background image

  

2001

10

Flue system
The boiler allows the flue outlet to be taken from the rear of the boiler or from either side.

A standard flue length of 0.75 metres is provided. Alternative lengths of two or three metres can be supplied (equivalent to wall
thicknesses of up to 565, 1815 and 2815 mm for rear flues and deduct 91 mm plus distance from side wall for side outlet flues).

It  is  absolutely  essential,  to  ensure  that  products of combustion discharging from the terminal cannot re-enter the building, or
enter any adjacent building, through ventilators, windows, doors, natural air infiltration, or forced ventilation/air conditioning.

The flue must be installed with a fall of: 35 mm per metre (2

°

) towards the boiler, see fig. 12.

Gas Supply
If  necessary  the  local Gas Region should be consulted, at the installation planning stage, in order to establish the availability of
an adequate supply of gas.

An existing service pipe must not be used without prior consultation with the Local Gas Region.

A gas meter can only be connected by the Local Gas Region, or by a Local Gas Region's Contractor.

Installation pipes should be fitted in accordance with BS6891-1988.

Appliance inlet working pressure must be 20 mbar MINIMUM.

Pipework from the meter to the combination boiler must be of an adequate size, minimum 22 mm.

The boiler requires 2.65 m

3

/h (93.6 ft

3

/h) of natural gas.

Do not use pipes of a smaller size than the combination boiler inlet gas connection.

The complete installation must be tested for gas soundness and purged as described in BS6981-1988. All pipework must be
adequately supported. An isolating gas valve is provided and should be fitted on the manifold assembly.

Water System

Central Heating

It  must  be  a  sealed  system.  Detailed  recommendations are given in BS6798, BS5449, BS6700 and CP342 Part. 2. Pipework
not  forming  part  of  the  useful  heating  surface  should be insulated to prevent any heat losses or possible freezing (i.e. in roof
spaces  or  ventilated  underfloor  spaces).  Drain  taps  should  be  positioned  at  the  lowest  point  of  the system in accessible
locations  to  permit  the  whole system to be drained down. The drain taps should be in accordance with BS2879. Copper tubing
to  BS2871,  Part.  1  is  recommended  for  water  carrying  pipework.  Pipework in horizontal runs should have a gradient where
possible  to  facilitate  the  removal  of  air.  It should be ensured that the boiler heat exchanger is not a natural point for collecting
air. A typical heating system with domestic hot water circuit is illustrated in fig. 6.

Important  -  A  bypass must be fitted to ensure a minimum flow rate through the boiler of 6 l/min. The bypass should be fitted as
far as possible from the boiler if thermostatic radiator valves are fitted throughout.

Make up Water

Provision  must  be  made  for  replacing  water  lost  from  sealed system. Reference should be made to BS6798, for methods of
filling  and  making  up  sealed  systems. There must be no direct connection between the boiler's central heating system and the
mains  water  supply.  The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water
Byelaw. Again any such connection must be disconnected after use.

Domestic Hot Water

Always  fit  a  water  softener  or  descaler  in  «hard  water areas». A 15 mm copper connection point on the boiler jig bracket for
attaching  to  the main supply is provided. The maximum domestic water pressure for the inlet supply is 10 bar (145 P.S.I.). If the
cold  mains supply exceeds 5 bar (72 P.S.I.), a water governor or pressure reducing valve must be fitted by the installer into the mains
supply in an inconspicuous but accessible position preferable between 3 and 5 metres (10-16 ft) before the appliance.
Such a valve must be approved by the Water Research Council.

Attention - Is drawn to the Model Water Byelaws.

Fittings  manufactured  from  duplex  (alpha-beta)  brass  are  not acceptable for underground use and certain water undertakings
will not accept their use above ground.

Summary of Contents for optima 2001 VMF7

Page 1: ...3500 Fax 0121 3523510 ALL SPECIFICATIONS SUBJECT TO CHANGE Phone numbers Installer Service Engineer Serial No Read these Instructions thoroughly before using the appliance FERROLI HELPLINE FOR SERVICE...

Page 2: ...ticHotWaterSystem 21 8 3 Electricity Supply 21 8 4 The Gas Installation 22 8 5 To Light the Boiler 23 Burner pressure C H and D H W 24 Gas pressure adjustment with Honeywell VR 4605 NA 4003 valve 25 8...

Page 3: ...Heating pump The pump is switched ON OFF by the time clock and or a 24 Volt room thermostat The pump circuit also has a 6 minute over run time There is a Domestic Hot Water flow switch fitted and whe...

Page 4: ...Domestic Hot Water Flow 2 5 l min Maximum domestic cold water Inlet pressure 10 0 bar C H Safety valve pressure setting 3 bar C H Expansion vessel capacity 7 litre Min heating circuit pressure 0 8 ba...

Page 5: ...stic Hot Water outlet 4 Domestic Cold Water inlet 5 Central Heating Pressure relief valve 6 Central Heating Flow outlet 7 Central Heating Return inlet FRONT VIEW LEFT SIDE VIEW REAR VIEW TOP VIEW 480...

Page 6: ...2001 6 Boiler Flow Diagram Fig 2...

Page 7: ...regulator Modureg gas valve 48 Burner pressure test point 49 Overheat cut off thermostat 50 Central heating limit thermostat 51 Central heating frost thermostat 53 Heat exchanger venting point 56 Expa...

Page 8: ...ce control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower Terminal Position POSITION MINIMUM SPACING fig 3 mm A Directly below an open...

Page 9: ...the boiler must be available for maintenance min 600 mm Fig 5 Fig 4 APPLIANCE FLUE SYSTEM APPLIANCE LOCATION ROOM SEALED AIR VENT AREAS IN ROOM NIL IN COMPARTMENT OPEN TO ROOM IN COMPARTMENT OPEN TO O...

Page 10: ...vent any heat losses or possible freezing i e in roof spaces or ventilated underfloor spaces Drain taps should be positioned at the lowest point of the system in accessible locations to permit the who...

Page 11: ...Fig 6 Key 1 Filling point C H 2 Temporary connection 3 Cold water supply Gas Cold water Additional expansion vessel C H if required Filling point C H Bypass TEMPORARY FILLING LOOP A temporary filling...

Page 12: ...EXPANSION VESSELS Deduct from the value given in the table the 7 litre vessel supplied Note 1 Fill C H installation to min 1 5 bar 2 Select by preference the expansion vessel for increased system pres...

Page 13: ...g a 10 mm drill drill 70 mm deep holes to accept the wall plugs and insert wall plugs 2 5 Fit the top and bottom brackets using the four fixing screws provided Ensure that all the service cocks are in...

Page 14: ...ide flue outlet Rear flue outlet Diam min 118 mm 2 Gas 22 mm 3 Domestic Hot Water outlet 15 mm 5 Outlet central heating safety valve 15 mm 4 Domestic Cold Water inlet 15 mm 6 Central Heating flow outl...

Page 15: ...t The aluminium flue pipe must protrude into the outside grill by 2 in 50 mm never cut it to the same length as the plastic air pipe Side Flue Outlet Fig 13 Rear flue Outlet Fig 12 Air sealing sleeve...

Page 16: ...tor provided through the jig bracket into the valve using the remaining washer fig 17 5 6 Connect the pressure relief valve discharge pipe 15 mm to the outside of the building where possible over a dr...

Page 17: ...2001 17 Fixing points Lift here Fig 15 Fixing screws Fig 16 Fig 17...

Page 18: ...nal cover see fig 18 7 1 Procedure 7 1 1 The supply cable must be no less than 0 75 mm 24x0 2 mm to BS6500 table 16 7 1 2 The earth conductor must be cut longer than the live and neutral fig 19 Connec...

Page 19: ...or should be installed on the North North West wall or on the one facing the majority of the main living rooms in the building The sensor must never be exposed to the first morning sunlight It must ne...

Page 20: ...em flow temperature 7 4 4 Read from the graph the number setting that the boiler is to be adjusted to If the setting is between two numers this can be set on the boiler say between 2 and 3 7 4 5 Remov...

Page 21: ...system in accordance with BS 7593 8 2 Filling the Domestic Hot Water System Close all hot water draw off points Open main cold water stop cock and ensure the cold water inlet cock is open at the boile...

Page 22: ...ly c Adjust room thermostat and all external controls to ON Check operation of pump d Turn the boiler thermostat to maximum Fan will run A waiting time of max 3 minutes before fan will run is possible...

Page 23: ...tiometer P1 on the PCB fig 24 in the control panel until the required burner pressure is obtained Anticlockwise to reduce the pressure Note 2 Shortcircuit12 13onlyonconnectorX3ontheP C B Boiler starts...

Page 24: ...ut F then check that the pressure is still at the required value 11 Adjust minimum pressure by rotating screw E anticlockwise until the required value is reached 12 Fit coil C by sliding it into the s...

Page 25: ...III Examine all pipework for leakage also check for leaks from the condensate drainage system IV Turn on a D H W tap and check that the C H pump stops running V As the D H W temperature reaches 60 C c...

Page 26: ...THE P C B HAS A BUILT IN OVERHEAT PROTECTION IF THIS IS OPEN ALL LED S WILL BE OFF BUT THE C H PUMP 32 WILL RUN SWITCH OFF THE BOILER FOR AT LEAST 20 MINUTES 12 1 TR1 X4 X6 2 3 4 X2 RY1 X1 2AT 230V 50...

Page 27: ...n 16 not running at full speed or air flow too low air pressure switch 43 faulty B CENTRAL HEATING ON Room stat 72 at Max HW tap closed LED OK FAULT POSSIBLE CAUSE OF FAULT 1 1 0 No main electricity s...

Page 28: ...sed Relay not energised Replacement of Parts 1 0 INITIAL PROCEDURE Before work commences ensure that a The boiler is cold electricity supply is isolated and the gas supply is turned off at the inlet o...

Page 29: ...ontrol panel cover Note The panels are located in keyhole slots push panels upwards and pull away i Removal of Combustion Chamber Outer Cover Remove the five combustion chamber outer cover fixing scre...

Page 30: ...2001 30 Key 16 Fan 28 Flue collector from heat exchanger Fig 32 Details Combustion Chamber...

Page 31: ...the flow switch unions and carefully lower the flow switch taking care not to lose either the three sealing washers filter or flow restrictor c Disconnect the electrical connections to the flowmeter d...

Page 32: ...n of the new gas valve and reset burner pressures as prescribed see commissioning 4 0 P C B a Refer to section 1 items a c d f and j b Unscrew two fixing screws on the P C B top cover plate lift and d...

Page 33: ...tral heating c d f g h right hand side panel j and k b Loosen the two pump union connections c Remove electrical cover on pump one screw fig 40 Rotate pump to remove cover d Disconnect the live neutra...

Page 34: ...ock is fitted to the boiler to control the central heating this will come into operation when the selector switch is turned to the position marked heating timed and hot water AUTO R OVER RIDE 12 31 x...

Page 35: ...rding to the programme set 1 Slide switch A to right position P Display 2 Press button P Display 3 Press button P Display 4 Press button P Display 5 Press button P Display 6 Press button P Display 7 T...

Page 36: ...der 14 0 AIR PRESSURE SWITCH a Refer to Section 1 items a c d f and i b Remove the two screws securing the air collection plate fig 45 and withdraw the plate complete with the air pressure switch Take...

Page 37: ...d c Drain C H side of boiler II Remove the two screws from the expansion vessel securing plate fig 47 which can be found at the top back of the boiler III Undo the compression fitting on the top of th...

Page 38: ...ack panel 77 Combustion chamber insulation side panel 78 Flue collector 81 Fan 87 Panel isolation 88 Combustion chamber panel 89 Glass window 94 Burner box 95 Burner Venturi 96 Injector 104 pressure t...

Page 39: ...st thermostat 132 Central heating limit thermostat 133 Overheat cut off thermostat 140 Automatic air vent 141 Safety valve 143 Central heating pump 147 D H W limit thermostat Fig 50 148 Flue deflector...

Page 40: ...1 Air pressure switch 44 802640 1 Combination gas valve 49 800170 1 Overheat cut off thermostat 50 386577 800160 1 Heat exchanger limit thermostat 51 386828 800180 1 Heat exchanger frost thermostat 61...

Page 41: ...1 2 Shaft 3 Adjustment screw for max pressure setting 4 Adjustment screw for min pressure setting 5 6 3 mm AMP terminals 6 O ring 71 Modulating balance tube If necessary replace complete MODUREG Fig 2...

Page 42: ...wo pipe air intake flue outlet Special Air Intake Flue Outlet The standard Flue air intake hood on top of the boiler can be replaced by a special two pipe flue adapter For details see separate instruc...

Page 43: ...2001 43...

Page 44: ...st Midlands B76 8DH Tel 0121 3523500 Fax 0121 3523510 ALL SPECIFICATIONS SUBJECT TO CHANGE Phone numbers Installer Service Engineer BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY S...

Reviews: