background image

BLUEHELIX TECH S 45H

39

EN

Proceed in reverse order to refit the front panel. Make sure it is correctly hooked to the
upper fastenings and is correctly positioned at the sides. When tightened, the head of
screw "A" must not be below the lower fold (see fig. 25).

fig. 25 - Correct position of front panel

Periodical check

To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly inspection, providing for the following checks:

The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly

The fume exhaust circuit must be perfectly efficient

The sealed chamber must be tight

The air-fume end piece and ducts must be free of obstructions and leaks

The burner and exchanger must be clean and free of deposits For possible cleaning
do not use chemical products or wire brushes

The electrode must be properly positioned and free of scale

The gas and water systems must be tight.

The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value

The circulating pump must not be blocked.

The expansion tank must be filled.

The gas flow and pressure must correspond to that given in the respective tables

The condensate evacuation system must be efficient with no leakage or obstruc-
tions

The trap must be full of water.

4.4 Troubleshooting
Diagnostics

In case of operation faults or problems, the display flashes and the fault identification
code appears. 
There are faults that cause permanent shutdown (marked with the letter “

A

”): to restore

operation just press the 

reset

 button (detail 6 - fig. 1) for 1 second or RESET on the op-

tional remote timer control if installed; if the boiler fails to start, it is necessary to firstly
eliminate the fault.
Faults marked with the letter “

F

” cause temporary shutdowns that are automatically reset

as soon as the value returns within the boiler's normal working range.

Table of faults

Table. 8 - List of faults

Fault 
code

Fault

Possible cause

Cure

A01

No burner ignition

No gas

Check the regular gas flow to the 
boiler and that the air has been 
eliminated from the pipes

Ignition/detection electrode fault

Check the wiring of the electrode and 
that it is correctly positioned and free 
of any deposits

Faulty gas valve

Check the gas valve and replace it if 
necessary

Insufficient gas supply pressure

Check the gas supply pressure

Trap blocked

Check the trap and clean it if 
necessary

A02

Flame present signal with 
burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature 
protection intervention

Heating sensor damaged

Check the correct positioning and 
operation of the heating sensor

No water circulation in the system

Check the circulating pump

Air in the system

Vent the system

A04

Fume extraction duct safety 
device intervention

Fault F07 generated 3 times in the 
last 24 hours

See fault F07

A05

Fan protection activated

Fault F15 generated for 1 hour 
(consecutive)

See fault F15

OK

NO

A06

No flame after ignition stage 
(6 times in 4 minutes)

Ionisation electrode fault

Check the position of the ionisation 
electrode and replace it if necessary

Flame unstable

Check the burner

Gas valve Offset fault

Check the Offset adjustment at 
minimum power

air/fume ducts obstructed

Remove the obstruction from the flue, 
fume extraction ducts and air inlet and 
terminals

Trap blocked

Check the trap and clean it if 
necessary

F07

High fume temperature

The fume probe detects an excessive 
temperature

Check the exchanger

F10

Delivery sensor 1 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F11

Return sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F12

DHW sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F13

Fume probe fault

Probe damaged

Check the wiring or replace the fume 
probe

Wiring shorted
Wiring disconnected

F14

Delivery sensor 2 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F15

Fan fault

No 230V power supply

Check the 3-pin connector wiring

Tachometric signal interrupted

Check the 5-pin connector wiring

Fan damaged

Check the fan

F34

Supply voltage under 170V Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

F37

Incorrect system water 
pressure

Pressure too low

Fill the system

Water pressure switch damaged or 
not connected

Check the sensor

F39

External probe fault

Probe damaged or wiring shorted

Check the wiring or replace the sensor

Probe disconnected after activating 
the sliding temperature

Reconnect the external probe or 
disable the sliding temperature

A41
A44

Sensor positioning

Heating sensor detached from pipe

Check the correct positioning and 
operation of the heating sensor

A42

Heating sensor fault

Sensor damaged

Replace the sensor

F43

Exchanger protection inter-
vention.

No system H

2

O circulation

Check the circulating pump

Air in the system

Vent the system

F52

Heating sensor fault

Sensor damaged

Replace the sensor

A61

Controller 

ABM03C

 fault

Controller 

ABM03C

 internal error

Check the earth connection and 
replace the controller if necessary.

A62

No communication between 
electronic controller and 
gas valve

Controller not connected

Connect the controller to the gas valve

Valve damaged

Replace the valve

A63

F64

A65

F66

Controller 

ABM03C

 fault

Controller 

ABM03C

 internal error

Check the earth connection and 
replace the controller if necessary.

A23
A24

F20
F21

A26

F40
F47

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary.

Fault 
code

Fault

Possible cause

Cure

cod. 3541G102  -  Rev. 0

  -  0

/2016

Summary of Contents for BLUEHELIX TECH S 45H

Page 1: ...E ES INSTRUCCIONES DE USO INSTALACIÓN Y MANTENIMIENTO TR KULLANMA KURULUM VE BAKøM TALIMATLARø EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INSTALLATION ET D ENTRETIEN RO INSTRUCğIUNI DE UTILIZARE INSTALARE ùI ÎNTRETINERE RU ɊɍɄɈȼɈȾɋɌȼɈ ɉɈ ɗɄɋɉɅɍȺɌȺɐɂɂ ɆɈɇɌȺɀɍ ɂ ɌȿɏɈȻɋɅɍɀɂȼȺɇɂɘ UA ȱɇɋɌɊɍɄɐȱə Ɂ ȿɄɋɉɅɍȺɌȺɐȱȲ ɆɈɇɌȺɀɍ ɌȺ ɈȻɋɅɍȽɈȼɍȼȺɇɇə ...

Page 2: ...ons premix condensing heat generator with heat exchanger in steel and incorporated DHW production running on natural gas or LPG and equipped with a microprocessor control system The sealed chamber unit is suitable for indoor installation or outdoors in a partially pro tected place according to EN 297 A6 with temperatures to 5 C A The boiler is arranged for connection to an external storage tank fo...

Page 3: ...d the boiler will keep the system at the set system delivery setpoint temperature Room temperature adjustment with optional remote timer control Using the remote timer control set the required temperature in the rooms The boiler will adjust the system water according to the required room temperature For operation with remote timer control please refer to the relevant instruction manual Hot water t...

Page 4: ... on the unit fig 12 Plumbing connections 1 System delivery Ø 3 4 3 Gas inlet Ø 1 2 5 System return Ø 3 4 Antifreeze system antifreeze fluids additives and inhibitors When necessary antifreeze fluids additives and inhibitors can be used only if the man ufacturer of such fluids or additives guarantees that they are suitable and do not cause damage to the exchanger or other components and or material...

Page 5: ...connections terminal block fig 14 The layout of the terminals for the various connections is given in the wiring diagram in fig 29 fig 14 Accessing the terminal block 3 6 Fume ducts Important The unit is type C with sealed chamber and forced draught the air inlet and fume outlet must be connected to one of the following extraction suction systems Before installation check and carefully observe the...

Page 6: ...nd check the tightness of the connection 6 Apply the label contained in the conversion kit near the data plate 7 Refit the front panel 8 Modify the parameter for the type of gas put the boiler in standby mode press the DHW buttons details 1 and 2 fig 1 for 10 seconds the display shows b01 flashing press the DHW buttons details 1 or 2 fig 1 to set parameter 00 for operation with natural gas or 01 f...

Page 7: ...ystem DHW circuits connections or boiler Check correct connection of the electrical system and efficiency of the earthing system Make sure the gas pressure for heating is that required Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler Checks during operation Switch the unit on Check the tightness of the fuel circuit and water systems Check the efficiency...

Page 8: ...traction duct safety device intervention Fault F07 generated 3 times in the last 24 hours See fault F07 A05 Fan protection activated Fault F15 generated for 1 hour consecutive See fault F15 OK NO A06 No flameafter ignitionstage 6 times in 4 minutes Ionisation electrode fault Check the position of the ionisation electrode and replace it if necessary Flame unstable Check the burner Gas valve Offset ...

Page 9: ...Auxiliary contact 104 Fuse 114 Water pressure switch 193 32 114 14 36 186 81 95 278 10 7 11 44 191 196 22 16 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H2O A 8 9 C B 2 500 Data Unit BLUEHELIX TECH S 45H Max heating capacity kW 43 0 Q Min heating capacity kW 7 5 Q Max Heat Output in heating 80 60 C kW 4 P Min Heat Output in heating 80 60 C kW 7 3 P Max Heat Output in heating 50 30 C kW 4 Min...

Page 10: ...ĨĨŝĐŝĞŶĐLJ Ăƚ ϯϬй ŽĨ ƌĂƚĞĚ ŚĞĂƚ ŽƵƚƉƵƚ ĂŶĚ ůŽǁͲƚĞŵƉĞƌĂƚƵƌĞ ƌĞŐŝŵĞ ΎΎͿ ƚ ĨƵůů ůŽĂĚ ƚ ƉĂƌƚ ůŽĂĚ Ŷ ƐƚĂŶĚďLJ ŵŽĚĞ ƚĂŶĚďLJ ŚĞĂƚ ůŽƐƐ ŐŶŝƚŝŽŶ ďƵƌŶĞƌ ƉŽǁĞƌ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞŶĞƌŐLJ ĐŽŶƐƵŵƉƚŝŽŶ ŽƵŶĚ ƉŽǁĞƌ ůĞǀĞů ŵŝƐƐŝŽŶƐ ŽĨ ŶŝƚƌŽŐĞŶ ŽdžŝĚĞƐ dƌĂĚĞŵĂƌŬ ZZK ŽŶĚĞŶƐŝŶŐ ďŽŝůĞƌ z ŽǁͲƚĞŵƉĞƌĂƚƵƌĞ ďŽŝůĞƌ ΎΎͿ EK ϭ ŽŝůĞƌ EK ŽŵďŝŶĂƚŝŽŶ ŚĞĂƚĞƌ EK ŽŐĞŶĞƌĂƚŝŽŶ ƐƉĂĐĞ ŚĞĂƚĞƌ EK ΎͿ ŝŐŚͲƚĞŵƉĞƌĂƚƵƌĞ ƌĞŐŝŵĞ ŵĞĂŶƐ ϲϬΣ ƌĞƚƵƌŶ ƚĞŵƉĞƌĂ...

Page 11: ...ontrol 278 T T 32 191 N L 186 44 114 139 72 230Vac 50Hz LC32 3 2 1 95 16 PWN GND 256 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 3 4 5 6 1 2 5 1 GND Vcc TACHO PWM 1 3 104 FUSE 3 15A 250V ABM03C 81 T1 X4 X3 X2 X1 18 12 1 2 1 1 1 X6 24 230V 1 2 A 155 10 k 1 8 k 138 cod 3541G102 Rev 0 0 2016 ...

Page 12: ...rettiva Bassa Tensione 2006 95 Direttiva Compatibilità Elettromagnetica 2004 108 Presidente 3DROD Ferroli IT Uygunluk beyani ømalatçi FERROLI S p A Adres Via Ritonda 78 a 37047 San Bonifacio VR bu cihazin asagida yer alan AET EEC yönergelerine uygunluk içinde oldugunu beyan etmektedir 2009 142 Gazla çalistirilan üniteler için Yönetmelik QHUJH U3 Yönerge 2006 95 Düsük Voltaj 2004 108 Elektromanyeti...

Page 13: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Reviews: