Festo — MSE6-E2M — 2022-08d
Commissioning
Recommended: allocate the station numbers in ascending order. Allocate the station numbers in
accordance with the machine structure of the system.
DIL switch 3
Description
1
2
3
4
5
6
7
8
DIL 3.8
Device-specific diagnostics
ON = activated, factory setting
OFF = deactivated
1)
DIL 3.7
Station number
The station number of the energy efficiency module is set in binary
code with DIL switch 3.1 … 3.7.
Permissible station numbers: 1 … 125
Factory setting: 3
Example
Tab. 24 Setting station number and diagnostic mode,
DIL 3.6
DIL 3.5
DIL 3.4
DIL 3.3
DIL 3.2
DIL 3.1
1) If device-related diagnostics are deactivated, then no device-related diagnostic information about the energy efficiency module will
be sent to the master system.
Tab. 23: Setting station number and diagnostic mode, DIL switch 3
Example for setting station number 23 and activating device-related diagnostics
1
2
3
4
5
6
7
8
DIL 3.8: ON –
Device-related diagnostics activated
DIL 3.7: OFF 2
6
= 64
Example:
2
0
+ 2
1
+ 2
2
+ 2
4
=
1 + 2 + 4 + 16 = 23
Station number set = 23
DIL 3.6: OFF 2
5
= 32
DIL 3.5: ON 2
4
= 16
DIL 3.4: OFF 2
3
= 8
DIL 3.3: ON 2
2
= 4
DIL 3.2: ON 2
1
= 2
DIL 3.1: ON 2
0
= 1
Tab. 24: Setting station number and diagnostic mode, example
8.3.5
Commissioning and configuration
Commissioning and configuration of the bus node depend on the higher-order control.
The steps described below are examples of using the controller ‘Siemens SIMATIC S7-315’ and the
controller software ‘Siemens STEP 7’, version 5.5 with Service Pack SP 3, with English language
version
è
documentation for the higher-level controller and controller software.