A.2 CABLE LENGTH AND SECTIONAL AREA
PLEASE NOTE
The following information is for the exclusive
use of personnel trained in electrotechnology
and who are already familiar with the contents
of the chapters on "Installation" in this manual.
A load-dependent drop in voltage occurs on all
three cables for the operating voltage supply to a
valve terminal. This can cause the voltage at pin
1 or 2 of the operating voltage connection to be
outside the permitted tolerances.
Recommendation
•
Avoid long distances between the power unit
and the terminal.
•
Calculate suitable cable lengths and sectional
areas in accordance with the following graphs
or formulae. Please note that:
– the graphs supply proximity values for
sectional areas; 1.5 and 2.5 mm
2
.
– the formulae supply exact values for any
sectional area.
PLEASE NOTE
The following graphs and formulae assume as
a basis that the operating voltage supply
cables (pins 1, 2 and 3) have the same sec-
tional area.
VIFB8 - 03/05
Appendix A
A-6
9809c
Summary of Contents for 03-FB-8 Series
Page 15: ...VIFB8 03 05 General safety instructions XIV 9809c ...
Page 16: ...1 SYSTEM SUMMARY VIFB8 03 05 1 System summary 9809c 1 1 ...
Page 28: ...2 FITTING VIFB8 03 05 2 Fitting 9809c 2 1 ...
Page 41: ...3 INSTALLATION VIFB8 03 05 3 Installation 9809c 3 1 ...
Page 74: ...4 COMMISSIONING VIFB8 03 05 4 Commissioning 9809c 4 1 ...
Page 96: ...5 DIAGNOSIS AND ERROR TREATMENT VIFB8 03 05 5 Diagnosis and error treatment 9809c 5 1 ...
Page 110: ...TECHNICAL APPENDIX VIFB8 03 05 Appendix A 9809c A 1 ...
Page 122: ...INDEX VIFB8 03 05 Appendix B 9809c B 1 ...
Page 127: ...VIFB8 03 05 Appendix B B 6 9809c ...