Festo CPX-M-FB20/21-Z6 2018-11b English
8
3.2 DIL switch settings
Switch
Setting
Function
1)
1
1 = OFF
Baud rate 500 kBd
1 = ON
Baud rate 2 Mbd
1)
2
---
Reserved
1)
3
3 = OFF
Data format standard
1)
3 = ON
Data format Siemens (Byte swap)
4
4 = OFF
Register undervoltage V
load
as
peripheral fault
1)
4 = ON
Do not register undervoltage V
load
5 / 6
5 = OFF
6 = OFF
(M1) without diagnostics in PAE
1)
5 = OFF
6 = ON
(M2) 4 Byte diagnostics start PAE
5 = ON
6 = OFF
(M3) 2 Byte diagnostics end PAE
5 = ON
6 = ON
(M4) 4 Byte diagnostics end PAE
7 / 8
---
Reserved
1)
1)
Factory setting