ECONCEPT SOLAR ST
47
EN
cod. -- - 11/2010 (Rev. 00)
4.8 FZ4B low temperature zone card
Service Menu
Press the Ok button for 5 seconds to access the zone controller Service Menu.
Press the buttons
and
to select:
"tS"
= Transparent Parameters Menu
"In"
= Information Menu
"Hi"
= History Menu (of the zone controller)
"rE"
= History Menu Reset (of the zone controller).
After selecting the Menu, press the Ok button to access it.
“tS” - Transparent Parameters Menu
The zone controller is provided with 35 transparent parameters also modifiable from Remote Control (Service Menu):
Press the "+" and "-" buttons to scroll the list of parameters in increasing or decreasing order respectively. To modify
the value of a parameter, press the Ok button after selecting it: press the + and - buttons to modify it, and the setting
will be automatically saved. Press the Ok button to return to the list of parameters. Press the Ok button for 3 seconds
to return to the Service Menu. Press the Ok button for 5 seconds to exit the Service Menu.
Remote
Control
Zone Card
FZ4B
Boiler Card
(if prearranged)
Description
transparent parameters
Range
Default
(for mixed
zone)
Recom-
mended for
Direct Zone
01
P01
Zone1 Min. Temperature
10-90°C
10°C
10°C
02
P02
Zone1 Max. Temperature
10-90°C
40°C
70÷80°C
03
P03
Zone1 calculated set point offset
0-40°C
10°C
0°C
04
P04
Do not modify
10-90°C
90°C
05
P05
o01
Zone1 External Probe Curve
0-10
0
06
P06
o02
Zone1 External Probe Offset
20-40°C
30°C
07
P07
Zone2 Min. Temperature
10-90°C
10°C
08
P08
Zone2 Max. Temperature
10-90°C
80°C
09
P09
Zone2 calculated set point offset
0-40°C
0°C
10
P10
DO NOT MODIFY
10-90°C
90°C
11
P11
o03
Zone2 External Probe Curve
0-10
0
12
P12
o04
Zone2 External Probe Offset
20-40°C
30°C
13
P13
Zone3 Min. Temperature
10-90°C
10°C
14
P14
Zone3 Max. Temperature
10-90°C
80°C
15
P15
Zone3 calculated set point offset
0-40°C
0°C
16
P16
DO NOT MODIFY
10-90°C
90°C
17
P17
o05
Zone3 External Probe Curve
0-10
0
18
P18
o06
Zone3 External Probe Offset
20-40°C
30°C
19
P19
Mixing valve on+off time
0-15sec
15sec
20
P20
Mixing valve boost
0-120sec
0sec
21
P21
Mixing valve on time for °C
0-15sec/°C
1sec/°C
22
P22
DO NOT MODIFY
0-20°C
4°C
23
P23
DO NOT MODIFY
70-85°C
80°C
24
P24
DO NOT MODIFY
0-60°C
0°C
25
P25
DO NOT MODIFY
0-1
0
26
P26
DO NOT MODIFY
10-65°
55°C
27
P27
Post-circulation time
0-20 min
10 min
28
P28
DO NOT MODIFY
0-1
0
29
P29
Delay for Zone
0-255 sec.
30 sec.
30
P30
DO NOT MODIFY
0-1
0
31
P31
DO NOT MODIFY
0-3 min
3 min
32
P32
DO NOT MODIFY
0-10°C
5°C
33
P33
DO NOT MODIFY
0-10 min
2 min
34
P34
DO NOT MODIFY
0-1
0
35
P35
DO NOT MODIFY
0-1
0