CONTROL SYSTEM

Label

Description

RW

Register

address

Bit

number

Lsb

CPL

EXP

UM

Dec

Hex

COOL

Set point cooling

RW

16900

4204

16

0

Y

-1

°C

HEAT

Set point heating

RW

16902

4206

16

0

Y

-1

°C

CF19

Remote stand by enable

RW

49303

C097

8

0

Y

0

-

CF20

Remote Cooling-Heating enable

RW

49304

C098

8

0

Y

0

-

CF63

Device serial address

RW

49178

C01A

8

0

N

0

-

tr01

Heat pump enable

RW

49665

C201

8

0

N

0

-

tr17

Heat pump lock set point

RW

16930

4222

16

0

Y

-1

°C

PI05

Modulating pump speed : cooling

RW

49749

C255

8

0

N

0

%

PI11

Modulating pump speed : heating

RW

49757

C25D

8

0

N

0

%

Hi02

Integrative electrical heaters enable

RW

49858

C2C2

8

0

N

0

-

CP01

Compressor operating hours

R

753

02F1

16

0

N

0

ore

PU01

Pump operating hours

R

763

02FB

16

0

N

0

ore

AI01

Water inlet probe

R

344

0158

16

0

Y

-1

°C

AI02

Water outlet probe

R

346

015A

16

0

Y

-1

°C

AI03

Liquid line probe

R

348

015C

16

0

Y

-1

°C

AI04

Outdoor air probe

R

350

015E

16

0

Y

-1

°C

-

Unit operating in COOLING

R

33028

8104

1

4

N

0

-

-

Unit operating in HEATING

R

33028

8104

1

6

N

0

-

-

Unit in STAND BY (user interface or serial communication)

R

33028

8104

1

2

N

0

-

-

Unit in STAND BY (digital input)

R

33028

8104

1

3

N

0

-

-

Unit in OFF

R

33028

8104

1

0

N

0

-

-

COOLING mode enable *

W

33471

82BF

1

3

N

0

-

-

HEATING mode enable *

W

33471

82BF

1

4

N

0

-

-

STAND BY enable *

W

33471

82BF

1

5

N

0

-

-

Unit switching on ( 1 = ON ; 0 = OFF )

W

33471

82BF

1

7

N

0

-

-

Alarm  

Er05

R

33037

810D

1

5

N

0

-

-

Alarm

 Er20

R

33039

810F

1

4

N

0

-

-

Alarm

 Er30

R

33040

8110

1

6

N

0

-

-

Alarm

 Er41

R

33042

8112

1

1

N

0

-

-

Alarm

 Er45

R

33042

8112

1

5

N

0

-

-

Alarm

 Er46

R

33042

8112

1

6

N

0

-

-

Alarm

 Er60

R

33044

8114

1

4

N

0

-

-

Alarm

 Er61

R

33044

8114

1

5

N

0

-

-

Alarm

 Er62

R

33044

8114

1

6

N

0

-

-

Alarm

 Er68

R

33045

8115

1

4

N

0

-

* If several operation modes are enabled by mistake :

OFF has priority over STAND BY, HEATING, COOLING

STAND BY has priority over HEATING, COOLING

HEATING has priority over COOLING

Temperature

Resistance

[°C]

[k

]

0

25,7950

5

21,3963

10

17,7477

15

14,7213

20

12,2110

25

10,1287

30

8,4015

35

6,9688

40

5,7805

45

4,7948

50

3,9771

55

3,2989

Probes characteristics

The temperature probes used are NTC 10K (10 kΩ

 

at 25°C).

When the probe bulb is at the temperature of 25°C the electrical resi-

stance measurable at the probe ends is 10 kΩ.

The thermistor of these probes has a negative temperature coefficient: 

the electrical resistance value decreases as the temperature increases.

To find out if a temperature probe is faulty or disconnected, check the 

correspondence between the resistance value in kΩ and the bulb tem-

perature in °C according to the table.

For a reliable verify it is not necessary to check all the single values but 

is  enough  to  check  some  random  values.  If  the  instrument  indicates 

neverending resistance then the probe is interrupted.

Summary of Contents for RMA series

Page 1: ...RMA AIR WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL R E F R I G E R A N T G A S E C O FRIEND L Y...

Page 2: ...of experiences and of particular research studies and has been made with top quality materials and advanced technologies The CE mark guarantees that the products satisfy all the applicable European Di...

Page 3: ...diant plants 14 COOLING performances 15 HEATING performances 16 Plant side hydraulic performances 17 Operating limits 19 Electrical data 20 Noise levels 21 Weights 22 Overall dimensions 23 Minimum ope...

Page 4: ...n If the unit requires fixing contact only specialized service centers recognized by the manufacturer and use original spare parts The unit must be installed outdoor and connected to a hydronic coolin...

Page 5: ...duce noise emissions in such operating conditions The low noise acoustic setting up AS is obtained starting from the base setting up AB reducing the rotational speed of the fans and mounting sound jac...

Page 6: ...rcuit high and low pressure switches in order to assure the compressor to operate inside the permitted limits 4 way reverse cycle valve 6 to allow operating mode change reversing the refrigerant flow...

Page 7: ...pump operating hours recording serial communication through Modbus protocol remote stand by remote cooling heating general alarm digital output Versions Each model can be supplied in three different v...

Page 8: ...nal speed of the pump in order to get the requested flow rate without the necessity to install other setting devices The thermal inertia of the buffer tank allows to reduce the number of compressor st...

Page 9: ...he operating conditions of the unit through Modbus communication protocol The RS485 serial line ensures the signal quality up to distances of about 1200 meters that can be extended by means of proper...

Page 10: ...Type axial axial axial axial axial axial Quantity 1 1 1 1 1 1 n Diameter 630 630 630 800 800 800 mm Maximum rotational speed 900 900 900 900 900 900 rpm Total installed power 0 6 0 6 0 6 1 8 1 8 1 8...

Page 11: ...ops plant side 25 30 25 35 29 37 kPa Heating A7W45 source air in 7 C d b 6 C w b plant water in 40 C out 45 C Heating capacity 21 0 23 3 27 1 32 5 37 6 42 4 kW Power input 6 49 7 14 8 33 10 3 11 7 13...

Page 12: ...12 7 14 4 kW EER 3 45 3 47 3 47 3 37 3 40 3 38 Water flow rate plant side 4173 4637 5410 6475 7471 8432 l h Pressure drops plant side 37 45 37 52 44 56 kPa Heating A7W35 source air in 7 C d b 6 C w b...

Page 13: ...4 3 17 3 15 Water flow rate plant side 3381 3773 4388 5259 6078 6847 l h Pressure drops plant side 25 30 25 35 30 37 kPa Heating A2W45 source air in 2 C d b 1 C w b plant water in 40 C out 45 C Heatin...

Page 14: ...1 9 13 7 15 5 kW EER 3 07 3 09 3 11 3 02 3 03 3 01 Water flow rate plant side 4002 4448 5204 6217 7179 8089 l h Pressure drops plant side 34 42 34 48 41 51 kPa Heating A7W35 source air in 7 C d b 6 C...

Page 15: ...e graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions The reference nominal condition is...

Page 16: ...allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions The reference nominal condition is A7W35 sou...

Page 17: ...to units operating with water at the temperature of 10 C density 1000 kg m3 Flow rate l h Pressure drops kPa 0 40 80 120 160 200 240 280 320 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 Available s...

Page 18: ...8000 9000 Available static head unit with option Storing and pumping module Modulating pump or Tank and modulating pump The graphs are referred to units operating with water at the temperature of 10...

Page 19: ...0 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 HEATING Inlet air temperature d b C Outlet temperature plant side C The graphs reported below show the operating area inside which the cor...

Page 20: ...1 A F L I Maximum total power input 0 7 0 7 0 7 0 7 1 0 1 0 kW Standard pump option Power supply 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 V ph Hz F L A Maximum total current input 6 1 6 1...

Page 21: ...ions A35W7 Unit placed in free field on reflecting surface directional factor equal to 2 The sound power level is measured according to ISO 3744 standard The sound pressure level is calculated accordi...

Page 22: ...pumping module Standard pump 9 9 9 9 11 11 kg High head pump 12 12 12 12 13 13 kg Modulating pump 12 12 12 14 16 16 kg Tank and standard pump 31 31 31 31 33 33 kg Tank and high head pump 34 34 34 34...

Page 23: ...od accessibility and facilitate maintenance and control operations A 400 mm B 600 mm C 200 mm Plant return Plant flow Frame 1 2 Model 19 1 22 1 26 1 30 1 35 1 40 1 1 1 1 4 F 1 1 4 F 1 1 4 F 1 1 4 F 1...

Page 24: ...n heating mode is collected in the tray obtained in the basement of the unit and can be drained connecting a pipe to the fitting supplied as standard with all the heat pump units Precautions during wi...

Page 25: ...uitable for ensuring protection against overcurrents and indirect contacts must be installed upstream each power supply line Coordination between line switch must be carried out observing the regulati...

Page 26: ...o avoid damages to the unit Prevent the unit or parts of it from falling down Storing The units must be stored in a dry place repaired from sun rain sand or wind Do not stack the units Maximum tempera...

Page 27: ...V Calculate the average line voltage value average V1 2 V2 3 V3 1 3 390 397 395 3 394 V Calculate the percentage unbalance value Vmax Vaverage x 100 7 394 x 100 1 78 2 Turning on Turn on the main swi...

Page 28: ...ed on the unit To each button are associated a direct function indicated on the button itself and activated pressing the button an associated function indicated on the front of the instrument at the c...

Page 29: ...ns Amber Active load Safety time in progress Pump Amber Active load Safety time in progress Display Normally are shown the setting temperature that is the water inlet temperature in tenths of Celsius...

Page 30: ...point heating COOL Display real set point cooling Hr CP01 Display compressor operating hours PU01 Display pump operating hours Programming Press ESC SET buttons at the same time combined functioni ESC...

Page 31: ...t exchanger antifreeze heater relay 2 A resistive 250 Vac RAG RE1 Tank antifreeze heater Integrative heater 1st step DO5 P Pump 500mA 12Vdc voltage output for control of relay K1 4 A resistive 250 Vac...

Page 32: ...the Alarm digital output is disabled The deactivation of the alarm does not affect the alarm in progress Number of events per hour For some alarms the number of events per hour is recorded if in the...

Page 33: ...larm is bypassed for 120 seconds from the activation of the compressor or of the reverse cycle valve The alarm is disabled during defrosting Er20 Differential pressure switch The alarm is activated if...

Page 34: ...eat exchanger heater When the outdoor air temperature approaches 0 C if the unit is not working the pump is activated in any case to prevent excessive cooling of the water in the pipes Integrative ele...

Page 35: ...must appear in the message Some registers contain more than one piece of information in this case the bits representing the resource value are identified by means of the number of bits used Bit number...

Page 36: ...4 N 0 STAND BY enable W 33471 82BF 1 5 N 0 Unit switching on 1 ON 0 OFF W 33471 82BF 1 7 N 0 Alarm Er05 R 33037 810D 1 5 N 0 Alarm Er20 R 33039 810F 1 4 N 0 Alarm Er30 R 33040 8110 1 6 N 0 Alarm Er41...

Page 37: ...ly cable that connects the unit to the distribution panel is not affected by cuts cracks or alterations that could compromise the insulation Contact an authorized service center if maintenance is requ...

Page 38: ...Inhalation Do not administer anything if the person has fainted Take the person outdoors Use oxygen or artificial respiration if necessary Do not administer adrenaline or similar substances Contact w...

Page 39: ...s informed about the potential risk of the load and knows what to do in case of accident or emergency Before starting transport make sure the load is properly secured and make sure the valve of the co...

Page 40: ...40...

Page 41: ...41 DECLARATION OF CONFORMITY...

Page 42: ...42...

Page 43: ...43...

Page 44: ...Ferroli spa 37047 San Bonifacio Verona Italy Via Ritonda 78 A tel 39 045 6139411 fax 39 045 6100933 www ferroli it COD 3QE29240...

Reviews: