3. Installation
3-9
Festo P.BE-VIDN-03-8A-GB 0003NH
3.3
Connecting the valve terminal
3.3.1 Connecting cable
Use a twisted screened 4-core cable for the field bus. The bus
interface and the internal logic of the valve terminal are sup-
plied with power via the field bus cable.
Please note
S
You must refer to the PLC manual or to the manual for
your scanner in order to ascertain the correct type of
cable to use.
S
Take into account here the distance and the baud rate
selected. Select the appropriate cable diameter.
Notice the voltage drop:
– in the supply cable for the bus interface and
– in the internal logic of the valve terminal.
Bus length
The table below shows the guide values for the distance de-
pending on the baud rate selected. Detailed information can
be found in the manuals for your control system and
scanner.
Baud rate
Maximum
main bus
length
Branch line
length
(maximum)
Branch line
length
(cumulative)
125 kBaud
500 m
6 m
156 m
250 kBaud
250 m
78 m
500 kBaud
100 m
39 m
Summary of Contents for 03-B
Page 2: ......
Page 4: ...Contents and general safety instructions II Festo P BE VIDN 03 8A GB 0003NH...
Page 14: ...Contents and general safety instructions XII Festo P BE VIDN 03 8A GB 0003NH...
Page 15: ...System summary 1 1 Festo P BE VIDN 03 8A GB 0003NH Chapter 1...
Page 25: ...Fitting 2 1 Festo P BE VIDN 03 8A GB 0003NH Chapter 2...
Page 35: ...Installation 3 1 Festo P BE VIDN 03 8A GB 0003NH Chapter 3...
Page 59: ...Commissioning 4 1 Festo P BE VIDN 03 8A GB 0003NH Chapter 4...
Page 77: ...Diagnosis and error treatment 5 1 Festo P BE VIDN 03 8A GB 0003NH Chapter 5...
Page 90: ...5 Diagnosis and error treatment 5 14 Festo P BE VIDN 03 8A GB 0003NH...
Page 91: ...Technical Appendix A 1 Festo P BE VIDN 03 8A GB 0003NH Appendix A...
Page 118: ...A Technical Appendix A 28 Festo P BE VIDN 03 8A GB 0003NH...