown (BN)

+24 V DC supply voltage

3

green (GN)

Analogue input W- (- setpoint value)

4

yellow (YE)

Analogue input W+
(+ setpoint value)
0 … 10 V

Analogue input W+
(+ setpoint value)
4 … 20 mA

5

grey (GY)

Digital input D2

6

pink (PK)

Analogue output X (actual value)

7

blue (BU)

GND supply earth

8

red (RD)

Digital output D3

2)

1) With usage of the plug socket with cable as specified in accessories.
2) The hysteresis of the digital comparator output D3 is 0.5% FS.

Tab. 3: Pin allocation

Digital comparator output D3
The “Pressure reached” function permits monitoring of the pressure control func-
tion. The setpoint value is compared with the actual value.
The digital switching output D3 becomes active as soon as the divergence is

£

 0.5% FS and becomes inactive when the divergence 

>

 1% FS is exceeded.

Graph for VPPM-...-...P switching variant

1

2

3

4

Fig. 6: Switching variant VPPM-...-...P

1

Setpoint value

2

Actual value

3

Upper tolerance limit

4

Lower tolerance limit

Graph for VPPM-...-...N switching variant

1

2

3

4

Fig. 7: Switching variant VPPM-...-...N

1

Setpoint value

2

Actual value

3

Upper tolerance limit

4

Lower tolerance limit

Circuit diagram VPPM-...-...P

Circuit diagram VPPM-...-...N

Tab. 4: VPPM-... circuit diagrams Switching output

8

Commissioning

• Keep high-frequency radiation away from the VPPM-... in order to avoid

increased tolerances of the outlet pressure.

• The VPPM-... interprets setpoint signals that are less than 1% Full Scale (FS) as

0 V or 4 mA. In this case the working pressure is set to ambient pressure.

• At typical input values below 3.6 mA , the valve detects a cable break and the

last pressure set remains unregulated. Leakage results in a change of pressure
over the long term.

1. Connect the VPPM-... with a setpoint value signal. The VPPM-... has a differen-

tial input. Apply the setpoint signal 0 … 10 V or 4 … 20 mA to contacts 3 and 4.
Apply the lower potential to contact 3 and the higher potential to contact 4.

Contact 3 (– setpoint value) can be connected to contact 7 (GND).

2. Power the VPPM-... with direct current.

Supply voltage UV = 24 V DC ±10%

Select a parameter set for the regulator.

Press and hold the [Edit] key for 3 seconds.

Select a parameter set with the [UP] and [DOWN] keys. The LED of the
selected parameter set lights up.

Press the [Edit] key to confirm the selection.

The control response of the VPPM-... can also be set by remote control via
digital inputs D1 and D2.

Parameter set Control response

Input D1 (PIN
1)

Input D2 (PIN
5)

1

Fast control response

1 (24 V DC)

0 (0 V DC)

2

Factory setting: universal control
response

0

1

3

Precise control response

1

1

Tab. 5: Parameter sets
The following 3 tables show the recommended parameter sets for the different
pneumatic ports:

Parameter sets recommended for VPPM-6...
Tube length

1)

Open system

Output volume in ml
0 … 100

100 … 1000

>

1000

0 m

3

3

2

1

1 m

3

3

2

2

3 m

3

3

3

2

³

 5 m

3

3

3

2

1) with inner tubing diameter 6 mm or 8 mm

Tab. 6: Parameter sets recommended for VPPM-6...

Parameter sets recommended for VPPM-8...
Tube length

1)

Open system

Output volume in ml
0 … 500

500 … 2000

>

2000

0 m

3

1

2

3

1 m

3

1

2

3

3 m

3

2

3

3

³

 5 m

3

3

3

3

1) with tubing diameter 8 mm or 10 mm

Tab. 7: Parameter sets recommended for VPPM-8...

Parameter sets recommended for VPPM-12L-...
Tube length

1)

Open system

Output volume in ml
0 … 2000

2000 … 10000

>

10000

0 m

3

1

2

3

1 m

3

1

2

3

3 m

3

2

3

3

³

 5 m

3

3

3

3

1) with tubing diameter 12 mm or 16 mm

Tab. 8: Parameter sets recommended for VPPM-12L-...

9

Maintenance

9.1

Disassembly

NOTICE

• When switching off the VPPM.-..., first make sure that the setpoint value is set

to 0, then that the supply pressure and finally the supply voltage are switched
off.

Switch off the following energy sources:

Operating voltage

Compressed air

2. Disconnect the connections from the device.
3. Remove the device from the mounting surface or H-rail.
9.2

Cleaning

Switch off the following energy sources to clean the outside:

Operating voltage

Compressed air

2. Clean the device on the outside with a soft cloth as required.