7
TECHNICAL DATA AN PERFORMANCE
System technical data
NOTA:
Declared according to
European regulation 811/2013
. The values are referred to units without options and accessories.
Effi ciency class in heating mode
- Average climate
Model
4
6
8
10
12
14
16
12T
14T
16T
Ef
fi
ciency capacity - medium temperature (water 55°C)
A++
A++
A++
A++
A++
A++
A++
A++
A++
A++
Season ef
fi
ciency - medium temperature (water 55°C)
127
130
125
127
127
128
128
128
130
130
Ef
fi
ciency capacity - low temperature (water 35°C)
A++
A++
A++
A++
A++
A++
A++
A++
A++
A++
Season ef
fi
ciency - low temperature (water 35°C)
183
185
170
177
175
168
158
184
179
172
OUTDOOR UNIT TECHNICAL DATA
4
6
8
10
12
14
16
12T
14T
16T
Refrigerant
R410A
Tipo
Refrigerant charge
2.5
2.5
2.8
3.9
3.9
3.9
3.9
4.2
4.2
4.2
kg
Power supply
220-240V ~ 50 Hz
380-415V - 3N ~ 50 Hz
-
Compressor type
Twin rotary
-
N° compressors / N° refrigerant circuits
1 / 1
n°
Source side heat exchanger type
Finned coil
-
Fans type
Brushless DC
-
N° fans
1
2
n°
Liquid connections diameter
Ø
9.52
-
Gas connections diameter
Ø
15.88
-
SWL - Sound power level**
62
66
69
67
69
71
72
70
72
72
dB(A)
INDOOR UNIT TECHNICAL DATA
8
16
16T
Power supply
220-240V ~ 50 Hz
220-240V ~ 50 Hz
380-415V - 3N ~ 50 Hz
-
Plant side heat exchanger type
Brazed stainless steel plate
-
Pump type
Electronic circulator
-
Expansion tank volume
10
l
Water safety valve set
3
bar
Hydraulic fi ttings - plant
1”M
-
Hydraulic fi ttings - domestic hot water
3/4”M
-
Liquid connections diameter
Ø
9.52
-
Gas connections diameter
Ø
15.88
-
Integrative electrical heaters (2-stages) *
3 (1.5 + 1.5)
6 (4 + 2)
kW
SWL - Sound power level**
43
45
dB(A)
* =
Optional for mod. 8 e 16, as standard mod. 16T. The firt digit indicate the total power, between brackets the power for stage 1 and stage 2
** SWL = Sound power levels, with reference to 1x10
-12
W.
The Total sound power level in dB(A) measured in compliance with ISO 9614 standards. The Total Sound Power in db(A) the only binding acoustic specification.
The values are referred to units without options and accessories.
Data declared according to
EN 14511
:
EER
(Energy Efficiency Ratio) = ratio of the total cooling capacity to the effective power input of the unit
COP
(Coefficient Of Performance) = ratio of the total heating capacity to the effective power input of the unit
A35W7
= source : air in 35°C d.b. / plant : water in 12°C out 7°C
A35W18
= source : air in 35°C d.b. / plant : water in 23°C out 18°C
A7W45
= source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C
A7W35
= source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C
Performances data
-
Models
4
6
8
10
12
14
16
12T
14T
16T
UM
A7W35
Heating capacity
4.10 6.10 8.00 10.00
12.10
14.00
15.50
12.00
14.00
15.50
kW
Power input
0.82
1.29
1.73
2.17
2.74
3.39
3.82
2.66
3.26
3.79
kW
COP
5.00 4.73 4.62 4.61 4.42 4.13
4.06 4.51
4.29
4.09
W/W
Water fl ow rate
705
1049
1376
1720
2081
2408
2666
2064
2408
2666
l/h
Avaialble static pressure
79
68
53
42
21
0
0
22
0
0
kPa
A7W45
Heating capacity
4.01 5.96 7.34 10.12 11.85 14.05
16.05 11.97
13.93
15.48
kW
Power input
1.13
1.68
2.13
2.93
3.48
4.41
5.03
3.5
4.21
4.87
kW
COP
3.55 3.55 3.45 3.45 3.41 3.19
3.19 3.42
3.31
3.18
W/W
Water fl ow rate
690
1025
1262
1741
2038
2417
2761
2059
2396
2663
l/h
Avaialble static pressure
79
69
58
41
24
0
0
23
1
0
kPa
A35W1
8
Cooling capacity
4.10 6.20 8.00 10.50 11.70 13.10
13.80
12.00
13.50
14.50
kW
Power input
0.84
1.43
1.93
2.30
2.79
3.48
3.77
2.8
3.45
3.94
kW
EER
4.88 4.34 4.15 4.57 4.19 3.76
3.66 4.29
3.91
3.68
W/W
Water fl ow rate
705
1066
1376
1806
2012
2253
2374
2064
2322
2494
l/h
Avaialble static pressure
79
67
53
37
26
11
3
22
6
0
kPa
A35W7
Cooling capacity
4.12 6.15 6.44 9.39 11.02
12.49
12.85 11.7
12.53
12.91
kW
Power
input
1.30 2.08 2.24 3.26 4.17 5.07
5.39 4.65
5.21
5.52
kW
EER
3.17 2.96 2.88 2.88 2.64 2.46
2.38 2.52
2.40
2.34
W/W
Water fl ow rate
709
1058
1108
1615
1895
2148
2210
2012
2155
2221
l/h
Avaialble static pressure
79
67
65
47
32
17
13
26
17
13
kPa
Summary of Contents for OMNIA H 04E
Page 26: ...26 FOR SEVICEMAN menu SETUP OF THE SYSTEM...
Page 27: ...27 SETUP OF THE SYSTEM...
Page 28: ...28 SETUP OF THE SYSTEM...
Page 29: ...29 SETUP OF THE SYSTEM...
Page 46: ...46 The overview pages available user CONTROL SYSTEM...
Page 47: ...47 CONTROL SYSTEM...