Auto difference monitoring

With the auto difference monitoring function, a change in pressure from a refer­
ence value is detected. As a result, a maximum permissible pressure drop can be
monitored, for example.
If the input variable is in the work range between [SP.Hi] and [SP.Lo] and is con­
stant, its value is set automatically as the reference value P

Ref

. The output

switches.
A constant input variable is present if the signal change is less than 0.2 % FS dur­
ing the set observation time [t.obs].
The parameter [d.SP] establishes the permissible deviation of pressure from the
reference value and thus the monitoring range. If pressure exceeds or falls below
[d.SP], the output switches back.

Function

NO (normally open)

NC (normally closed)

Switching  function:
– 2 switching points (SP.Lo,

SP.Hi) for setting the valid
work range

TEACH mode

1)

:

– 2 teach-in points (TP1, TP2)
– TP1 = SP.Lo, TP2 = SP.Hi

SP.Lo    P

Ref

     SP.Hi

d.SP

1

0

Out

p

1

SP.Lo    P

Ref

     SP.Hi

d.SP

0

Out

p

1)

SP.Lo = smaller pressure value, SP.Hi = larger pressure value, independent of the Teach sequence

Fig. 6

3

Requirements for product use

 Only use the product in original status, without any unauthorised modifications.
 The product is intended for use in industrial environments. Measures may need

to be implemented in residential areas for radio interference suppression.

 Take into consideration the ambient conditions at the location of use.
 Operate the product only with compressed air of the specified air quality class

(

è

 Technical data).

 Remove all transport packaging. The material used in the packaging has been

specifically chosen for its recyclability.

 Accessories 

è

 www.festo.com/catalogue.

Range of applications and certifications

In combination with the UL mark on the product, the information included in this
section is also applicable for compliance with the certification requirements of
Underwriters Laboratories Inc. (UL) for USA and Canada. Observe the following
English-language remarks from UL:

UL approval information

Product category code

QUYX, QUYX7

File number

E322346

Considered standards

UL 61010­1, CAN/CSA­C22.2 No. 61010­1

UL mark

Fig. 7

Only for connection to an NEC/CEC Class 2 supply.
Raccorder uniquement a un circuit NEC/CEC Classe 2.

Electrical and environmental ratings

Input voltage

max. 30 V DC, Class 2

Input current

max. 0.24 A

Power

max. 7.2 W

Pressure differential

max. 1.6 MPa

Ambient temperature

max. 50 °C /122 °F

Pollution degree

3

Humidity range

93 %

Only for indoor use.

Altitude up to 2000 m. Altitude up to 2000 m or above 2000 m if specified by the manufacturer.

Fig. 8

Warning

Unit shall be supplied by a power source which complies with the requirements
of a limited­energy circuit in accordance with IEC/EN/UL/CSA 61010­1 or a Lim­
ited Power Source (LPS) in accordance with IEC/EN/UL/CSA 60950­1 or IEC/EN/
UL/CSA 62368­1 or a Class 2 circuit in accordance with NEC or CEC.

4

Installation

Note

Installation and commissioning are to be carried out only by qualified personnel
in accordance with the operating instructions.

4.1 Mechanical and pneumatic

Note

An unfavourable mounting position can impair the function of the product.
 Mount the sensor so that no condensation from the compressed air lines can

gather in the device.

 Install the sensor so that it cannot be heated above the maximum permissible

operating temperature (plan for convection possibilities).

SPAU-...-T

– Seal connecting thread.

Max. 10 Nm

Max. 7 Nm

For example, with double 
nipple 

x

Fig. 9

Fig. 10

SPAU-...-H

SPAU-...-A

– Mounting bracket hole pattern

è

 Fig. 29

M3
max. 0.5 Nm

Fig. 11

Fig. 12

SPAU-...-W

– Wall mounting hole pattern 

è

 Fig. 30

1.

2.

Fig. 13

SPAU-...-F

– Size of the front panel cut-out in mm 

è

 Fig. 14

– Guide sensor from the front into the cut-out on the front panel.
– Attach the clamping plate and press until the fastening slide clips in.

34 ±

0.3

61 ±

0.3

M3
max. 0.7 Nm

s

s < 2 mm: remove 1 washer
s < 1 mm: remove 2 washers

Fig. 14

Fig. 15

Summary of Contents for SPAU Series

Page 1: ... m cable Protective devices G None Safety guard Certificate T None Test report Fig 2 2 Function and application The pressure sensor SPAU is intended for monitoring pressure in the piping The sensor converts pneumatic pressure values relative pressure into electrical sig nals which can be used for control or regulating functions Measurements are carried out using a piezoresistive sensor element wit...

Page 2: ...irements of Underwriters Laboratories Inc UL for USA and Canada Observe the following English language remarks from UL UL approval information Product category code QUYX QUYX7 File number E322346 Considered standards UL 61010 1 CAN CSA C22 2 No 61010 1 UL mark Fig 7 Only for connection to an NEC CEC Class 2 supply Raccorder uniquement a un circuit NEC CEC Classe 2 Electrical and environmental rati...

Page 3: ...ation of the reference value with auto difference monitoring 0008 d SP Threshold value of the differential pressure with auto difference monitoring NO logic Switching characteristics of the switching outputs NO normally open NC normally closed bLUE COLR Display colour bLUE Blue colour change function deactivated R ON Red if switching output set R OFF Red if switching output not set Note Independen...

Page 4: ...e Edit button briefly è SP Lo flashes 3 Set the value for the switching point with A or B key 4 Press the Edit button briefly è SP Hi flashes 5 Set the value for the switching point with A or B key 6 Press the Edit button briefly è t obS flashes 7 With A or B key select the time interval 8 Press the Edit button briefly è d SP flashes 9 With A or B key select the differential pressure 10 Press the ...

Page 5: ...me for configuring the switching outputs for OutA and OutB In the following the process is described using the switching output OutA Requirement The sensor is ready for operation RUN mode If the security code is activated the parameter entry option is blocked Lock flashes Enter the security code è Chap 5 4 1 Establish switching function in the EDIT mode è Chap 5 4 2 Create pressure value 1 3 Press...

Page 6: ... 4 Switch off time ms Max 5 3 Max output current mA 100 Capacitive load maximum DC nF 100 Voltage drop V Max 1 6 Pull down pull up resistor PNP integrated NPN not integrated Inductive protective circuit On hand Analogue output Output characteristic curve initial value final value SPAU V V 0 10 SPAU B V 1 5 SPAU A mA 4 20 Rise time ms 3 at Filt OFF Max load resistance of current output SPAU A Ω 500...

Reviews: