Connection for voltage forwarding [XD2]
Socket M8, 4-pin, A-coded
Signal
1
+24 V DC logic supply PS
2
0 V DC load supply PL
3
0 V DC logic supply PS
4
+24 V DC load supply PL
Tab. 5 Connection for voltage forwarding
Connection for system communication [XF10]
Socket M8, 4-pin, D-coded
Signal
1
TX
–
Transmitted data
–
2
RX+
Received data +
3
TX+
Transmitted data +
4
RX
–
Received data
–
Tab. 6 Connection for system communication
Connection for system communication [XF20]
Socket M8, 4-pin, D-coded
Signal
1
RX
–
Received data
–
2
TX+
Transmitted data +
3
RX+
Received data +
4
TX
–
Transmitted data
–
Tab. 7 Connection for system communication
Connection for inputs [X0]
…
[X3]
Socket M12, 5-pin, A-coded
Signal
1
+24 V DC inputs
2
Input 1, 3, 5, 7
3
0 V DC inputs
4
Input 0, 2, 4, 6
5
Functional earth FE
Tab. 8 Connection for inputs