background image

 21 

SAFETY 

The law requires that any service work must be carried out by 
a Gassafe Registered Engineer.  In IE service work must be 
carried out by a competent person. 

WARNING. 

Always turn off the gas supply at the gas service cock. 
Switch off and disconnect the electricity supply to the 
appliance and any external controls before servicing or 
replacing components.

 

IMPORTANT

 

After completing the servicing or replacement of       
components always: 

 Test for gas tightness 

Test the burner manifold flanges for soundness. 

This can be done with leak detection spray whilst  
operating the boiler.  The gas valve and controls must be 
shielded from the spray. 
 
Check the water system is correctly filled and free 
of air. Air in the boiler could cause damage to the  
heat exchanger. For this reason if an automatic air vent is 
fitted it must never be shut off. 

Check the inner front and outer jacket panels are correctly 
fitted. 

With the system hot examine all water connections for sound-
ness. 

Check the gas rate and measure the combustion CO/CO2 
content. Refer to page 19 for reference on how to force the 
burner to maximum and minimum gas rates. 

The CO/CO2   ratio of the flue gas on each  module should not 
be greater than 0.004 ratio. The CO2  values should be cor-
rect to the figures on page 20. 

Carry out functional checks as appropriate. 

HANDING OVER 

ROUTINE OPERATION 

Full instructions covering routine lighting and operation of the 

boiler are given on the Lighting and Operation Instruction 

section of this manual. 

Draw the attention of the boiler owner or his representative to 

the Lighting and Operating Instructions. Give a practical 

demonstration of the lighting and shutting down of the boiler. 

Describe the function of the boiler and system controls and 

show how they are adjusted and used. 

Hand these Installation and Servicing Instructions/User's 

Instructions and Log book to the customer and request him to 

keep them in a safe place for ready reference. For IE, it is 

necessary to complete a "Declaration of Conformity" to indi-

cate compliance to the appropriate standard. 

 

IMPORTANT 

Point out to the owner that the boiler must have regular 

maintenance and cleaning, at least annually, in order to 

ensure reliable and efficient operation. Regular attention will 

also prolong the life of the boiler and should preferably be 

performed at the end of the heating season. 

After servicing, complete the service section of the log book 

and return to the owner or their representative. 

Recommend that a contract for this work should be made 

with the regional gas authority or a Gas Safe Registered 

Engineer. In IE servicing work must be carried out by a 

competent person. 

SERVICING INSTRUCTIONS 

To ensure the continued safe and efficient operation of the 
appliance it is recommended that it is checked at regular in-
tervals and serviced as necessary. The frequency of servicing 
will depend upon the installation condition and usage but 
should be carried out at least annually. 

Ferroli Ltd does not accept any liability resulting from the use 
of unauthorised parts or the repair and servicing of appliances 
not carried out in accordance with the Company's recommen-
dations and specifications.   

Note. 

Some aluminium oxide build-up within the heat exchanger 
assembly is quite usual with this type of condensing boiler. 
Though removal and cleaning is recommended annually, the 
heat exchanger, sump and condensate trap must be inspect-
ed and cleaned after a maximum of 2 years operation. 

Light the boiler and carry out function checks, noting any op-
erational faults. 

 

Run the boiler for 10 minutes and then check the gas con-
sumption rate. Refer to Technical Data Table. To force the 
burner to maximum and minimum rates refer to page 19. 

For correct boiler operation the CO/CO ratio of the flue gas 
should not be greater than 0.004 ratio and the CO2 values 
should be correct to the figures given on page 20 of this man-
ual. If this is the case and the gas input is at least 90% of the 
nominal, then no further action need be taken. If not proceed 
to page19 for guidance. 

Remove and inspect the fan/venturi assembly. 

Remove the burner manifold and inspect the electrodes and 
sight glass. 

Remove and clean the burner. 

Inspect the heat exchanger through the burner opening. Op-
tionally remove the inspection covers on the side of the heat 
exchanger. If there are signs of aluminium oxide build up, 
spray water down the flue ways taking care not to get water 
on the gas valve and controls. 

Clean the condensate trap.  

Check that the flue terminal and air inlet are unobstructed and 
that the flueing and ducting are correctly sealed. 

Put the boiler back into normal operation. 

Summary of Contents for 303: 304

Page 1: ...NEW CONDENS FS 300 SERIES Cast Aluminium Floor Standing Condensing Boilers for Natural Gas INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE Rev 00 12 2015 PB IB300 ...

Page 2: ...lies with the following EU directives Gas Appliance Directive 2009 142 Efficiency Directive 92 42 Low Voltage Directive 2006 95 Electromagnetic Compatibility Directive 2004 108 EN President andLegalRepresentative NEW CONDENS FS 300 SERIES 0051 ...

Page 3: ... appliance The installer must abide by the following instructions Read and follow the instructions given in the manuals provided with the appliance Install the appliance in compliance with prevailing legislation and standards Carry out initial commissioning and any checks necessary Explain the installation to the user If maintenance is necessary warn the user of the obligation to check the applian...

Page 4: ...someone responsible for their safety The unit and its accessories must be appropriately dis posed of in compliance with the current regulations The images given in this manual are a simplified repre sentation of the product In this representation there may be slight and insignificant differences with respect to the product supplied HEALTH SAFETY The electricity at work regulations 1989 The manufac...

Page 5: ...0 160 150 Structural Characteristics Water Contents l 6 5 8 5 10 5 12 5 14 5 Empty weight kg 107 133 164 196 226 Width mm 420 490 490 580 580 Height mm 1220 1220 1220 1240 1260 Depth mm 755 865 1130 1275 1415 Electrical Specifications Power supply voltage V Hz 230 50 Protection level IP 20 Power consumption W 160 190 260 260 320 Water and Gas Fittings Central heating flow outlet 1 1 1 1 1 Central ...

Page 6: ...100 233 87 104 302 R 1 R 80 50 304 488 803 1078 934 380 941 111 281 97 156 394 R 1 R 100 80 305 488 1066 1078 949 394 932 120 284 96 160 374 R 1 R 1 110 80 306 583 1213 1138 945 385 963 127 305 97 183 385 R 1 R 1 125 115 307 583 1309 1138 956 396 945 133 311 110 175 433 R 1 R 1 160 115 ...

Page 7: ...nt 600mm except access doors may be closer but not less than 200mm and 600mm must still be available for service across the width of the boiler Rear 1000mm or adequate space from the rear of the jacket to make the flue connections and access to the flue sample point drain connection flue and any safety or control devices Top 800mm Left side 800mm Right side 800mm Between boilers 200mm Recommended Min...

Page 8: ...s in buildings BS 6880 1 1988 Code of practice for low temperature hot water heating systems of output greater than 45 kW Funda mental and design considerations BS 6880 2 1988 Selection of equipment BS 6880 3 1988 Installation commissioning and maintenance BS EN 13384 1 2015 Chimneys Thermal and fluid dynamic calculation methods Chimneys serving one heating appliance BS EN 13384 2 2015 Chimneys Th...

Page 9: ... soundness and purged in accordance with the appropriate standards Gas Boosters A gas booster is required if the gas pressure available at the boiler is lower than that required by the boiler manufacturer to attain the flow rate for maximum burner input rating Location of the booster requires careful consideration but should preferably be closer to the burner rather than the gas meter Ventilation s...

Page 10: ...om a clean source outside the boiler room building Where it is not possible to duct air from outside the boiler the air inlet guard MUST be used Material With no requirement for buoyancy to discharge flue products and with low flue gas temperatures single wall flues are suitable for most installations Care should still be taken to maintain compliance with building regulations and relevant standards T...

Page 11: ...s a pump must be sup plied from the terminals inside the boiler Note for pumps requiring greater than 1 0 amp current they must be con nected via a relay When sizing pumps reference should be made to the Hydraulic Resistance Table on page 12 which show the boiler resistance against flow rates to achieve the required temperature differential Flow rates for common systems using either 11o C or 20o C ...

Page 12: ...H value and the volume of top up water used It is most important that the correct concentration of the water treatment products is maintained in accordance with the manu facturers instructions If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleansing In hard water areas treatment to prevent lime scale may be necessary In this instance the use o...

Page 13: ... not show safety valves wa ter flow switches etc necessary for the safe operation of the system Cold Feed Pipe Sizes Open Vent Pipe Sizes OPEN VENTED SYSTEM REQUIREMENTS Detail reference should be made to the appropriate standards listed on page 8 The information and guidance given below is not intended to override any requirements of the above publications or the requirements of the local authorit...

Page 14: ...er is specified the flue manifold conden sate drain connection must also be connected in the same manner SEALED SYSTEM REQUIREMENTS Working pressure 6 bar maximum Particular reference should be made to BS 6644 and Guid ance note BG01 Automatically controlled steam and hot water boilers published by the Health and Safety Executive The information and guidance given below is not intended to override a...

Page 15: ... should be 3 core PVC insulated cable NOT LESS than 0 75mm2 24 x 0 2 mm and to BS 6500 The fuse rating should be 7A Wiring external to the boiler MUST be in accordance with the current I E E BS7671 wiring Regulations and any local regu lations For Ireland reference should be made to the current ETCI rules for electrical installations Connection should be made in a way that allows complete isolatio...

Page 16: ...16 Wiring diagram ...

Page 17: ...17 Sensor locations ...

Page 18: ... drain system and trap Ensure the water is circulating correctly between the boiler and the system Ensure the gas valve modulates correctly in heating and domestic hot water modes Put the boiler through several ignition sequences to ensure correct firing operation Using a combustion analyser connected to the boiler flue outlet check that the CO2 content in the fumes with the boiler operating at ma...

Page 19: ...he units memory the information button will need to be pressed again until a percentage figure is shown on the screen Fig 2 The display now shows the boilers power output as a percentage Press the confirmation button once The figure will now flash intermittently Rotate the selection dial until the figure reads 100 Fig 3 Press the confirmation button once more to save this value To reduce the boile...

Page 20: ...chieve the correct CO2 reading shown in the table below Clockwise to decrease anti clockwise to increase Minimum rate adjustment Adjust the modulation rate to minimum 0 as described on page 19 Allow combustion and flame to stabilise then compare CO2 reading to that given in the table below To adjust remove adjustment cover with a flat blade screwdriver Using a 40Torx driver adjust CO2 Clockwise to...

Page 21: ... operation Regular attention will also prolong the life of the boiler and should preferably be performed at the end of the heating season After servicing complete the service section of the log book and return to the owner or their representative Recommend that a contract for this work should be made with the regional gas authority or a Gas Safe Registered Engineer In IE servicing work must be car...

Page 22: ...22 Notes ...

Page 23: ...23 ...

Page 24: ...24 FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Reviews: