38
Festo — MSE6-E2M — 2022-08d
Commissioning
A bus termination network for cable type A is integrated in the housing of the FBS-SUB-9-GS-DP-B
plug. The switch for the bus termination must be in the ON position.
Fig. 21: Circuit diagram for bus termination network for cable type A as per EN 50170, switch in Festo
plug in ON position
8.3.4
Setting DIL switches
You can set the following parameters with the DIL switches:
–
Operating mode. The energy efficiency module only supports the Remote I/O operating mode.
–
PROFIBUS address
–
Diagnostics mode
1. Switch off the power supply.
2. Unscrew the retaining screws of the cover.
3. Remove the cover.
Ä
The 3 DIL switches can now be set.
4. Set the operating mode with DIL switch 1.
5. Set a station number that is not yet allocated for the energy efficiency module with DIL switch
Tab. 24 Setting station number and diagnostic mode, example.
6. Set the diagnostic mode with DIL switch 3.
7. Fit the cover.
8. Screw on the retaining screws hand-tight and then tighten to 0.4 Nm ± 10%.