4.4 Troubleshooting
Diagnostics
The boiler has an advanced self-diagnosis system. In case of a boiler fault, the display
will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdowns (marked with the letter "
A
"): to restore
operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed. At this point the display will show
“d4”
for about
30 seconds
or
“d5”
for about
5 minutes
which indicates the waiting time after which the
boiler will resume normal operation. if the boiler fails to restart, it is necessary to eliminate
the fault.
Other faults cause temporary shutdowns (marked with the letter “
F
”) which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
List of faults
Table. 10
5. TECHNICAL DATA AND CHARACTERISTICS
Table. 11- Legend, fig. 26, fig. 27 and fig. 28
Code
fault
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the
boiler and that the air has been elim-
inated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode
and that it is correctly positioned and
free of any deposits
Faulty gas valve
Check the gas valve and replace it if
necessary
Gas valve wiring disconnected
Check the wiring
Ignition power too low
Adjust the ignition power
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature protection
activation
Heating sensor damaged
Check the correct positioning and
operation of the heating sensor
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
F04
Card parameter fault
Wrong card parameter setting
Check the card parameter and mod-
ify it if necessary
F05
Card parameter fault
Wrong card parameter setting
Check the card parameter and mod-
ify it if necessary
Fan fault
Wiring disconnected
Check the wiring
Defective fan
Check the fan
Card fault
Check the card
A06
No flame after the ignition
phase
Low pressure in the gas system
Check the gas pressure
Burner minimum pressure setting
Check the pressures
F07
Card parameter fault
Wrong card parameter setting
Check the card parameter and mod-
ify it if necessary
A09
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F11
DHW sensor fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
A16
Gas valve fault
Wiring disconnected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
F20
Combustion control fault
Fan fault
Check the fan and fan wiring
Faulty baffle
Check the baffle and replace it if
necessary
Flue not correctly sized or
obstructed
Check the flue
A21
Poor combustion fault
Fault F20 generated 6 times in the
last 10 minutes
See fault F20
A23
Card parameter fault
Wrong card parameter setting
Check the card parameter and mod-
ify it if necessary
A24
Card parameter fault
Wrong card parameter setting
Check the card parameter and mod-
ify it if necessary
F34
Supply voltage under 180V.
Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Incorrect system water pres-
sure
Pressure too low
Fill the system
Water pressure switch damaged or
not connected
Check the sensor
F39
External probe fault
Probe damaged or wiring shorted
Check the wiring or replace the sen-
sor
Probe disconnected after activating
the sliding temperature
Reconnect the external sensor or
disable the sliding temperature
A41
Sensor positioning
Delivery sensor or DHW sensor
detached from the pipe
Check the correct positioning and
operation of the sensors
F42
Heating sensor fault
Sensor damaged
Replace the sensor
F43
Exchanger protection trips.
No H
2
O system circulation
Check the circulating pump
Air in the system
Vent the system
F50
Gas valve fault
Modulating Operator wiring discon-
nected
Check the wiring
Faulty gas valve
Check the gas valve and replace it if
necessary
A51
Poor combustion fault
Inlet/exhaust flue obstruction
Check the flue
5
Sealed chamber
44
Gas valve
7
Gas inlet - Ø 1/2”
56
Expansion vessel
8
DHW outlet - Ø 1/2”
74
System filling faucet
9
DHW inlet - Ø 1/2”
81
Ignition and detection electrode
10
System delivery - Ø 3/4”
95
Diverter valve
11
System return - Ø 3/4”
114
Water pressure switch
14
Pressure relief valve
136
Flowmeter
16
Fan
137
Pressure sensor
19
Combustion chamber
191
Contact fume thermostat
22
Burner
193
Trap
27
Copper exchanger for heating and DHW
194
DHW exchanger
29
Fume outlet collar
241
Automatic bypass
32
Heating circulating pump
277
Fume recuperator
36
Automatic air vent
278
Double sensor ( heating)
37
Cold water inlet filter
42
DHW temperature sensor
Code
fault
Fault
Possible cause
Cure