Fenwal SERIES 35-67 Manual Download Page 8

400 MAIN STREET, ASHLAND, MA 01721

TEL: (508) 881-2000    FAX: (508) 881-6729

www.fenwalcontrols.com

© 2009 Kidde-Fenwal     Printed in 

U.S.A.    TAG

These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications are subject to change without
notice. Should further information be desired or should particular problems arise which are
not covered sufficiently for the purchaser’s purposes, the matter should be referred to
KIDDE-FENWAL, Inc., Ashland, Massachusetts.

P/N 35.67.03   01/22/09

Page 8

Series 35-67, 24 VAC Hot Surface Ignition Control

www.fenwalcontrols.com   

1-800-FENWAL-1

®

CONTROL CONFIGURATION

-   X X  X

Trial for Ignition

0 = 2 Seconds
1 = 4 Seconds
3 = 7 Seconds
5 = 10 Seconds
7 = 15 Seconds

Proving Current (Amps)

0 = 0.8
1 = 0.5 
3 = 2.1
4 = 2.3
5 = 2.7
6 = 3.1
7 = 3.3

Purge Timing

0 = 0 Prepurge, 0 Interpurge, 0 Postpurge
1 = 15 Prepurge, 15 Interpurge, 0 Postpurge
2 = 30 Prepurge, 30 Interpurge, 0 Postpurge
3 = 0 Prepurge, 15 Interpurge, 0 Postpurge (3 Try Units Only)
4 = 0 Prepurge, 30 Interpurge, 0 Postpurge (3 Try Units Only)
5 = 15 Prepurge, 15 Interpurge, 30 Postpurge (Full Time Power) 
6 = 30 Prepurge, 30 Interpurge, 30 Postpurge (Full Time Power)
7 = 0 Prepurge, 15 Interpurge, 15 Postpurge (Full Time Power)
8 = 0 Prepurge, 30 Interpurge, 30 Postpurge (Full Time Power)

Tries For Ignition

0 = Single Try - Local Sense. Recycle On Flame Loss
1 = Single Try - Remote Sense. Recycle On Flame Loss
2 = Single Try - Local Sense. Lockout On Flame Loss
3 = Single Try - Remote Sense. Lockout On Flame Loss
5 = Three Tries - Local Sense. Recycle On Flame Loss
6 = Three Tries - Remote Sense. Recycle On Flame Loss
7 = Three Tries - Local Sense. Lockout On Flame Loss
8 = Three Tries - Remote Sense. Lockout On Flame Loss

Dwell Time

0 = 4 Seconds
1 = 6 Seconds
5 = 20 Seconds
7 = 40 Seconds

Full Time Power, Termination, Lockout Type

0 = No Full Time Power, Q.C. Terminals, Automatic Reset
1 = No Full Time Power, Mate-N-Lock, Automatic Reset 
2 = Full Time Power, Q.C. TERMINALS, Automatic Reset
3 = Full Time Power,  Mate-N-Lock, Automatic Reset
4 = No Full Time Power, Q.C. Terminals, Non-volatile Lockout 
5 = No Full Time Power,  Mate-N-Lock, Non-volatile Lockout 
6 = Full Time Power, Q.C. Terminals, Non-volatile Lockout  
7 = Full Time Power, Mate-N-Lock, Non-volatile Lockout 
8 = Aftermarket Kits (Consult Factory for Special Number)
9 = Special OEM Features (Consult Factory for Special Number)

Other Features

0 = No Indicators With No Inducer
1 = No Indicators With  Inducer
2 = Indicators With No Inducer
3 = Indicators and Inducer
4 = CE Approved Model
9 = Manual Reset (Standard Includes Indicators and Inducer)

35  -  67

X X X X

Description

Summary of Contents for SERIES 35-67

Page 1: ...h LED output provide assistance with troubleshooting to ensure safe and efficient burner operation Agency Certifications Design certified by CSA International to CAN C22 2 199 M89 and ANSI Z21 20 for Automatic Ignition Systems including UL1998 Software Review Special models approved to EN298 2003 available upon request SERIES 35 67 24 VAC Microprocessor Based Proven HSI Control with Combustion Blo...

Page 2: ...current through the ignition element When the current reaches a pre determined level the LED will flash once Dwell Time From the point when the current has been proven there will be a delay called dwell time Dwell time assures that the ignition element has sufficient time to reach ignition temperature 4 IGNITION When dwell time is completed the gas valve will open The ignition element will turn of...

Page 3: ...fications could result in failure of the Fenwal product and other equipment with injury or death to people and damage to property Service to this product should only be preformed by a qualified technician 5 Series 35 67 24 VAC Hot Surface Ignition Control Page 3 www fenwalcontrols com 1 800 FENWAL 1 PIN LOCATION 1 2 3 4 5 6 7 8 9 10 11 WIRE COLOR ORANGE RED VIOLET GRAY BROWN BLUE YELLOW GREEN WHIT...

Page 4: ...lect the proper harness based on the 35 67 control s termination connection Once the terminal configuration is determined complete the part number by replacing the last two digits XX with the length in inches l dimension Standard wire lengths are 12 18 24 30 36 and 48 inches Example 05 129845 018 18 inches For other lengths please contact Fenwal Part Number 22 100001 110 REMOTE FLAME SENSE ROD ...

Page 5: ...Series 35 67 24 VAC Hot Surface Ignition Control Page 5 www fenwalcontrols com 1 800 FENWAL 1 WIRING Figure 4A STANDARD DESIGN AUTOMATIC RESET PIN LAYOUT Figure 5A ...

Page 6: ...www fenwalcontrols com 1 800 FENWAL 1 Page 6 Series 35 67 24 VAC Hot Surface Ignition Control OPTIONAL DESIGN MANUAL RESET WIRING Figure 4B PIN LAYOUT Figure 5B ...

Page 7: ...Series 35 67 24 VAC Hot Surface Ignition Control Page 7 www fenwalcontrols com 1 800 FENWAL 1 DIMENSIONS Figure 6 Figure 7 ...

Page 8: ...ge 30 Interpurge 30 Postpurge Full Time Power 7 0 Prepurge 15 Interpurge 15 Postpurge Full Time Power 8 0 Prepurge 30 Interpurge 30 Postpurge Full Time Power Tries For Ignition 0 Single Try Local Sense Recycle On Flame Loss 1 Single Try Remote Sense Recycle On Flame Loss 2 Single Try Local Sense Lockout On Flame Loss 3 Single Try Remote Sense Lockout On Flame Loss 5 Three Tries Local Sense Recycle...