DOMINA N 80 DGT
35
7.12 Spark or fl ame detect electrode
(fi g. 41)
• Isolate gas and electricity supply
• Remove outer case (two screws bottom rear
corners)
• Open room sealed compartment and
combustion chamber
• Identify electrode from fi g. 41
• Unplug electrical connection "A" from sensing
electrode
• Remove fi xing screw and remove fl ame detect
electrode
• Remove the two fi xing screw from spark
electrode plate and remove it.
Spark
A
Flame
detect
Fig. 41
7.13 D.H.W. fl owmeter
• Isolate electricity and water supplies
• Open a hot water tap to release water
pressure from the domestic side of
the heat exchanger, close tap.
• Remove outer case (two screws bottom rear
corners).
• Remove two screws from control panel and tilt
forward
• Take off protective cover from main PCB and
unplug fl ow meter lead from terminal X6
• Place a piece of cloth or some other
absorbent material over rear of control
panel to catch any drops of water that may be
released when removing the fl ow meter
• Using a 24mm open ended spanner, undo fl ow
meter unions "A" and "B" taking care not to
twist the copper tubing (access through base
panel).
• Remove fl ow meter, check + clean fi lter +
rest fi t to new fl ow meter.
• Reassemble in reverse order.
A
B
Fig. 42a
37
39
38
38
Key
37
Cold water inlet fi lter
38
Gasket
39
Cold water fl ow limiter
Take care on correct position of
components as reported in fi g. 42b
Fig. 42b