Characteristic pneumatic values
VPPI-…-0L10H-…
0 … 1.3
0 … 13
1.0 … 1.2
10 … 12
VPPI-…-0L12H-…
0 … 1.3
0 … 13
1.2 … 1.3
12 … 13
Product type
Input pressure at (3) (vacuum)
Operating pressure at (3)
[MPa]
[bar]
[MPa]
[bar]
VPPI-…-1V0H-…
–0.1 … 0
–1 … 0
–0.1 … 0
–1 … 0
VPPI-…-1V1H-…
–0.1 … 0
–1 … 0
–0.1 … 0
–1 … 0
Product type
Pressure regulation range
3)
at (2) –
[MPa]
[bar]
VPPI-…-1V0H-…
4)
0 … –0.1
0 … –1
VPPI-…-1V1H-…
–0.1 … +0.1
–1 … +1
VPPI-…-0L2H-…
0 … 0.2
0 … 2
VPPI-…-0L6H-…
0 … 0.6
0 … 6
VPPI-…-0L10H-…
0 … 1.0
0 … 10
VPPI-…-0L12H-…
0 … 1.2
0 … 12
1) The valve can be operated at an input pressure within the specified range. It must be noted here that the
specified control quality is only fulfilled with a permanent supply within the operating pressure range and
that the control pressure can reach the maximum available input pressure.
2) The specified control quality is only achieved if there is a permanent operating pressure supply at the
valve within the specified range.
3) Active regulation is only from a setpoint value of 1% FS, below which the valve is at zero point suppres-
sion.
4) For variants VPPI-...-1V0H-... 0% corresponds to setpoint value 0 bar and 100% to setpoint value –1 bar.
Tab. 11: Characteristic pneumatic values
Normal position
Valve variant
Normal position (de-energised state)
VPPI-…-3-…
Working pressure (2) blocked.
VPPI-…-4-…
Working pressure (2) is exhausted to the pressure at the exhaust air port (3).
Tab. 12: Normal position
Cable break detection
Valve variant
Setting ‘Input
min’
Cable break detection
VPPI-…-A4-…
<
2 mA
Cable break detection inactive.
³
2 mA
Cable break detection active. At analogue input values below 2 mA
the ‘Cable break’ error is displayed and the valve moves to the
normal position.
VPPI-…-V1-…
<
500 mV
Cable break detection inactive.
³
500 mV
Cable break detection active. At analogue input values below
500 mV the ‘Cable break’ error is displayed and the valve moves
to the normal position.
Tab. 13: Cable break detection
Zero point suppression
Valve variant
Setting ‘Pressure min’
Response with setpoint value
<
0.7% Full scale
VPPI-…-...L…H-…
0 MPa
Exhaust to 0 bar and keep the exhaust open.
>
0 MPa
Active control on ‘Pressure min’.
VPPI-…-1V1H-…
–0.1 MPa
Valve moves to normal position.
>
–0.1 MPA
Active control on ‘Pressure min’.
VPPI-…-1V0H-…
–
Active control on ‘Pressure max’.
Tab. 14: Zero point suppression
Setpoint values
<
0.7% Full scale above the minimum input value (‘Input min’) are
interpreted as the lowest input value in order to suppress noise at the input signal
Fig. 5. Depending on the valve variant and the minimum input pressure, there
may be a special response in this area
Tab. 14 Zero point suppression.
4
1
2
3
Fig. 5: Zero point suppression
1
Minimum input value + 0.7% FS
2
Minimum input value
3
Minimum pressure/vacuum
4
Zero point suppression
Characteristic electrical values
Nominal operating voltage
[V DC]
24
Operating voltage range
[V DC]
21.6 … 27.6
Nominal current
[mA]
150
Current consumption
[mA]
£
525
Permissible signal line length
[m]
£
30
Setpoint input
Setpoint value input
VPPI-…-V1-…
[V]
0 … 10
VPPI-…-A4-…
[mA]
4 … 20
PWM input voltage
Characteristic electrical values
VPPI-…-V1-
24 V DC (type 1 in accordance with DIN EN 61131)
PWM input frequency
VPPI-…-V1-…
[Hz]
200 … 800
Input resistance
VPPI-…-V1-...
[k
W
]
100
VPPI-...-A4-...
[k
W
]
0.3
Actual value output
Output current
[mA]
£
25
Analogue output
VPPI-…-V1-…
[V]
0 … 10
VPPI-…-A4-…
[mA]
4 … 20
Tab. 15: Characteristic electrical values
Control characteristics
1)
Linearity
0.9% FS (full scale)
Hysteresis
0.4% FS
Reproducibility
0.4% FS
Total accuracy
1.1% FS
Temperature coefficient
0.02/K
1) Maximum deviation, characteristic values determined at room temperature in accordance with ISO 10094.
Linearity refers to the ideal characteristic curve.
Tab. 16: Control characteristics