Festo ELGS-BS Series Operating Instructions Download Page 2

Mounting product 

è

 spindle axis ELGC-BS-KF, instruction manual, operation.

8

Installation

WARNING!

Risk of injury due to electric shock.

For the electrical power supply with extra-low voltages, use only PELV circuits
that guarantee a reinforced isolation from the mains network.

Observe IEC 60204-1/EN 60204-1.

Damage to the device due to non-approved potentials at the pins

Power connection: do not connect pin 3 to high or low potential
(24 V DC/0 V DC).

Logic connection: do not connect pin 2 and 3 to high potential if pin 1 is not
supplied with 24 V DC.

1. Connect the cables to the [Logic] and [Power] connections of the integrated

drive EMCS-ST.

2. Connect cables to the controller or IO-Linkmaster and to the PELV fixed power

supply units.

Wiring diagram: DIO operation (digital I/O)

1 PELV fixed power supply for 24 V

DC load voltage supply

2 Reset button for acknowledging an

error and triggering a restart
(optional)

3 PELV fixed power supply for logic

power supply 24 V DC

4 Higher-level open-loop control

(controller) with digital I/O 

5 EMCS-ST

Fig. 5 Wiring diagram: DIO operation (digital I/O)

Wiring diagram: IO-Link operation, port class A (with and without NEFC adapter)

Current consumption of IO-Link power supply [Logic]

An input current at pin 1 (L+) of 100 ... 150 mA is required for operation.

1 PELV fixed power supply for 24 V

DC load voltage supply

2 IO-Link master with IO-Link inter-

face

3 EMCS-ST

Fig. 6 Wiring diagram: IO-Link operation

1 PELV fixed power supply for 24 V

DC load voltage supply

2 Adapter NEFC

3 IO-Link master with IO-Link inter-

face

4 EMCS-ST

Fig. 7 Wiring diagram: IO-Link operation with adapter

Core colours of Festo cables:
BK = black, BN = brown, BU = blue, GN = green, GY = grey, PK = pink,
WH = white, YE = yellow

9

Commissioning

WARNING!

Risk of injury due to unexpected movement of components.

Protect the positioning range from unwanted intervention.

Keep foreign objects out of the positioning range.

Perform commissioning with low dynamic response.

WARNING!

Severe, irreversible injuries from accidental movements of the connected actu-
ator technology.

Unintentional movements of the connected actuator technology can result from
exchanging the connecting cables of a servo drive or between servo drives.

Before commissioning: All cables must be correctly assigned and connected.

WARNING!

Danger of burns from hot housing surfaces.

Metallic housing parts can reach high temperatures during operation.
Contact with metal housing parts can cause burn injuries.

Do not touch metallic housing parts.

After the power supply is switched off, let the device cool down to room tem-
perature.

9.1

Commissioning: DIO operation (digital I/Os)

Preparation
1. Check the mounting of the drive system.
2. Check wiring of power supplies [Power], [Logic] and digital I/O (DIO) [Logic].
Processing
1. Switch on load voltage.
2. Switch on logic voltage.
3. Wait for initialisation until LED C/Q lights yellow.
4. Parameterise (optional): Velocities (Speed In/Speed Out), Force/Torque

(Force), Reference End Position Ref (Reference) or Start Press Position Pos

Start

Press

 (Start Press) 

è

 10.3 Display and operating components (HMI).

The drive system is ready for operation and can be controlled via the DIO control
interface (digital I/O). With the first motion task and after every restart, the posi-
tion of the reference end position "Ref" is re-initialised (drive first moves to the
reference end position "Ref" before the actual motion task is executed), LED C/Q
lights green.

Control end-to-end operation 

è

 10.5 End-to-end operation.

9.2

Commissioning: IO-Link operation

Preparation
1. Check the assembly of the drive unit.
2. Check the wiring of the power supplies [Power] and the IO-Link interface

[Logic].

3. Install the application software.
4. Open IODD file in the application software 

è

 www.festo.com/sp.

Processing
1. Switch on load voltage.
2. Switch on logic voltage via IO-Link master.
3. Wait for initialisation until LED C/Q lights yellow.
4. Establish IO-Link connection with the drive system.

Summary of Contents for ELGS-BS Series

Page 1: ...ns è www festo com 5 Product overview 5 1 Scope of Delivery The following components are included in the scope of delivery Spindle axis unit ELGS BS Instruction manual for the spindle axis unit ELGS BS Adapter for IO Link operation optional accessory è www festo com catalogue 5 2 System overview 1 PELV fixed power supply for load voltage 2 PELV fixed power supply for logic voltage 3 Application so...

Page 2: ...n objects out of the positioning range Perform commissioning with low dynamic response WARNING Severe irreversible injuries from accidental movements of the connected actu ator technology Unintentional movements of the connected actuator technology can result from exchanging the connecting cables of a servo drive or between servo drives Before commissioning All cables must be correctly assigned an...

Page 3: ...C 4 false Menu function with pushbutton actuators select selecting menu press Parameterise setpoint values Speed Out Speed In and Force Set value 10 20 100 of maximum value è 13 Technical data and save Save press Parameterise the position of the reference end position Ref Set Ref and run the homing movement MovRef StartRef PosAct è LimIn è LimOut press Run Start Press movement Start Stop and save ...

Page 4: ...esto 0x1000 0x000F 15 I2t monitoring power stage error 0x1805 0x0016 22 Logic voltage undersupply2 0x1804 0x0017 23 Logic voltage oversupply 0x1803 0x0026 38 Load voltage undersupply or not connected 0x1802 0x0027 39 Load voltage oversupply 0x1801 0x0031 49 Device undertemperature 0x0033 51 Device overtemperature 0x4000 0x012F 303 IO Link connection lost red light z 1 Additional information è Desc...

Reviews: