[PS] (green)
[PL] (green)
[SF] (red)
[M] (yellow)
Lights up
Lights up
Off
Off
Tab. 8 Display Components after Error-free Commissioning
You can find information on troubleshooting in the event of incorrect behaviour in
the “Description of Automation system CPX-E” and the descriptions of the mod-
ules used
è
10
Service
NOTICE!
Accumulation of heat due to reduced air supply to electronics.
•
Keep the ventilation slots free and regularly remove contamination.
11
Diagnostics and fault clearance
11.1
Diagnostics options
Various options are available for diagnosing errors:
–
Internal system diagnostics
–
LED indicators on the product
11.2
Internal System Diagnostics
•
Activate internal system diagnostics via the corresponding catalogue input.
–
Status bits: E-PN [Status]
–
I/O diagnostic interface: E-PN [STI]
The internal system diagnostics is described in the “Description of automation
system CPX-E”
è
11.3
LED Displays
The network-specific LED displays are described below.
The system-specific LED indicators are described in the documents for the auto-
mation system CPX-E
è
Network fault [NF]
LED
(red)
Meaning
Remedy
Network connection not OK.
Possible causes:
Device name not correct
Check device name.
IO controller defective
Repair IO controller.
Flashes
Network connection interrupted, short-cir-
cuited or disturbed
Check network connection.
Off
No fault (if [PS] LED lights up green)
–
Tab. 9 Network Fault [NF]
Maintenance/PROFIenergy [M/P]
LED
(yel-
low/gr-
een)
Meaning
LED (yellow/green)
Remedy
Lights up
yellow
Maintenance measures required
Check push-in connector.
Flashes
green
PROFIenergy activated
–
Off
No maintenance measures required, no
PROFIenergy activated
–
Tab. 10 Maintenance/PROFIenergy [M/P]
Connection status [XF1], [XF2]
LED
(green)
Meaning
Remedy
Lights up
Network connection OK
–
Flashes
Locating module if the LEDs XF1 and XF2
flash synchronously;
e.g. for fault finding or during configura-
tion
–
Off
No network connection
Check network connection.
Tab. 11 Connection Status [XF1], [XF2]
12
Disposal
ENVIRONMENT!
Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations
è
13
Technical Data
13.1
General Technical Data
General technical data
General technical data
Automation system CPX-E
Description of automation system CPX-E
è
Dimensions
(length × width × height)
1)
[mm]
125.8 × 37.8 × 76.5
Product weight
2)
[g]
145
Mounting position
Vertical/horizontal
Ambient temperature with
vertical mounting position
[°C]
–5 … +60
3)
Ambient temperature with
horizontal mounting position
[°C]
–5 … +50
3)
Storage temperature
[°C]
–20 … +70
Humidity (non-condensing)
[%]
0 … 95
Module code/sub-module code
(CPX-E-specific)
222/34
Module identification
E-PN
Degree of protection in accordance with
EN 60529
IP20
The degree of protection is not UL-tested.
Protection against electric shock
(Protection against direct and indirect
contact in accordance with IEC 60204-1)
through the use of PELV circuits
(protected extra-low voltage)
Electromagnetic compatibility
To EN 61000-6-2/-4 and NE 21
Assigned address space (inputs/outputs)
Without diagnostics
[bit]
–/–
With status bits
[bit]
8/–
With I/O diagnostics inter-
face
[bit]
16/16
1) not including linking element
2) Including linking element
3) for non-conforming technical data see UL operating conditions table UL
Tab. 12 General Technical Data
Power supply
Operating power supply
U
EL/SEN
[V DC]
24
_
25%
Intrinsic current consumption
at nominal operating voltage
24 V from U
EL/SEN
[mA]
73
Reverse polarity protection
24 V U
EL/SEN
against 0 V
U
EL/SEN
Yes
Mains buffering time
[ms]
20
Tab. 13 Power Supply
Network-specific data
Protocol
PROFINET
1)
Specification
(Standards and norms with reference to
PROFINET)
IEC 61158
IEC 61784
IEC 61918
Conformity class
CC-C
Transmission rate
[Mbps]
100
Crossover detection
Auto-MDI/MDI-X