14
Festo — CPX-AP-A-8DI-M12-5P — 2022-07
Technical data
Digital inputs
No. of inputs
8
Type in accordance with
IEC 61131-2
3 (24 V DC)
Cable length
[m]
Max. 30
Design
[V DC]
0 … 30, positive logic (PNP)
Logic level (logic 0/1)
[V DC]
£
5/
³
11
Input debounce time
Parameterisable
Electrical isolation between
the channels
No
Electrical isolation between
inputs and PS
No
Sensor supply
Sensor power supply SEN
[V DC]
24
±
25%
Voltage drop at short-circuit
protection (reduction SEN)
[V DC]
£
1
Reverse polarity protection
24 V SEN against 0 V SEN
Yes
Potential difference between
0 V SEN external and 0 V
SEN internal
Not permissible
Sensor power supply short circuit protection
Short-circuit protection
Electronic
Trigger level
[A]
>
1.8
Characteristic
Slow-blowing
Response after end of over-
load
Automatic recovery
Tab. 13: Digital inputs