IR
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
19,1
21,2
24,8
29,6
34,2
38,6
kW
Power input
7,34
8,09
9,42
11,6
13,3
15,0
kW
EER
2,60
2,62
2,63
2,55
2,57
2,57
-
Water flow rate plant side
3295
3655
4273
5113
5903
6658
l/h
Pressure drops plant side
24
29
24
33
28
36
kPa
IP
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
18,7
20,8
24,3
29,1
33,6
37,8
kW
Power input
7,27
8,00
9,33
11,4
13,1
14,9
kW
EER
2,57
2,60
2,60
2,55
2,56
2,54
-
Water flow rate plant side
3226
3586
4187
5010
5783
6520
l/h
Pressure drops plant side
23
28
23
32
27
34
kPa
Heating A7W45
( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
19,9
22,2
25,8
31,0
35,8
40,3
kW
Power input
6,22
6,85
7,98
9,88
11,3
12,8
kW
COP
3,20
3,24
3,23
3,14
3,17
3,15
-
Water flow rate plant side
3381
3773
4388
5259
6078
6847
l/h
Pressure drops plant side
25
30
25
35
30
37
kPa
Heating A2W45
( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
16,4
18,3
21,3
25,5
29,5
33,2
kW
Power input
6,13
6,74
7,87
9,73
11,1
12,6
kW
COP
2,68
2,72
2,71
2,62
2,66
2,63
-
Water flow rate plant side
2800
3107
3620
4337
5020
5651
l/h
Pressure drops plant side
17
21
17
24
21
26
kPa
Frame
1
2
Model
19 .1
22 .1
26 .1
30 .1
35 .1
40 .1
U.M.
Power supply
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
V-ph-Hz
IR
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
19,2
21,3
24,9
29,8
34,4
38,8
kW
EER
2,64
2,67
2,67
2,61
2,63
2,62
-
Pressure drops plant side
24
29
24
33
28
35
kPa
ESEER
2,98
3,02
3,02
2,95
2,97
2,96
-
IP
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
18,8
20,9
24,4
29,2
33,7
38,0
kW
EER
2,61
2,64
2,64
2,58
2,59
2,59
-
Pressure drops plant side
23
28
23
32
27
34
kPa
ESEER
2,95
2,98
2,98
2,92
2,93
2,93
-
Heating A7W45
(air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity
19,8
22,1
25,7
30,8
35,6
40,1
kW
COP
3,22
3,28
3,26
3,17
3,21
3,18
-
Pressure drops plant side
25
31
25
35
30
38
kPa
13
TECHNICAL DATA AND PERFORMANCES
Frame
1
2
Model
19 .1
22 .1
26 .1
30 .1
35 .1
40 .1
U.M.
Power supply
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
400 - 3N - 50
V-ph-Hz
NOMINAL performances - Low noise setting up (AS) - Standard plants
NOMINAL performances - Low noise setting up (AS) - Standard plants - EUROVENT certified data
Data declared according to
EN 14511
. The values are referred to units without options and accessories.
Performances referred to an available static head of the fan equal to 150 Pa.
Performances referred to an available static head of the fan equal to 150 Pa.
Summary of Contents for RMP series
Page 4: ...4...
Page 24: ...Cod 3QE29590...