28
INDUSTRIE
FALCON
7.07 D.H.W. temperature sensor or Central Heating Temperature Sensor
(fig. 31)
• Isolate electricity and water supplies
• Remove outer case (two screws bottom rear corners)
• Remove the two securing screws and lower control panel
• Identify the sensor from figure 31
• Disconnect electrical connection to the sensor
• Drain the boiler
• Unscrew the sensor
• Replace in reverse order
7.11 Water Pressure Switch
(fig. 31)
• Isolate electricity and water supplies
• Remove outer case (two screws bottom rear corners)
• Remove the two securing screws and lower control panel
• Identify the switch from figure 31
• Disconnect electrical conne note positions to the switch
• Drain the boiler
• Unscrew the sensor
• Replace in reverse order
7.12 Safety Valve
(fig. 31)
• Isolate electricity and water supplies
• Remove outer case (two screws bottom rear corners)
• Remove the two securing screws and lower control panel
• Identify valve from fig. 31
• Drain the boiler
• Release the outlet union to the valve and undo the valve union
connection
• Remove the valve outlet fitting
• Replace in reverse order
7.05 Gas valve
(fig. 29)
• Isolate gas and electricity supplies
• Remove outer case (two screws bottom rear corners)
• Remove the two securing screws and lower control panel
• Disconnect electrical connections from valve ("A", "B")
• Disconnect plastic tube "C"
• Loosen the connection "D" on gas pipe and connection of the boiler
• Remove the two fixing screw "E" below gas valve
• Slide out gas valve
• Remove four fixing screw "F" on top of the disconnect the gas pipe
• Remove bottom connection from gas valve.
• Fit top + bottom gas connections to the new gas valve and replace in
reverse order
Fig. 29
7.06 Air pressure switch
(fig. 30)
• Isolate electricity
• Remove outer case (two screws bottom rear corners)
• Open room sealed department
• Remove the two screw "A" fixing air pressure switch
• Disconnect electrical leads "B"
• Remove pressure sensing tubes (white=D; Red=C)
• Note relevant positions of all connections and
replace in reverse order.
D
C
A
F
B
E
Fig. 30
A
B
C
D
C.H. sensor
Water pressure
switch
D.H.W. sensor
Safety valve
Fig. 31