M 1261-06-X AquaSol Ferroli Installation Manual.doc
July 2006
Page 16 of 24
Diagram 1
Typical discharge pipe arrangement
300mm
minimum
500mm maximum
tundish
metal discharge pipe (D1) from
temperature relief valve to tundish
metal discharge pipe (D2) from tundish
with continuous fall. See 3.9d i-iv,
Table 1 and worked example
Discharge below
fixed grating
(3.9 gives
alternative points
of discharge)
fixed grating
trapped gulley
safety device
(e.g. temperature
relief valve)
Valve
Outlet
Size
Minimum
size of
Discharge
pipe D1
Minimum
size of
discharge
pipe D2
from tundish
Maximum
resistance
allowed,
expressed as a
length of
straight pipe
(i.e. no bends
or elbows)
Resistance
created by
each elbow
or bend
G½ 15mm
22mm
28mm
35mm
Up to 9m
Up to 18m
Up to 27m
0.8m
1.0m
1.4m
G¾ 22mm
28mm
35mm
42mm
Up to 9m
Up to 18m
Up to 27m
1.0m
1.4m
1.7m
G1 28mm
35mm
42mm
54mm
Up to 9m
Up to 18m
Up to 27m
1.4m
1.7m
2.3m
Tabel 1
Sizing of copper discharge pipe D2 for common temperature relief valve outlet sizes.