EGEA
90LT - 120LT
97
cod. 3541T580 - Rev. 00 - 12/2019
EN
Parameters Description
Range
Default
Note
P23
Photovoltaic mode integration
0 = permanently deactivated
1 = activated
0
Modifiable
P24
Off-peak working mode
0 = permanently deactivated
1 = activated with ECO
2 = activated with AUTO
0
Modifiable
P25
Offset value on upper water temp probe
-25÷25°C
0°C
Modifiable
P26
Offset value on lower water temp probe
-25÷25°C
0°C
Modifiable
P27
Offset value on air-inlet temp probe
-25÷25°C
0°C
Modifiable
P28
Offset value on defrosting temp probe
-25÷25°C
0°C
Modifiable
P29
Antilegionella starting hour
0÷23 hours
23 hours
Modifiable
P30
Hysteresis on upper water probe for electrical
heater working
2÷20°C
7°C
Modifiable
P31
Heat-pump working period in AUTO mode for
heating rate calculation
10÷80 min
30 min
Modifiable
P32
Temperature threshold for electrical heater us-
age in AUTO mode
0÷20°C
4°C
Modifiable
P33
Electronic-expansion valve (EEV) control
0 = permanently deactivated
1 = activated
1
Modifiable
P34
Superheating calculation period for EEV auto-
matic control mode
20÷90s
30 s
Modifiable
P35
Superheating setpoint for EEV automatic con-
trol mode
-8÷15°C
5°C
Modifiable
P36
Desuperheating setpoint for EEV automatic
control mode
60÷110°C
88°C
Modifiable
P37
EEV step opening during defrosting mode (x10) 5÷50
15
Modifiable
P38
Minimum EEV step opening with automatic
control mode (x10)
3~45
9
Modifiable
P39
EEV control mode
0= automatic
1 = manual
0
Modifiable
P40
Initial EEV step opening with automatic control
mode / EEV step opening with manual control
mode (x10)
5÷50
25
Modifiable
P41
AKP1 temperature threshold for EEV KP1 gain -10÷10°C
-1°C
Modifiable
P42
AKP2 temperature threshold for EEV KP2 gain -10÷10°C
0°C
Modifiable
P43
AKP3 temperature threshold for EEV KP3 gain -10÷10°C
0°C
Modifiable
P44
EEV KP1 gain
-10÷10
5
Modifiable
P45
EEV KP2 gain
-10÷10
2
Modifiable
P46
EEV KP3 gain
-10÷10
1
Modifiable
P47
Maximum allowed inlet temperature for heat-
pump working
30÷50°C
43°C
Modifiable
P48
Minimum allowed inlet temperature for heat-
pump working
-10÷10°C
-5°C
Modifiable
P49
Threshold on inlet temperature for evaporator
EC or AC with double speed blower speed set-
ting
10÷40°C
25°C
Modifiable
P50
Antifreeze lower water temperature setpoint 0÷15°C
12°C
Modifiable
P51
Evaporator EC blower higher speed setpoint 60÷100%
90%
Modifiable
P52
Evaporator EC blower lower speed setpoint
10÷60%
60%
Modifiable
(1) = NOT USABLE FOR THIS EQUIPMENT