15
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - Radiant plants
Data declared according to
EN 14511
. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
IH
Heating W10W35
( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity
28,8
33,0
39,0
43,6
49,1
57,6
kW
Power input
5,20
6,02
7,11
8,02
8,99
10,7
kW
COP
5,54
5,48
5,49
5,44
5,46
5,38
-
Water flow rate plant side
4970
5698
6719
7516
8468
9906
l/h
Pressure drops plant side
20
26
24
30
29
39
kPa
Water flow rate source side
6813
7825
9211
10326
11641
13657
l/h
Pressure drops source side
37
48
45
56
54
73
kPa
Heating B0W35
( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity
22,1
25,4
30,0
33,6
37,8
44,2
kW
Power input
5,09
5,84
6,92
7,74
8,68
10,2
kW
COP
4,34
4,35
4,34
4,34
4,35
4,33
-
Water flow rate plant side
3827
4381
5178
5801
6529
7620
l/h
Pressure drops plant side
12
16
15
19
18
24
kPa
Water flow rate source side
5469
6274
7400
8323
9369
10970
l/h
Pressure drops source side
26
34
31
39
37
50
kPa
IP
Heating W10W35
( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity
28,2
32,4
38,2
42,7
48,1
56,4
kW
Power input
5,13
5,93
7,01
7,90
8,86
10,5
kW
COP
5,50
5,46
5,45
5,41
5,43
5,37
-
Water flow rate plant side
4866
5594
6598
7360
8295
9715
l/h
Pressure drops plant side
20
26
24
29
28
38
kPa
Water flow rate source side
6655
7670
9031
10089
11378
13368
l/h
Pressure drops source side
36
47
43
53
51
70
kPa
Heating B0W35
( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity
21,6
24,9
29,4
32,9
37,0
43,4
kW
Power input
5,02
5,76
6,84
7,64
8,57
10,1
kW
COP
4,30
4,32
4,30
4,31
4,32
4,30
-
Water flow rate plant side
3741
4295
5074
5680
6390
7481
l/h
Pressure drops plant side
12
16
14
18
17
23
kPa
Water flow rate source side
5326
6134
7231
8122
9140
10744
l/h
Pressure drops source side
25
32
30
37
36
48
kPa
Cooling W30W18
( source : water in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity
30,5
34,9
41,2
46,0
51,8
60,6
kW
Power input
5,18
5,97
7,07
7,95
8,90
10,6
kW
EER
5,89
5,85
5,83
5,79
5,82
5,72
-
Water flow rate plant side
5276
6052
7138
7983
8983
10518
l/h
Pressure drops plant side
23
30
28
34
33
44
kPa
Water flow rate source side
6146
7040
8314
9284
10444
12204
l/h
Pressure drops source side
30
39
37
45
43
58
kPa
Cooling B30W18
( source : brine in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity
30,1
34,5
40,8
45,6
51,3
60,1
kW
Power input
5,22
6,04
7,15
8,06
9,02
10,7
kW
EER
5,77
5,71
5,71
5,66
5,69
5,62
-
Water flow rate plant side
5207
5983
7069
7897
8897
10431
l/h
Pressure drops plant side
22
29
27
33
32
43
kPa
Water flow rate source side
6598
7569
8953
9987
11247
13157
l/h
Pressure drops source side
36
47
44
54
52
70
kPa
Frame
1
Model
30 .1
35 .1
40 .1
45 .1
50 .1
55 .1
U.M.
Power supply
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
V-ph-Hz