background image

1. Check the mounting of the drive system.
2. Check wiring of the power supplies and the "DI/DO" digital inputs and out-

puts at the [Power] and [Logic] connections.

Procedure:
1. Switch on load voltage.
2. Switch on logic voltage (switch-on delay ≥50 ms required).
3. Wait for initialisation until C/Q LED is yellow (

L

 7 s).

4. Select the reference end position "Ref" from the HMI interface in the "Refer-

ence" menu and start the referencing movement with end position detection
(only required if the reference end position "Ref" is different from the factory
setting or if the useful range has been changed). The drive system is refer-
enced after successful referencing.

Referencing sets the start press position "Pos

Start Press

" equal to the deter-

mined useful range.

5. Parameterise operating modes via HMI interface:

Basic parameters for point-to-point operation with and without press function
or manual operation (demo)

Velocity "Speed Out"

Velocity "Speed In"

additional parameters for point-to-point operation with press function

Force

Start Press "Pos

Start Press

" position (reference point end position "Ref")

The EMCS-ST is then ready for operation and the application can be controlled via
the "DI/DO" digital inputs and outputs 

è

 9.6 Point-to-point operating modes.

8.2

Commissioning: IO-Link operation

Preparation
1. Check the mounting of the drive system.
2. Check the wiring of the power supplies and the IO-Link "C/Q" interface at the

[Power] and [Logic] connections.

Procedure
1. Switch on load voltage.
2. Switch on logic voltage via IO-Link master (switch-on delay ≥50 ms required).
3. Wait for initialisation until C/Q LED is yellow (

L

 7 s).

4. Select the reference end position  "Ref" from the IO-Link device data

(0x0103.0, reference) and start the referencing movement with end position
detection (0x0104.0, Execute "Reference" Movement) (only required if the
reference end position Ref" is different from the factory setting or if the useful
range has been changed). The drive system is referenced after successful
referencing.

Referencing sets the intermediate position "Pos

Imp

" and the start press posi-

tion "Pos

Start Press

" equal to the determined useful range.

5. Parameterise operating modes via IO-Link interface:

Basic parameters for point-to-point operation with and without press function
or manual operation (demo)

0x0100.0, velocity "Speed In"

0x0101.0: velocity "Speed Out"

0x0106.0, end position "Out" "Lim

Out

" (reference point reference end posi-

tion "Ref")

0x0108.0, intermediate position "Pos

Imp

" (reference point reference end

position "Ref")

additional parameters for point-to-point operation with press function

0x0102.0, "Force"

0x0105.0, start press position "Pos

Start Press

" (reference point reference end

position "Ref")

Then the EMCS-ST is ready for operation and the application can be controlled
via the IO-Link interface "process data 0x0029.1, 0x0029.2 and 0x0029.5" or
"system parameter 0x0002" 

è

 9.6 Point-to-point operating modes.

9

Operation

WARNING

Danger of burns from hot housing surfaces.
Metallic housing parts can reach high temperatures during operation.
Contact with metal housing parts can cause burn injuries.
• Do not touch metallic housing parts.
• After the power supply is switched off, let the device cool down to room

temperature.

9.1

Master control

Lowest priority: DIO operation (after Power ON and initialisation)

Medium priority: IO-Link operation (after established IO-Link communication)

Highest priority: HMI operation (unlocked pushbuttons)

9.2

Dimension reference system

The correct positioning of the drive requires a defined dimension reference
system.

Linear drive system

Ref 

: reference end position (reference point for Lim

In

, Lim

Out

, Pos

Act

, Pos

Imp

 and Pos

Start Press

)

motor facing (default)

motor facing away

Lim

In

/Lim

Out

 

: end positions

Mech

In

/Mech

Out

: mechanical stops

Pos

Act

  : current position

Pos

Imp

: intermediate position (IO-Link only)

Pos

Start Press

: start press position

Tab. 3: Dimension reference system for linear drive systems

9.3

Restart with referencing

Re-initialise reference end position "Ref"
The referencing of the reference end position is lost on Power OFF of the logic
voltage L

+

 [Logic, Pin 1]. After every restart the position of the reference end

position "Ref" is re-initialised at the "Speed Ref" velocity with the first motion
task.

Referencing after a restart as a function of the positioning task

Sequence

Mov

Ref

: force-controlled movement 

 against mechanical stop "Mech

In

"

Mov

Out

: position-controlled movement 

 to the reference end position "Ref"

Travel to the target position as a function of the positioning task

No travel, end position "Lim

In

" reached

Mov

Out

: position-controlled movement 

 to the end position Lim

Out

Mov

Imp

: position-controlled travel 

 to the intermediate position Lim

Imp

 (IO-Link only)

Start

In

 positioning task to the end position Lim

In

Start

Out

 positioning task to the end position Lim

Out

Start

Imp

 positioning task to the intermediate position Pos

Imp

 (IO-Link only)

Tab. 4: Initialise restart sequence with reference end position "Ref"