3
ECC+ 230 V Electronic Module
The unit has to be programmed using the DIP switches on the front of the unit. If any
change is made to any of the above switch selections, the unit must be switched OFF
and ON again to read the new programming.
The switches functions are:
1
Working.
ON:
Encoder.
The door movement control will be done using the motor encoder or the motor encoder
and a close limit switch.
OFF:
Limit switch.
The door movement control will be done using an open limit switch and a close limit
switch.
2
Motor (This option is only used with the motor ELVI 104661 FCE).
ON:
Special Motor.
Different control is applied to perform the door movement with a special motor.
OFF:
Standard Motor.
Standard control is applied to perform the door movement.
3
Door model (This option is only used with the motor ELVI 104661 FCE).
ON:
Heavy door.
The motor supplies a 30% extra torque to be able to move heavy doors.
OFF:
Standard door.
Standard control is applied to perform the door movement.
4
Floor level.
Inputs
12 V battery
ON
2 Inputs
1 Input
OFF
Note:
With DIP-switch No. 4 OFF is necessary to install a floor level contact in each floor.
J209
1 and 2 INPUTS.
1 Input (1-IN
).
The door control unit will be controlled by a single input. Any voltage between 24 V DC
to 60 V DC or 100 V AC to 230 V AC applied between terminals 10 and 12 will close the
doors. Without input active the door remains opened. Open input is not used.
2 Inputs (2-IN
).
The door control unit will be controlled by two independent inputs. Any voltage between
24 V DC to 60 V DC or 100 V AC to 230 V AC applied between terminals 10 and 12 will
cause the doors to close. And between terminals 8 and 10 will cause the doors to open.
In the absence of a signal, the doors will remain static. If both inputs are applied then the
open signal has priority.
1
O
N
2 3 4
O
F
F
PROGRAMMING