background image

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no
responsibility for the product's suitability for a particular application. The product must be prop-
erly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

Protection Systems

KIDDE-FENWAL, INC.

400 MAIN STREET, ASHLAND, MA 01721

TEL: (508)881-2000 FAX: (508) 881-8920

www.fenwalfire.com

TM

70.03 Rev. AA             ©2006 Kidde-Fenwal Inc.           Printed in USA

Table 4. Ordering Information

Part Number

Model

Description

Detector Heads - Ionization Smoke

70-540000-001

CPD-7054

Ionization Advanced Smoke Detector 

  

(cULus)

70-540000-002

CPD-7054D

Ionization Advanced Smoke Detector 

  

(cULus)

Detector Heads - Photoelectric Smoke

71-570000-001

PSD-7157

Photoelectric Advanced Smoke Detector 

  

(cULus)

71-570000-002

PSD-7157D

Photoelectric Advanced Smoke Detector 

 

(cULus)

Detector Heads - Heat

70-520000-001

THD-7052

135

o

F Fixed Heat Detector, 15

o

F Rate of Rise 

 

(cULus)

70-530000-001

THD-7053

135

o

F Fixed Heat Detector 

 

(cULus)

Detector Bases

70-501000-001

2-WIRE

2-Wire Standard Base

70-501000-002

2WRLT

2-Wire Base with Remote LED & Test Capabilities

70-501000-005

2WRB

2-Wire Base with Auxiliary Relay, Remote LED & Test Capabilities

70-501000-101

4WRB

4-Wire Base with Auxiliary Relay, Remote LED & Test Capabilities

70-500000-004

2WRM

Spare 2-Wire Relay Module

70-500000-102

4WRM

Spare 4-Wire Relay Module

Detector Accessories

06-117883-001

Test Magnet

29-116788-001

EOL Supervisory Relay

70-200000-911

RA-911

Remote Alarm Indicator

70-200000-914

RA-914

Remote Alarm Indicator with Smoke Detector Test Switch

70-500000-003

DST-003

Advanced Handheld Wireless Smoke Detector Sensitivity Tester

70-501000-003

MA-001

Mechanical Retrofit Adapter

Table 3. Detector Base Options

Part Number

Model

CID

Description

70-501000-001

2-WIRE

FE51A

2-W Base. Connects to circuit via screw terminals

70-501000-002

2WRLT

FE52A

2-W  Base w/ Remote LED & Test capabilities.  Connects to detection via screw

terminals. Minimum Alarm Current 15 mA @ 24 VDC.

70-501000-005

2WRB

FE55A

2-W Base w/ 2WRM, Remote LED & Test capabilities. Connects to detection circuit

via pigtail leads. Minimum Alarm Current 19 mA @ 24VDC

70-501000-101

4WRB

N/A

4-W Base w/ 4WRM, Remote LED & Test capabilities. Connects to detection circuit
via pigtail leads. Minimum Alarm Current 35 mA @ 24VDC

70-500000-004

2WRM

N/A

SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 VDC/ 0.5 A, 125 VAC

70-500000-102

4WRM

N/A

SPDT Relay for 4WRB Bases. Contacts rated 1.0 A,  30 VDC / 0.5 A, 125 VAC

70-501000-003

MA-001

MAFE1

Mechanical Adapter allows CPD-705X & PSD-715X Detectors to physically connect to
Base P/Ns 70-201000-001, -002, -003, -005 & DH-22

Summary of Contents for THD-7052

Page 1: ...ecial signal processing techniques verify the presence of smoke before the detector will alarm The detector head is installed into the base with a simple twist lock action A locking feature is provided for vandal resistant se curity Detector base options are available to provide for auxiliary test indication and or control functions Optional bases are available for supplementary 2 wire or 4 wire r...

Page 2: ...feature Fenwal Model THD 7052 Heat Detectors The contractor shall also furnish and install where indicated on the plans thermistor based electronic Fixed Temperature Fenwal Model THD 7053 Heat Detectors The fixed temperature alarm set point of the THD 7052 and THD 7053 Detectors shall be 135F 57C and the Rate Of Rise detection feature of the THD 7052 shall be rated at 15F 8 3C per minute The combi...

Page 3: ...100 mA 100 mA Response Indicators Quantity 2 external LEDs 2 external LEDs Standby Condition One flash every 6 seconds One flash every 6 seconds Thermistor Trouble Double flash every 6 seconds Double flash every 6 seconds Alarm Condition Steady at full brilliance Steady at full brilliance Operating Environment Operating Temperature 32o to 100o F 0 to 38o C 32o to 100o F 0 to 38o C Storage Temperat...

Page 4: ...iary Relay Remote LED Test Capabilities 70 501000 101 4WRB 4 Wire Base with Auxiliary Relay Remote LED Test Capabilities 70 500000 004 2WRM Spare 2 Wire Relay Module 70 500000 102 4WRM Spare 4 Wire Relay Module Detector Accessories 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator with Smoke Detecto...

Reviews: