Ferroli SKY ECO C Instructions For Use, Installation And Maintenance Download Page 35

SKY ECO C

35

ENG

code A73022200

1  USER'S MANUAL

1.1  Introduction 

The new 

SKY ECO C

 is a high-performance, low-emission heater for domestic hot water 

production, powered by 

natural gas

 or 

LPG

 and equipped with a compact, 

WATER-

COOLED

, battery-powered burner with electronic ignition, designed for indoor installation.

1.2  Control panel

3

5

2

1

4

fig. 1 - Control panel

DHW temperature indication at the outlet 
from the boiler

2

  Battery charge indication. Fixed symbol: 

Very low battery; change as soon as pos-
sible. When flashing, the battery is dead 
and must be replaced.

3

 

Burner power adjustment

4

 

Temperature adjustment

5

 

Burner on indication

1.3  Turning the heater on and off

Preliminary checks and operations
1. Make sure the hot water taps are closed.
2. Open the gas supply cock to the heater, located at the gas connection to the unit.
3. Check that the 1.5 V batteries are properly installed with the correct polarity (+/-). To 

replace the batteries, see (3.4 Replacing the batteries).

4. Also verify that the batteries are sufficiently charged for heater operation.

1.3.1  Turning the unit on

Turn the knob to the required water heating level.
The unit will begin operating every time hot water is drawn.

fig. 2 - Turning the unit on

1.3.2  Turning the unit off

The burner goes off automatically when hot water is no longer demanded.
To use the unit again, no action is required.
To completely shut off the unit, place the knob in the () position.

fig. 3 - Turning the unit off

If the water heater will not be used for an extended period of time, close the gas cock 
supplying the unit.

If the unit will be inactive for an extended period of time during the 

winter, all water should be removed to avoid ice damage.

1.4  Settings

1.4.1  Setting the burner power manually

Use the knob (3 - fig. 1) to select the heater power. You may choose between the mini-
mum, maximum, and intermediate positions, depending on the required heating power.
If the knob is turned counterclockwise, the unit will operate at maximum power. If the 
temperature is too high, for example in the summer, or if you need a reduced flow of not 
very hot water, turn the knob clockwise. This reduces the power, and therefore the gas 
consumption. In the 

 

position, the unit is turned off.

1.4.2  Setting the temperature 

Turn the water temperature selector clockwise to increase the temperature, or counter-
clockwise to decrease it.

fig. 4 - Setting the temperature

1.5  Faults

Once the adjustments described above have been made, the heater is ready to operate 
automatically. When a hot water tap is opened, an intermittent discharge is generated on 
the ignition electrode to light the burner.
All electronic models have an ionization electrode built into the burner to monitor flame 
presence. If a malfunction or lack of gas causes the heater to turn off, close the hot water 
tap.
It is then necessary to eliminate the fault or obstacle preventing the gas from reaching the 
heater, e.g., inadvertent closing of the gas cock, empty gas cylinder, etc.
To reactivate the heater, close and open the hot water tap.
If no hot water is produced after eliminating the cause and opening the hot water tap, 
repeat the process.
If the problem persists, call the technical support center.

Table 1 - Faults 

The burner does 
not ignite

Absence of gas

Check the flow of gas 
to the heater, and make 
sure the pipes have been 
purged.

Failure of the 
ignition/detection 
electrode

Check the electrode 
cable, and make sure it's 
properly connected and 
free of deposits.

Defective gas valve

Check and/or change the 
gas valve.

Activation of the 
over-temperature 
protection

Damaged or badly 
positioned heating 
sensor

Check that the heating 
sensor is properly instal-
led and operating and/or 
change it.

Activation of the 
flue gas thermo-
stat (after this 
operation, the unit 
is reset by turning 
on the tap, and 
the thermostat 
cools off).

Flue gas thermostat 
contact open

Check the thermostat.

Cables 
disconnected

Check the connections.

Thermostat 
obstructed or 
incorrectly sized

Check the thermostat.

Probe disconnected

Check the connection or 
change the probe.

Summary of Contents for SKY ECO C

Page 1: ...STRUCCI N DE USO INSTALACI N Y MANTENIMIENTO RO INSTRUC IUNI DE UTILIZARE INSTALARE I NTRE INERE PL INSTRUKCJAOBS UGI INSTALACJI I KONSERWACJI EN INSTRUCTIONS FOR USE INSTALLATIONAND MAINTENANCE BAJAS...

Page 2: ...a personale professionalmente qualificato utilizzando esclusivamente ricambi originali Il mancato rispetto di quanto sopra pu compromettere la sicurezza dell apparecchio Questo apparecchio dovr essere...

Page 3: ...ura fosse troppo elevata ad esempio d estate o quando fosse necessaria una portata ridotta di acqua non molto calda girare la manopola in senso orario Si riduce cos la potenza e di conseguenza il cons...

Page 4: ...nell ambiente domestico risultano estremamente nocivi alla salute Il luogo di installazione deve comunque essere privo di polvere oggetti o materiali infiam mabili o gas corrosivi La caldaia predispos...

Page 5: ...Effettuare l allacciamento con un tubo metallico rigido per la rete di erogazione del gas oppure un tubo flessibile impianto GPL a parete continua in acciaio inox frapponendo un rubinetto del gas tra...

Page 6: ...iano perdite d acqua nell impianto o nell apparecchio Verificare il collegamento dell impianto elettrico e la funzionalit dell impianto di terra Verificare che il valore di pressione del gas sia quell...

Page 7: ...taria da 1 2 4 2 Vista generale e principali componenti 13 5 10 12 9 8 16 11 3 1 2 14 15 4 6 7 fig 11 Vista generale 1 Entrata gas 2 Entrata acqua fredda 3 Uscita acqua calda sanitaria 4 Camera combus...

Page 8: ...m3 h 0 873 1 10 Ugelli bruciatore G30 n x 12 x 0 50 14 x 0 50 Pressione gas alimentazione G30 mbar 28 30 28 30 Pressione gas max al bruciatore G30 mbar 27 5 27 5 Pressione gas min al bruciatore G30 mb...

Page 9: ...SKY ECO C 9 IT cod A73022200 4 5 Schema elettrico 9 10 11 13 16 12 8 14 17 15 fig 13 Legenda punto 4 2...

Page 10: ...do recambios originales En caso contrario puede comprometerse la seguridad del equipo Este equipo se ha de destinar s lo al uso para el cual ha sido expresamente dise ado Todo otro uso ha de considera...

Page 11: ...Si el mando se gira hacia la izquierda el aparato funciona a la potencia m xima Si la temperatura es demasiado alta por ejemplo en verano o si se necesita un caudal reducido de agua no muy caliente g...

Page 12: ...aso el aparato se ha de instalar en un lugar sin polvo ni objetos o materia les inflamables o gases corrosivos El aparato puede fijarse a la pared Fijar a la pared seg n las cotas indicadas en el apar...

Page 13: ...stalaci n g l p de pared continua de acero inoxidable interponiendo una llave de corte entre la instalaci n y el equipo LO MAS PR XIMO POSIBLE AL APARATO 3 Al finalizar la instalaci n de la red de gas...

Page 14: ...ue no haya p rdidas de agua en la instalaci n ni en el equipo Controlar que la conexi n a la instalaci n el ctrica y la puesta a tierra sean adecuadas Controlar que la presi n del gas sea correcta Con...

Page 15: ...2 4 2 Vista general y componentes principales 13 5 10 12 9 8 16 11 3 1 2 14 15 4 6 7 fig 11 Vista general 1 Entrada de gas 2 Entrada de agua fr a 3 Salida de agua caliente sanitaria 4 C mara de combu...

Page 16: ...G20 m3 h 2 241 2 85 Caudal m nimo gas G20 m3 h 0 873 1 10 Inyectores quemador G30 n x 12 x 0 50 14 x 0 50 Presi n de alimentaci n gas G30 mbar 28 30 28 30 Presi n m x quemador con G30 mbar 27 5 27 5 P...

Page 17: ...SKY ECO C 17 ES cod A73022200 4 5 Esquema el ctrico 9 10 11 13 16 12 8 14 17 15 fig 13 Leyenda apartado 4 2...

Page 18: ...folosesc pie se de schimb originale n caz contrar ar putea fi compromis siguran a aparatului Acest aparat trebuie utilizat numai n scopul pentru care a fost proiectat n mod expres Orice alt utili zar...

Page 19: ...aratul pune i butonul pe pozi ie fig 3 Oprirea Dac nchiderea dureaz mai mult nchide i robinetul de gaz de la intrarea n aparat n cazul unei opriri prelungite n perioada de iarn pentru a evita daunele...

Page 20: ...t rile locale privind instalarea i evacuarea produ ilor de combustie 2 2 Locul de instalare Circuitul de ardere este de tipul cu camer deschis i prin urmare aparatul poate fi instalat i poate func ion...

Page 21: ...ne i n acestea elementele de fixare prev zute pentru amplasarea aparatului Cod C85016210 fig 5 ablonul de montare 5 Scoate i aparatul din ambalaj 6 Verifica i toat documenta ia 7 Scoate i dopurile de...

Page 22: ...dic descrise n continuare trebuie s fie efectuate de un tehnician autorizat n conformitate cu reglement rile n vigoare FERROLI i declin orice responsabilitate pentru pagubele produse bunurilor sau per...

Page 23: ...ect Instala iile de gaz i de ap trebuie s fie perfect etan e Debitul de gaz i presiunea de func ionare trebuie s se men in n intervalul de valori indicat n tabele Pentru a cur a carcasa ori p r ile fi...

Page 24: ...16 11 3 1 2 14 15 4 6 7 fig 11 Vedere general 1 Intrare gaz 2 Intrare ap rece 3 Ie ire ap cald menajer 4 Camer de combustie 5 Grup de arz toare 6 Schimb tor de c ldur din cupru 7 Colector gaze arse 8...

Page 25: ...8 10 4 5 9 6 fig 12 Circuitul hidraulic 1 Intrare gaz 2 Intrare ap rece 3 Ie ire ap cald menajer 4 Grup de arz toare 5 Schimb tor de c ldur din cupru 6 Colector gaze arse 7 Valv de gaz 8 Senzor temper...

Page 26: ...cjonowanych serwisant w Naprawy urz dzenia oraz wymiany jego kom ponent w nale y zleca wy cznie licencjonowanym serwisantom Stosowa wy cznie oryginalne cz ci zamienne Nieprzestrzeganie tego zalecenia...

Page 27: ...symalnej z pozycjami po rednimi w cznie odpowiednio do danej intensywno ci pod grzewania Je li pokr t o b dzie obr cone ca kowicie w lewo urz dzenie b dzie pracowa z moc mak symaln Je li temperatura j...

Page 28: ...rodowisku domowym s bardzo szkodliwe dla zdrowia Urz dzenie nale y zawsze instalowa w miejscu wolnym od py u kurzu przedmiot w lub materia w atwopalnych oraz gaz w r cych Urz dzenie mo na mocowa na ci...

Page 29: ...laj c w gaz a urz dzeniem zainstalowa zaw r odcinaj cy MO LIWIE JAK NAJBLI EJ URZ DZENIA 3 Po zako czeniu pod czenia do sieci gazowej sprawdzi czy wszystkie pod czenia gazowe s szczelne W tym celu prz...

Page 30: ...elno ci na z czach za pomoc roztworu wody z myd em Nape ni instalacj hydrauliczn i sprawdzi czy w urz dzeniu lub w instalacji nie ma po wietrza Sprawdzi czy nie ma wyciek w wody z instalacji lub z urz...

Page 31: ...PARAMETRY I DANE TECHNICZNE 4 1 Wymiary i pod czenia Model A mm B mm C mm D mm a4 mm 11 295 210 62 62 110 14 335 250 50 58 130 A B a4 595 195 95 C 106 5 D 1 2 3 fig 10 Wymiary i pod czenia 1 Wlot gaz...

Page 32: ...a jonizacyjna 11 Podw jny czujnik bezpiecze stwo c w u 12 Termostat bezpiecze stwa 13 Termostat temperatury spalin 14 Termostat wlotu wody 15 Baterie 16 Elektronika 17 Mikroprze cznik nat enia przep y...

Page 33: ...nienie palnika przy G30 mbar 5 5 Maks nat enie przep ywu gazu G30 m3 h 1 7 2 11 Min nat enie przep ywu gazu G30 m3 h 0 65 0 80 Dysze palnika G31 Licz ba x 12 x 0 50 14 x 0 50 Ci nienie zasilania gazu...

Page 34: ...nt parts Otherwise the safety of the unit may be compromised This unit may only be used for the purpose for which it was expressly designed Any other use must be considered inappropriate and therefore...

Page 35: ...s turned counterclockwise the unit will operate at maximum power If the temperature is too high for example in the summer or if you need a reduced flow of not very hot water turn the knob clockwise Th...

Page 36: ...tach it to the wall in accordance with the dimensions indicated in section 4 1 The wall installation must be firm and stable If the unit is installed inside a cabinet or joined laterally to other elem...

Page 37: ...OSE TO THE UNIT AS POSSIBLE 3 Once the connection to the gas network is complete check that all gas connections are tight For this purpose a tightness test must be performed To avoid damage to the uni...

Page 38: ...the hydraulic system and make sure no air is present in the unit or system Check that there are no water leaks in the system or unit Make sure the grounding and connection to the electrical network a...

Page 39: ...inlet 3 1 2 domestic hot water outlet 4 2 Overview and main components 13 5 10 12 9 8 16 11 3 1 2 14 15 4 6 7 fig 11 Overview 1 Gas inlet 2 Cold water inlet 3 Domestic hot water outlet 4 Combustion ch...

Page 40: ...h 2 241 2 85 Minimum gas delivery G20 m3 h 0 873 1 10 Burner injectors G30 no x 12 x 0 50 14 x 0 50 Gas supply pressure G30 mbar 28 30 28 30 Max burner pressure with G30 mbar 27 5 27 5 Min burner pre...

Page 41: ...SKY ECO C 41 ENG code A73022200 4 5 Wiring diagram 9 10 11 13 16 12 8 14 17 15 fig 13...

Page 42: ......

Page 43: ......

Page 44: ...Fabbricato in Italia Made in Italy FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli com...

Reviews: