background image

IO-Link ports

1)

Number of ports

4

Max. number of
devices (per port)

1

Max. line length (per port)

[m]

20 (unshielded)

[kBit/s]

230.4 (corresponds with IO-Link COM3)

[kBit/s]

38.4 (corresponds with IO-Link COM2)

Transmission rate (per port)

[kBit/s]

4.8 (corresponds with IO-Link COM1)

Cycle time

[ms]

Minimum supported cycle time of the connected IO-Link
device

2)

Max. current U

EL/SEN

(per module)

[A]

1.8

Max. current U

OUT

 (per port)

[A]

1.6

Reverse polarity protection

3)

Yes, for U

EL/SEN

 and U

OUT

 respectively

Max. process data length (per port)

If all ports 1 … 4 are activ-
ated by
DIL switches

è

 Tab. 5 DIL

switch

[Bytes]

8 E/8 A

If only ports 1 and 2 are
activated by
DIL switches

è

 Tab. 5 DIL

switch

[Bytes]

16 E/16 A

If only port 1 is activated
by DIL switches

è

 Tab. 5 DIL

switch

[Bytes]

32 E/32 A

Short-circuit protection operating voltage supply U

EL/SEN

Electronic (per module)

1.8

Thermal (per port)

3.0

Behaviour after end of overload

Can be parameterised

Short-circuit protection load voltage supply U

OUT

Electronic (per module)

1.6

Thermal (per port)

3.0

Behaviour after end of overload

Can be parameterised

Electrical isolation

Between the ports

No

Between U

EL/SEN

 and U

OUT

[V]

Yes, DC 75/AC 60

1) in accordance with IO-Link specification V1.1
2) The cycle time used can be permanently set using the “Cycle time” parameter.
3) without feedback protection

Tab. 15 IO-Link Ports

Ambient conditions UL/CSA

Pollution degree

3

Installation site

for indoor use only

Max. installation height

[m]

2000

Tab. 16 Ambient Conditions UL/CSA