background image

Electronic Heat Detectors

Models THD-7052 & THD-7053

70.03

Effective: January 2006

FEATURES

Approvals/Listing

US and Canadian UL Listed (cULus)

FM Approved

CSFM Approved

NYC MEA Accepted (pending)

Thermistor based Heat Detection

Nominal Sensitivity

THD-7052: 135

o

F (57

o

C) Fixed Temperature w/

15

o

F (8.3

o

C) per minute Rate-Of-Rise

THD-7053: 135

o

F (57

o

C) Fixed Temperature

Wide Range of Input Voltage 10.2 to 36.8 VDC

Low Current design

Dual Response LEDs allow 360-degree viewing

Trouble Indication

Low Profile Appearance using Surface Mount Technology

Electrically and Mechanically Compatible with all Fenwal
Smoke and Electronic Heat Detectors and Bases

Interchangeable 2-Wire and 4-Wire Bases

Universal Relay Modules

Non Polarized

Locking Feature for Vandal Resistance

EMI and RFI Resistant

DESCRIPTION

The Fenwal Models THD-7052 and THD-7053 are thermistor-
based electronic Heat Detectors with a 135

o

F (57

o

C) Fixed

Temperature set point. In addition, the Model THD-7052 has a
Rate-Of-Rise of temperature detection feature rated at 15

o

F (8.3

o

C)

per minute. Both detectors have advanced solid-state, low-voltage,
surface-mount circuitry and are designed for 2-Wire and 4-Wire
installation using the appropriate Detector base. The detectors
are designed for Open Area Protection (UL 521) and may be
installed in systems intended for Releasing Device Service through
use of a compatible Fire Alarm Control Panel

Two Red Light Emitting Diodes are located diametrically opposite
each other so as to allow 360-degree viewing. Both LEDs
continuously indicate the operating condition of the Detector. During
standby, the LEDs flash once every six seconds. During alarm,
both LEDs light steady at full brilliance. A double flash every six
seconds indicates a detector with a thermistor trouble. An optional
base is available to provide remote LED function. A unique gated
output circuit design provides improved stability and transient sup-
pression. Special signal processing techniques verify the presence
of smoke before the detector will alarm.

The detector head is installed into the base with a simple twist-
lock action. A locking feature is provided for vandal resistant se-
curity. Detector base options are available to. provide for auxiliary
test, indication and/or control functions

Optional bases are available for supplementary 2-wire or 4-wire
relay functions. The Model THD-705x Heat Detectors may be in-
terchanged with other Fenwal Series CPD-705X Ionization and
Series PSD-715X Photoelectric Smoke Detectors when using
multifunction base configuration.

TECHNICAL SPECIFICATIONS

Table 2 lists the Technical Specifications for Models THD-7052
and THD-7053 Heat Detectors.

CONTROL UNITS

The Models THD-7052 and THD-7053 Detectors are designed
for operation with control units and releasing devices having spe-
cific voltage and current characteristics that are compatible with
the detector circuitry. The Detectors are compatible with the
Fenwal control units and interface modules listed in Table 1.

Please refer Fenwal Document 70.63 for UL Compatibility List-
ings with Fire Alarm Panels manufactured by others.

DETECTOR BASE OPTIONS

The Models THD-7052 and THD-7053 Detectors can be used
with the detector base options and accessories in Tables 3 and
4. Various base options are available to provide auxiliary relay
and/or remote indication and remote test feature.

SPACING (OPEN AREA LOCATION)

For UL/ULC applications, the Model THD-7052 and THD-7053
Detectors are listed to be installed on 70 foot (21.3 m) centers,
typically on smooth ceilings up to 15 feet (4.6 m) high and will
operate with minimum air circulation. Resultant maximum 4,900
square foot (455.2 m

2

) spacing may be used as a reasonable

guide for comparable applications.

For FM applications, the listed spacing is 35 feet (10.7 m) cen-
ters. Where special conditions exist (ceiling obstructions, etc.),
reduced spacing must be used to achieve adequate protection.

For additional information, consult the Fenwal Automatic Fire De-
tection Application Engineering Manual MC-402, NFPA-72 and
the local Authority Having Jurisdiction.

Summary of Contents for THD-7052

Page 1: ...ecial signal processing techniques verify the presence of smoke before the detector will alarm The detector head is installed into the base with a simple twist lock action A locking feature is provided for vandal resistant se curity Detector base options are available to provide for auxiliary test indication and or control functions Optional bases are available for supplementary 2 wire or 4 wire r...

Page 2: ...feature Fenwal Model THD 7052 Heat Detectors The contractor shall also furnish and install where indicated on the plans thermistor based electronic Fixed Temperature Fenwal Model THD 7053 Heat Detectors The fixed temperature alarm set point of the THD 7052 and THD 7053 Detectors shall be 135F 57C and the Rate Of Rise detection feature of the THD 7052 shall be rated at 15F 8 3C per minute The combi...

Page 3: ...100 mA 100 mA Response Indicators Quantity 2 external LEDs 2 external LEDs Standby Condition One flash every 6 seconds One flash every 6 seconds Thermistor Trouble Double flash every 6 seconds Double flash every 6 seconds Alarm Condition Steady at full brilliance Steady at full brilliance Operating Environment Operating Temperature 32o to 100o F 0 to 38o C 32o to 100o F 0 to 38o C Storage Temperat...

Page 4: ...iary Relay Remote LED Test Capabilities 70 501000 101 4WRB 4 Wire Base with Auxiliary Relay Remote LED Test Capabilities 70 500000 004 2WRM Spare 2 Wire Relay Module 70 500000 102 4WRM Spare 4 Wire Relay Module Detector Accessories 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator with Smoke Detecto...

Reviews: