background image

25

DOMIcompact F 24 D

fig. 13

Adjusting burner pressure

Since this unit has flame modulation, there are two fixed pressure settings: the minimum and maximum, 
which must be as stated in the technical data chart according to the type of gas.

• Connect a suitable pressure gauge to pressure point “

B

” downstream from the gas valve.,having loo-

sened it first

•  Disconnect the pressure compensation tube “

H

”.

•  Take off the protective cap “

D

”.

•  Run the boiler in TEST mode (press the multi-function button 3 times in 3 seconds):
  - TEST mode on: turn the heating knob (ref. 1 - fig 1) onto maximum.
•  Adjust the maximum pressure with the screw “

G

”, clockwise to increase it and anticlockwise to decrease 

it.

•  Disconnect one of the two electrical connectors from the modureg “

C

” on the gas valve.

•  Adjust the minimum pressure with the screw “

E

”, clockwise to decrease it and anticlockwise to increase it.

•  Reconnect the electrical connector disconnected from the modureg on the gas valve.
•  Check that the maximum pressure has not changed.
•  Reconnect the pressure compensation tube “

H

”.

•  Put the protective cap “

D

” back on.

•  To end TEST mode, repeat the sequence for turning it on or wait 15 minutes
•  Shut down the boiler
•  Remove the pressure gauge
•  Re-seal test point ‘B’
•  Re-light the boiler and check for gas leaks using a suitable “Leak detection fluid”

Key

 

B

 Pressure 

point

 

C

 

Modureg electrical connection

 

D

 Protective 

cap

 

E

 

Minimum pressure adjustment 

 

G

 

Maximum pressure adjustment 

Having disturbed test point ‘B’ when 
checking or adjusting the gas pressures, it 
is considered mandatory to check for gas 
leaks using a suitable leak detection fluid 
or sniffer.at that connection

Summary of Contents for DOMIcompact F 24 D

Page 1: ...wall mounted gas fired for hot water and heating DOMIcompact F 24 D INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FOR THE UNITED KINGDOM EIRE cod 3540B61 1 04 2006 ...

Page 2: ...ed out isolate the appliance from the mains electricity supply In the event of malfunction or faulty operation iso late the appliance Do not attempt to repair or carry out any other operation on the appliance directly Contact Ferroli or a qualified engineer only Repairs or the replacement of components must be carried out exclusively by qualified personnel using originalsparepartsonly Failuretoadh...

Page 3: ...2 2 5 Electrical Connections 14 2 4 Connection to the gas system 14 2 6 Flue system 16 3 Service and maintenance 24 3 1 Adjustments 24 3 2 Initial start up 26 3 3 Maintenance 27 3 4 Troubleshooting 29 4 Technical characteristics and data 30 4 1 Dimensions and connections 30 4 2 General view and main components 31 4 3 Hydraulic diagram 32 4 4 Technical data table 33 4 5 Diagrams 34 4 6 Time Clock o...

Page 4: ... safety thermostat and a low pressure switch Thanks to the microprocessor control and adjustment system with advanced self diagnosis unit ope ration is for the most part automatic The power for heating is automatically governed by the control system combined with the room thermostat not supplied The power for hot water is automatically and continually governed to ensure a fast delivery and comfort...

Page 5: ...erature 6 Flame symbol Appears when the burner is on 7 ECO symbol ECO is displayed when the Economy function is on 8 Hot water demand symbol Appears during hot water operation or when adjusting the hot water set point temperature Fig 1 Boiler on stand by Boiler on stand by ECO Heating operation burner on Hot tap water operation burner on Fault codes See chap 1 6 or 3 0 TEST mode operation burner o...

Page 6: ...and room thermostat call for heating Turning off Turn the knobs ref 1 and 2 Fig 1 onto minimum If the boiler is turned off this way then the P C B is still powe red Hot water and heating operation are disabled the display shows but the frost protection function remains active The frost protection will not work if the electricity and or gas supply to the unit are cut off To avoid damage caused by f...

Page 7: ...lay will stay on for another 5 seconds to then go back to the actual operating temperature providing there is a demand If the boiler is connected to the optional remote open therm control the above adjustments system and hot water temperature can only be made with the remote control ECO COMFORT selection The unit is equipped with a special internal device that ensures a high hot water delivery spe...

Page 8: ... that are automatically reset as soon as the value causing the fault comes back within the boiler s normal working range Listed below are some anomalies that can be caused by simple user solvable problems If the problem remains after two attempts at resetting contact the Ferroli Service Centre For other faults refer to section 3 4 Troubleshooting Before calling a Ferroli service engineer check tha...

Page 9: ...uld be made to the current ETCI rules for electrical installation Incorrect installation can cause damage or physical injury for which the manufacturer declines any responsibility This appliance must be installed strictly in accordance with these instructions and regulations The Gas Safety Regulations Installations Use The Local Building Regulations The Building Regulations Part L The Buildings St...

Page 10: ...st ensure a stable and effective support for the appliance using the bracket and fixings supplied If the unit is enclosed in a cupboard or mounted alongside there must be space for normal maintenance work Fig 2 and tab 1 give the minimum clearances to leave around the unit This appliance does not require compartment ventilation for combustion purposes Drilling Template Select suitable mounting pos...

Page 11: ...h connection must be disconnected after use The temporary filling loop Not supplied is shown in fig 5 Ensure the filling point is on the return pipe to the boiler Attention is drawn to the Local Water Byelaws Fittings manufactured from duplex alpha beta brass are not acceptable for underground use and certain water undertakings will not accept their use above ground Ensure all pipework is adequate...

Page 12: ...ding to current regulations For efficient operation and long life of the boiler the plumbing system must be well designed and always complete with all those accessories that guarantee regular operation and running ie room thermostat trv s and automatic bypass etc If the flow and return pipes follow a path where air pockets could form in certain places it is esential to install air vent valves at t...

Page 13: ...nce with the manufacturers instruc tions For further information contact Fernox Manufacturing Co LTD Cookson Electronics Forsyth Road Sheerwater Woking Surrey GU21 5RZ Tel 0870 8700362 Sentinel Division Betz Dearborn LTD Widnes Cheshire WA8 8ND Tel 0151 424 5351 Note When the boiler is installed with an existing or new system any unsuitable additives or system debris must be removed by thorough ch...

Page 14: ...olt 50 Hz electrical supply The unit s electrical safety is only guaranteed when correctly connected to an efficient earthing system installed according to current safety standards and checked by a professionally qualified person The manufacturer is not responsible for any damage caused by failure to earth the system Also make sure that the electrical system is adequate for the maximum power absor...

Page 15: ...inal block To access the terminal block where the room thermostat Low voltage or the remote timer control is to be connected carry out the following operations 1 Unscrew the two screws A Fig 8a 2 Lower the instrument panel Fig 8b 3 Turn the instrument panel Fig 8c You can now access the terminal block B Fig 8c Low voltage time clock or ...

Page 16: ...y FERROLI S p A in accordance with UNI CIG 7129 92 Failure to use them automatically forfeits all warranty and liability of FERROLI S p A Restrictors Boiler operation requires fitting the restrictors supplied with the unit as instructed in the following tables The restrictor Ø43 is fitted as standard on all boilers Before inserting the flue outlet pipe it is therefore necessary to check there is t...

Page 17: ... 80 30 50 30 95 80 80 3 mm m 108 70 S 50 125 P 70 D S 50 125 L 95 108 30 194 266 194 266 266 194 30 43 95 Rear Outlet Side view View from above Fig 9a Side Outlet Fig 9b Front view View from above P S 93 mm L S D 251 mm with rh outlet S D 179 mm with lh outlet Bend 60 100 010007X0 Bend 60 100 010007X0 Cut the internal pipe 70 mm longer than P Cut the internal pipe 70 mm longer than L between 10 an...

Page 18: ...e must protrude from the wall by between 10 and 60 mm Fig 9a and 9b Eliminate the cutting burrs 5 Connect the ducts to the boiler positioning the gaskets correctly and seal the wall cou pling points with special sleeves Fig 9c The total length in linear metres of the coaxial duct must not exceed the maximum lengths stated in the following table considering that each bend gives rise to the stated r...

Page 19: ...valent in linear metres since it is compared to the loss of one metre of duct in air suction defined as equal to 1 For example abendat90 ofØ80infumeextraction has an equivalent loss of 2 5 linear metres i e it has a loss equal to that of 2 5 linear metres of duct in air suction 2 After completely defining the layout of the system of split flues add up the losses in equi valent metres depending on ...

Page 20: ...A c c e s s o r i e s Ø 8 0 A c c e s s o r i e s Ø 8 0 Cup reduction Ø 80 100 mm Condensate collection cup coupling T coupling M F 80 mm with inspection cap trap to drain condensate Bend 90 Ø 80 mm male female Bend 90 Ø 80 mm female female Bend 45 Ø 80 mm Pipe Ø 80 male female Fume exhaust flue air suction for split connection Ø 80 mm Coupling for flue fume exhaust Ø 80 mm Fume exhaust flue air s...

Page 21: ...9 72 mm to 80 mm AISI 316L End sleeve flexible pipe Ø 72 79 mm to 80 mm AISI 316L Roll of flexible pipe 30 m smooth inside int Ø 72 mm ext Ø 79 mm AISI 316L Description Equivalent losses in metres linear Air 261 rtf 262 rtf 263 rtf 264 rtf Flue Cup reduction Ø 100 80 mm Cup reduction Ø 100 80 mm Windproof end pieces products of combustion Ø 100Ø 100 Bend 90 Ø 100 mm male female Bend 45 Ø 100 mm ma...

Page 22: ...l From a terminal facing the terminal From the wall on which the terminal is mounted From a vertical structure on the roof Above intersection with roof Horizontally from a terminal on the same wall Vertically from a terminal on the same wall From an opening in the car port e g door window into the dwelling Above ground roof or balcony level 300mm 300mm 300mm 200mm 75mm 200mm 150mm 100mm 300mm 600m...

Page 23: ...e sized according to the method of calculation stated in the standard Be airtight to the products of combustion resistant to the fumes and heat and waterproof for the con densate Have a circular or quadrangular cross section some hydraulically equivalent sections are permissible with a vertical progression and with no constrictions Have the ducts conveying the hot fumes adequately distanced or iso...

Page 24: ...setting the values given in the technical data chart for the type of gas used 3 How to Adjust the parameter for the specific type of gas to be used turn the boiler onto standby press the RESET button for 10 seconds P1 will appear on the display press the RESET button for 5 seconds turn the hot water knob ref 2 fig 1 onto 0 for Natural Gas operation or onto 1 for LPG operation press the RESET butto...

Page 25: ...connectors from the modureg C on the gas valve Adjust the minimum pressure with the screw E clockwise to decrease it and anticlockwise to increase it Reconnect the electrical connector disconnected from the modureg on the gas valve Check that the maximum pressure has not changed Reconnect the pressure compensation tube H Put the protective cap D back on To end TEST mode repeat the sequence for tur...

Page 26: ...and using a suitable leak detection fluid to detect any leaks in connections after completing a tightness test Fill the water system and make sure that all air contained in the boiler and the system has been vented by opening the air vent valve on the boiler and any vent valves on the system Make sure there are no water leaks in the system hot water circuits connections or boiler Make sure the ele...

Page 27: ...sabled the display shows but the frost protection mode remains active The frost protection system will not work if the electricity and or gas supply to the boiler are cut off To avoid damage caused by freezing during long shutdowns in winter it is advisable to drain all water from the boiler both tap and the system water or drain off just the tap water and add a suitable antifreeze to the heating ...

Page 28: ...operations check and carry out all the phases of ignition and thermostat operation the gas valve and circulation pump After these checks make sure there are no gas leaks Combustion analyser testing Itispossibletoanalysethecombustionthroughthe air and flue sampling points shown in fig 15 To make the measurement it is necessary to 1 Insert the probes as far as the stop 2 Open a hot water tap 3 Adjus...

Page 29: ...fan Air pressure switch contact open Incorrect wiring to the air pressure switch Wrong diaphragm Flue not correctly sized or obstructed Fault No burner ignition Possible cause Low system pressure System empty Water pressure switch not connected or damaged Cure Flame present with burner off signal Electrode fault Card trouble Delivery sensor fault Sensor damaged Wiring shorted Wiring broken Tap wat...

Page 30: ...74 120 120 146 108 158 681 680 4 TECHNICAL CHARACTERISTICS AND DATA 4 1 Dimensions and connections Fig 16 Top view Bottom view Key 1 Heating system delivery Ø 3 4 2 Hot water outlet Ø 1 2 3 Gas inlet 1 2 4 Tap water inlet Ø 1 2 5 Heating system return Ø 3 4 ...

Page 31: ...er for heating and hot water 28 Flue manifold 29 Flue outlet manifold 32 Heating circulator 34 Heating temp sensor 36 Automatic air vent 38 Flow switch 42 Tap water temperature sensor 43 Air pressure switch 44 Gas valve 47 Modureg 49 Safety thermostat 56 Expansion tank 81 Ignition and detection electrode 90 Flue detection point 91 Air detection point 114 Water pressure switch 132 Flue deflector 18...

Page 32: ...an 20 Burner assembly 27 Heat exchanger 29 Flueoutlet manifold 32 Heating circulator 34 Heating temperature sensor 38 Flow switch 42 Tap water temperature sensor 43 Air pressure switch 44 Gas valve 49 Safety thermostat 56 Expansion tank 81 Ignition and detection electrode 114 Water pressure switch 187 Flue restrictor 43 56 81 44 49 20 27 5 29 16 114 42 34 187 14 32 38 11 10 7 8 9 ...

Page 33: ... Maximum working pressure in heating bar 3 Safety valve bar 3 Minimum working pressure in heating bar 0 8 Expansion tank capacity litri 8 Expansion tank pre filling pressure bar 1 Boiler water content litres 1 5 Hot water Maximum hot water production Δt 25 C l min 13 7 Maximum hot water production Δt 30 C l min 11 4 Maximum working pressure in hot water production bar 9 Minimum working pressure in...

Page 34: ... D 4 5 Diagrams Pressure power diagrams Circulator losses of head Fig 19 Fig 20 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H2O A 3 2 1 Circulator speed 3 2 1 A Boiler losses of head mbar kW G31 LPG G20 Natural gas ...

Page 35: ...ition P Display 2 Press button P Display 3 Press button P Display 4 Press button P Display 5 Press button P Display 6 Press button P Display 7 The timer can be programmed with up to 8 ON and 8 OFF times by repeating the above procedure 6 30 1 8 30 2 12 00 3 12 00 4 6 00 1 9 00 2 12 30 3 14 00 4 16 30 5 22 30 6 16 00 5 23 30 6 Over ride By pressing the over ride button E the timer programme is over...

Page 36: ...hermostat 72 Room thermostat 81 Ignition detection electrode 114 Water pressure switch 139 Remote timer control opentherm 34 43 49 MF08FA 1 TRANSFORMER 42 114 44 16 32 230V 50Hz X5 X3 X7 X6 X4 1 2 1 2 3 1 2 3 4 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 9 10 11 FUSE FUSE X1 N L 81 47 38 F 3 15A F 3 15A 72 139 CAUTION Before connecting the room thermostat or the remote timer control remove the jumper on the ter...

Page 37: ...TED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE ft3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE C HOT WATER OUTLET TEMPERATURE C WATER FLOW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING THE H...

Page 38: ...NTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 5 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 6 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 7 DATE ENG...

Page 39: ......

Page 40: ...fore calling our Customer Service Helpline Lichfield Road Branston Industrial Estate Burton Upon Trent Staffordshire DE14 3HD Tel 08707 282 885 Fax 08707 282 886 EIRE only HEATOVENT Greenhills Industrial Estate Greenhills Road Walkinstown Dublin 12 IRELAND Tel 014508166 Fax 014508501 Should you require any assistance during the installation call our Technical Service Helpline on 08707 282 885 opti...

Reviews: