3. Service and maintenance

All adjustment, commissioning and periodical control operations described below must only be carried out by Qualified Per-
sonnel (meeting the professional technical requirements prescribed by current regulations).

FERROLI

 declines any liability for damage and/or injury caused by unqualified and unauthorised persons tampering with

the unit.

3.1 Adjustments

Secondary air adjustment

The secondary air control device must be set during the commissioning stage.

Adjust the air inlet door adjustment screw so that in any case there remains an air passage of not more than 1 - 2 mm.
With the boiler cold, set the thermostat to 60°. Hook the chain to the special air inlet door eyelet, adjusting its length so
that the air passage "L" (fig. 2) is approx. 15 mm for "coke III" and 2 mm for "wood".

3.2 Startup

B

Checks to be made at first lighting, and after all maintenance operations that involved disconnecting from the
systems or operations on safety devices or parts of the boiler.

Before lighting the boiler

Open any on-off valves between the boiler and the systems.

Check correct prefilling of the expansion tank

Fill the water system and make sure that all air contained in the boiler and the system has been vented.

Make sure there are no water leaks in the system, connections or boiler.

Check correct connection of the electrical system and efficiency of the earthing system

Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler

Checks during operation

Turn the unit on as described in sec. 1.3.

Check the seal of the water systems.

Check the efficiency of the flue and air-fume ducts while the boiler is working.

Check that the water is circulating properly between the boiler and the systems.

Check the seal of the wood loading and combustion chamber doors.

Check combustion and correct setting of the secondary air control device.

3.3 Maintenance

Instructions

B

 - Before carrying out any maintenance operation, disconnect the power to the boiler and wait until it is at room
temperature.

 - Never drain (even partially) the water from the system unless absolutely necessary.

 - Do not clean the boiler and/or its parts with easily flammable substances (e.g. petrol, alcohol, etc.).

 - Do not leave containers of flammable substances in the room where the boiler is installed.

 - Do not clean the heating system when the boiler is operating.

 - Use tube brushes and aspirators for cleaning; if rags are used, make sure they are not left inside the boiler.

- If the ash is still hot, wear protective gloves.

- Put the ashes in a non-flammable container provided with lid.

Regularly or the end of every period of operation, carefully clean the boiler, and also the flue if necessary. To clean the
boiler, open both cast-iron doors, remove the coal grate then, with a flexible metal tube brush, carefully clean the com-
bustion chamber and the various flueways. Then remove any soot deposited in the ashpan. Also make sure the fume
exhaust pipes and flue are clean and perfectly tight.

Summary of Contents for GFN K

Page 1: ...CTIONS FOR USE INSTALLATION AND MAINTENANCE INSTRUCTIONS D UTILISATION D INSTALLATION ET D ENTRETIEN UPUTE ZA UPORABU POSTAVLJANJE I ODR AVANJE INSTRUC IUNI DE UTILIZARE INSTALARE I NTRETINERE NAVODIL...

Page 2: ...instructions Incorrect installation or poor maintenance can cause damage or physical injury The manufacturer de clines any responsibility for damage caused by er rors in installation and use or by fai...

Page 3: ...of installation 35 2 3 Plumbing connections 36 2 4 Conversion for use with an oil or pellet burner 36 2 5 Electrical connections 36 2 6 Connection to the flue 37 3 Service and maintenance 38 3 1 Adjus...

Page 4: ...high heat efficiency performance and consider able energy saving The combustion chamber is specially designed to take large pieces of wood loading is by means of the large top door The combustion cham...

Page 5: ...auses a loss of efficiency Use wood logs dried outdoors and in the natural state stored for 2 years with max humidity of 20 Boiler lighting Open the bottom door and remove any ash present in the combu...

Page 6: ...nt knob to 60 C turning it to 80 C and adjusting the heating water temperature by means of the mixer valve would be optimum Load the combustion chamber with combustible material paper and wood and aft...

Page 7: ...s or materials corrosive gases volatile substances or dusts that can be sucked by the fan The room must be dry and not exposed to rain snow or frost A A space must be provided around the unit for remo...

Page 8: ...cs of the water system In the presence of water harder than 25 Fr 1 F 10ppm CaCO3 use suitably treated water in order to avoid possible scaling in the boiler Treatment must not reduce the hardness to...

Page 9: ...m opening of at least 3 mm interposing fuses of max 3A between the boiler and the line It is important to respect the polarities LINE brown wire NEUTRAL blue wire EARTH yellow green wire in making con...

Page 10: ...thing system Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler Checks during operation Turn the unit on as described in sec 1 3 Check the seal of the water...

Page 11: ...ce the seal if necessary The control and safety devices must work properly The fume exhaust circuit must be perfectly efficient The fume ducts must be free of obstructions and leaks The water pressure...

Page 12: ...esium anode 130 Hot water tank circulating pump 178 Hot water tank thermometer bulb 180 Hot water tank 192 Recirculation 209 Hot water tank delivery 210 Hot water tank return 233 Hot water tank drain...

Page 13: ...filling cock 97 Magnesium anode 130 Hot water tank circulating pump 178 Hot water tank thermometer bulb 180 Hot water tank 192 Recirculation 209 Hot water tank delivery 210 Hot water tank return 233...

Page 14: ...bar 3 PMS Max heating temperature C 95 tmax Heating water content litres 28 Heating expansion tank capacity litres 10 Heating expansion tank prefilling pressure bar 1 Max working pressure in hot water...

Page 15: ...ied 72 Room thermostat not supplied 98 Switch 130 Hot water tank circulating pump 143 Hot water tank control thermostat 185 Summer Winter switch 239 Electrical heating element L N L N 72 32 130 L N 4...

Page 16: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it...

Reviews: