5. TECHNICAL DATA AND CHARACTERISTICS
Key of figures cap. 5
7
Gas inlet
10
System delivery
16
Fan
32
Heating circulating pump (not supplied)
36
Automatic air vent
44
Gas valve
72
Room thermostat (not supplied)
72b
Second room thermostat (not supplied)
81
Ignition electrode
82
Detection electrode
95
Diverter valve (not supplied)
A
= Heating phase
B
= DHW phase
C
= Neutral
NOTE:
For valves with 2 wires and spring return, use the connections B and C
98
Switch
114
Water pressure switch
130
DHW circulating pump (not supplied)
138
External probe (not supplied)
139
Remote timer control (not supplied)
154
Condensate drain pipe
155
Hot water tank temperature probe (not supplied)
186
Return sensor
188
Ignition/Ionisation electrode
191
Fume temperature sensor
220
Ignition card
256
Modulating heating circulating pump signal
275
Heating system drain cock
278
Double sensor ( Heating)
298
Cascade temperature sensor (not supplied)
299
Input 0-10 Vdc
300
Burner lit contact (voltage-free contact)
301
Fault contact (voltage-free contact)
302
Remote reset input (230 Volt)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
321
Low temperature return
346
High temperature return
357
Faulty contact (230 Vac)
361
Cascade connection of next module
362
Cascade connection of previous module
363
MODBUS communication
5.1 Dimensions, connections and main components
fig. 71 - Front view model B 70
fig. 72 - Front view model B 125
A41
Sensor positioning
Delivery sensor disconnected from
the pipe
Check the correct positioning and
operation of the heating sensor
A42
Heating sensor fault
Sensor damaged
Replace the sensor
F50
Cascade temperature
sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F52
Heating sensor fault
Sensor damaged
Replace the sensor
A61
Faulty controller
Controller ABM03
Check the earth connection and
replace the controller if necessary.
A62
No communication between
controller and gas valve
Controller not connected
Connect the controller to the gas valve
Valve damaged
Replace the valve
A63
A64
A65
F66
Faulty controller
Controller ABM03
Check the earth connection and
replace the controller if necessary.
Fault
code
Fault
Possible cause
Cure
188
1760
540
16
114
16
114
188
660
1780